Surge arresters (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 254

Advertising
background image



5-12

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

Surge Arresters (cont.)

Surge Arresters

Figure 5.10 – Surge Arresters

Note: When the surge arrester is disconnected from MV, it is possible
that a small amount of static charge is retained by the arrester. As a
precautionary measure, install a temporary ground on the line-end of the
arrester and discharge the stored energy. Remove temporary ground
before the arrester is reinstalled. To avoid electrical shock when removing
the arrester from service, consider it to be fully energized until both the
line and ground leads are disconnected.

Field Test and Care

No field testing is necessary. The arresters do not require special care.
However at very dusty sites, it is suggested to clean the arrester when the
whole drive is cleaned.