Rockwell Automation 8720MC Drives Integration Manual User Manual

Page 25

Advertising
background image

Publication 8720MC-IN002A-EN-P — December 2002

Commissioning Your 8720MC SERCOS Interface Drive

1-13

3. Apply three-phase input power to the 8720MC-RPS. Refer to the

8720MC Regenerative Power Supply User Manual (publication
8720MC-RM001x-US-P) for power up procedure and
troubleshooting.

4. Wait for 8720MC-RPS to finish initialization and close the (MC)

contactor. Bus voltage is now supplied to 8720MC drive.

5. Observe the Drive Status LED.

6. Observe the SERCOS Network Status LED.

7. Observe the three SERCOS LEDs on the 1756-MxxSE module.

If the Drive Status LED is:

Status:

Do This:

Flashing green

Normal condition

Go to step 6.

Flashing red

Drive is faulted

Go to the chapter Troubleshooting
Your 8720MC Servo Drive
.

If the Network Status LED is:

Status:

Do This:

Flashing green

Establishing communication
with network

Wait for steady green.

Steady green

Communication is ready

Go to step 7.

Flashing red

No communication

Go to the chapter Troubleshooting
Your 8720MC Servo Drive
.

If the three SERCOS LEDs are: Status:

Do This:

Flashing green and red

Establishing communication

Wait for steady green on all three
LEDs.

Steady green

Communication ready

Go to Testing and Tuning Your
Axes
.

Not flashing or steady green

1756-MxxSE module is
faulted

Go to the ControlLogix Motion
Module Setup and Configuration
Manual
(publication
1756-UM006x-EN-P) for specific
instructions and troubleshooting.