Using the Human Interface Module (HIM)

B-13

Downloading a Parameter Profile

To download a parameter profile from the remote HIM to a drive:

The download function is only available when a valid profile is stored
in the HIM.

1. From the EEProm mode prompt, press the increment up key or

the decrement down key until “HIM

Drive” is displayed.

2. Press enter. A profile name (up to 14 characters) is displayed on

line 2 of the HIM.

3. Press the increment up key or the decrement down key to scroll

to a second profile (if available).

4. Press enter when the desired profile name is displayed. An

information display is shown that indicates the version numbers of
the profile and the drive.

5. Press enter to start the download. The parameter number currently

being downloaded is displayed on line I of the HIM. Line 2
indicates the total progress. Press ESC to stop the download.

6. Press enter when “COMPLETE” is displayed on line 2. If line 2

reports ‘ERROR”, refer to the following table.

If you receive this
error:

Then:

Error 1

An EEPROM CRC error occurred.

Error 2

The profile is a different length than the master.

Error 3

You are downloading between different types of masters.

Error 4

The data is out or range or illegal

Error 5

You attempted the download while the drive was running.

Error 6

You are downloading between different types of masters.