Publication 8720MC-IN002A-EN-P — December 2002

1-8

Commissioning Your 8720MC SERCOS Interface Drive

6. Select Controller Properties in the edit menu. The Controller

Properties window opens.

7. Select the Date and Time tab.

8. Check the box Make this controller the Coordinated System

Time master.

9. Select OK.

10. Right-click on I/O Configuration in the explorer window and

select New Module. The Select Module Type window opens.

11. Select 1756-MxxSE as appropriate for your actual hardware

configuration.

12. Select OK. The Module Properties wizard opens.

Name the module

Select the slot where your module resides (left most slot = 0)

Select an Electronic Keying option (select Disable Keying if
unsure)

IMPORTANT

Only one ControlLogix processor can be
assigned as the Coordinated System Time master.