Printed circuit board replacement – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual
Page 315

Component Definition and Maintenance 5-73
7000 “A” Frame
7000A-RM001A-EN-P – January 2011
M4 (P.H.M.S.) and
nylon shoulder washer
Mounting plate
Black insulation
Part ID label
DC/DC
Power Supply
M6 (H.H.T.R.S.)
VIEW “1”
VIEW “2”
Figure 5.57 – Replacement of DC/DC power supply
The replacement of printed circuit boards should be handled in a careful
manner.
There are some basic precautions that should be taken. They include the
following:
Remove all power to the drive.
Do not remove the replacement board from the anti-static bag until
necessary.
Use anti-static wrist strap, grounded in the Low Voltage Control
Section
There are no direct screw/terminal connections on any of the Low Voltage
circuit boards. All wire/terminal connections are made with plugs that
plug into the circuit boards. This means that changing boards only
requires the removal of the plugs, minimizing the chance of mistakes
when reconnecting all of the wiring.
Printed Circuit Board
Replacement