5-116

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


9.

Repeat above steps until you have assigned the desired parameters to

all the traces from Trace1 to Trace16.


10.

Now press F9 [TRIGGER] key. The first letter in the second line on

the screen will toggle between C and S. The letter C stands for
Continuous and S stands for Single shot. Select S for single shot

.


11.

Press F2 [CONDITION] key. The cursor will move to the “=” equal

sign. This defines the trigger condition. Press up or down arrow keys
to select + sign as the trigger condition for our example.

12.

Press F3 [DATA] key. The cursor moves to the data field. In our

example we will enter 8 and then press Enter key.

13.

Press F4 [RATE] key. The cursor moves to the rate field. Here we

will enter 0, which is the fastest sample rate (1 msec/sample) and then
press Enter key.

Setting up Diagnostic
Trending (cont.)