Ground filter component replacement – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 281

Advertising
background image


Component Definition and Maintenance 5-39

7000 “A” Frame

7000A-RM001A-EN-P – January 2011

Ground Filter Component Replacement


The number of capacitors will vary depending on the system voltage.

1. Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main
power has been disconnected before working on
the capacitor. Verify that all circuits are voltage
free using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in
injury or death.

2. Note the position of the leads.

3. Disconnect the leads connected to the failed capacitor/resistor bank.

4. Loosen and remove mounting screws as indicated in Figure 5.33 and

remove the failed component.

5. Assemble the new component in the reverse order of disassembly.

6. Reattach the leads strictly adhering to the torque requirements

outlined below.

I M P O R T A N T

I M P O R T A N T

The maximum torque for the capacitor terminal
is 3.4 Nm (30 lb-in).

Reactor Transformer

Reactor Transformer

Barrier

Resistor Bank

Capacitors

Figure 5.33 – Ground Filter Component Replacement

Advertising