Troubleshooting Your 8720MC Servo Drive

Parameters 691 and 692 - Analog Input 1 Value and Analog
Input 2 Value

These parameters may be used to display the analog inputs as the
8720MC sees them. The scaling is.00% to 100.00% where 100% = 10
volts. The displayed values include the associated analog offsets,
Parameters 693 and 694.

Troubleshooting SCANport
I/O

Two parameters are available to monitor the SCANport command and
status information exchange, parameters 717 and 718.

Parameter 717 - SCANport Logic Command

A SCANport peripheral gateway device such as an A-B PLC can initiate
drive activity via the SCANport Logic Command word. The structure of
parameter 717 is as follows. The 12 character command messages are
shown in italics.

If any bit is true the function is selected.

Bit 0: Regenerative stop request - “Regen Stop

Bit 1: Start request - “Start

Bit 2: Jog request - “Jog

Bit 3: Clear fault request - “Fault Clear”

Bit 4: Coast stop request - “Coast Stop

Bit 5: Parameter Set Select bit 0 - “Parmset Bit0

Bit 6: Parameter Set Select bit 1 - “Parmset Bit1”

Bit 7: Parameter Set Select bit 2 - “Parmset Bit2”

Bit 8: Parameter Set Strobe - “Parmset Chg

Bit 9: Orient Request - “Orient Req

Bit 10: Home request - “Home Req

Bit 11: Manual/Auto request - “Man Mode Req

Bits 12 to 15 are reserved: