Publication 8720MC-IN002A-EN-P — December 2002

1-6

Commissioning Your 8720MC SERCOS Interface Drive

Figure 1.5
Fiber-Optic Ring Connection Example

Note: You can mount two 1756-MxxSE SERCOS interface modules

in two separate ControlLogix chassis or you can mount them
in the same chassis (as shown above).

Utilizing two 1756-MxxSE SERCOS interface modules allows
you to reduce the SERCOS ring cycle times.

4. Set the SERCOS baud rate using DIP switches 2 and 3, as shown in

Figure 1.6. Refer to the table below for baud rate switch settings.
Refer to Figure 1.1 for the baud rate (DIP) switch location.

5. Set the SERCOS optical power level to High using DIP switch 1, as

shown in Figure 1.6. Refer to the table below for optical power
level switch settings. Refer to Figure 1.1 for the optical power
switch location.

Figure 1.6
SERCOS Baud Rate and Optical Power DIP Switches

1756-MxxSE SERCOS
Interface Module

ControlLogix Chassis

SERCOS Fiber-Optic Ring

8720MC
High Performance
Drive
Node Address = 01

8720MC

High Performance

Drive

Node Address = 02

Receive

Transmit

Receive

Transmit

Receive

Transmit

For this baud rate:

Set switch 2: Set switch 3:

4M baud

OFF

ON

8M baud

ON

OFF

For this optical power level:

Set switch 1:

Low

OFF

High

ON

1 2 3

1 2 3

DIP switches set for

4M baud applications

DIP switches set for

8M baud applications

ON

OFF

ON

OFF