5-20

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


4. Remove the device (SGCT) that is secured to the heatsink with the

thermal sensor. (Refer to Figure 5.11, 5.12, 5.13, 5.16 or 5.17).

5. Disconnect the fiber optic cable to the temperature feedback board.

6. Remove two M8 screws holding the heatsink in place.

7. Remove the heatsink with the temperature feedback board from the

PowerCage.

8. Disconnect the plug that connects the thermal sensor to the circuit

board.

9. Remove the screw that attaches the thermal sensor to the heatsink.

10. Replace with the new thermal sensor and cable assembly.

11. Note there is a small voltage difference between the thermal sensor

and its heatsink. For proper function, it is essential to mount the small
insulating pad between the thermal sensor and the heatsink and the
insulating bushing between the thermal sensor mounting screw and
the thermal sensor (see Figure 5.17).

12.

Replacement of the heatsink with the new thermal sensor is in the

reverse order of removal.

13.

Follow procedure “Uniform Clamping Pressure” to ensure the

heatsinks are clamped to a uniform pressure.

Insulating bushing

Mounting pad

Temperature feedback

circuit board

Mounting screw

Thermal sensor and

cable assembly

Figure 5.17 – Replacing the Thermal Sensor

Temperature Sensing
(cont.)