Commissioning 4-81

7000 “A” Frame

7000A-RM001A-EN-P – January 2011

Summary:

• Drive input contactor should be closed. If the drive input

contactor configuration is set to NOT RUNNING, you will have
to temporarily change it to ALL FAULTS.

• Ensure that the drive is not running when capturing these

waveforms.

• Capture line voltage at ACB test point “V2uv” and line current

at ACB test point “I2u”.

• Label the waveforms as “V2uv”, and “I2u”.

• Save the worksheet as “Harmonics (Drive Not Running)”.

Table 4.E – Oscilloscope Setting

Oscilloscope

Time Base

Waveform

Test-

Point

Waveform

Label

Sheet Name

Ch. 1

Line

Voltage

V2uv

V2uv

Ch. 2

10ms/div.

Line

Current

I2u

I2u

Harmonics

(Drive Not

Running)

Sample

Waveforms

Sample waveforms captured on SCBL test points under Drive Not Running
Condition [Ch1: V2uv, Ch2: I2u]