Grounding practices (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 72

Advertising
background image

2-42

Drive Installation

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


Grounding Practices (cont.)

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

Figure 2.27 – Ground Connection Diagram with Isolation Transformer

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

Figure 2.28 – Ground Connection Diagram with Line Reactor


Each power feeder from the substation transformer to the drive must
be provided with properly sized ground cables. Utilizing the conduit
or cable armor as a ground is not adequate.

Note that if a drive isolation transformer is used, the WYE secondary
neutral point should not be grounded.


Each AC motor frame must be bonded to grounded building steel
within 6 m (20 feet) of its location and tied to the drive's ground
bus via ground wires within the power cables and/or conduit. The
conduit or cable armor should be bonded to ground at both ends.