Publication 8720MC-IN002A-EN-P — December 2002

3-18

Troubleshooting Your 8720MC Servo Drive

Using Analog Test Points to Monitor System Variables

There are two analog output test points accessible from the P4
connector (refer to Figure 1.1 for connector location).

Figure 3.6
Pin Orientation for P4 Connector

Refer to the 8720MC High Performance Drives Installation Manual
(publication 8720MC-IN001x-EN-P) for analog output specifications.

Refer to Appendix C for a description of the analog output parameters
(Analog Outputs 1 and 2) under parameters 681 and 683. Each analog
output has an scaling parameter associated with it (parameters 682
and 684). The analog outputs can be changed from there default
linkages in the same way as the digital outputs.

Use the two analog output test points to monitor system variables, as
shown in the table below.

The value entered in Scale Parameter will scale the analog output so
that you can get a full scale reading of the specific parameter for the
dynamic range or values you are testing.

P4 Pin

Description

Signal

P4-1

Analog Output 1

ANAOUT_CH1

P4-6

Analog Output Common

ANA_COM

P4-5

Analog Output 2

ANAOUT_CH2

P4-6

Analog Output Common

ANA_COM

P4 Connector
(8720MC Control Board)

Analog
Output

Controlling Parameter

Scale Parameter

Parameter Number

Default Value

Parameter Number

Default Value

1

0681

0040

0682

0.0060

2

0683

0084

0684

0.1000