4-86 Commissioning

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

While simulating a synchronous transfer to determine the best lead
angle:
• Make sure the Diagnostic Trend has been setup and is armed.

• Capture motor voltage at ACB test point “Vuv” & bypass

voltage at ACB test point “Vuvs”.

• Capture and trigger on falling edge of the DC Link current

waveform at ACB test point “Idc1”.

• Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.

• Save the worksheet as “Drift @ 15 Degree Lead Angle”,

for example.

Table 4.I – Oscilloscope Setting

Oscilloscope

Time Base

Waveform

Test-Point

Waveform

Label

Ch. 1

DC Link Current

Idc1

Idc1

Ch. 2

Motor Voltage

Vuv

Vuv

Ch. 3

10ms/div.

Bypass Line

Voltage

Vuvs Vuvs


Synchronous Transfer Test to verify Sync Lead Angle (50Hz System)

Ch1:

Idc1 (black), Ch2: Vuv (red), Ch3: Vuvs (blue)