Rockwell Automation 8720MC Drives Integration Manual User Manual

Page 161

Advertising
background image

Publication 8720MC-IN002A-EN-P — December 2002

Programming Parameters

C-49

Name: AuxFdbk_Type

Data Type: ASCII Characters

R/W

Parameter No.
503
File:
Motor/Drive/
Fdbk
Group:
Aux Feedback

Description: The feedback type for a machine mounted feedback device is found in parameter 115. The
resolution of the machine mounted feedback device is found in parameter 117 for both rotary and linear devices.
Parameter 503 is used to provide additional auxiliary feedback information.

Structure of motor feedback type:

Bits: 3-0: 0000 = No Feedback

0001 = SRS_60

Single turn absolute 1024 S/C per rev

0010 = SRM_60

Multi-turn absolute 1024 S/C per rev

0011 = SCS_60

Single turn absolute 512 S/C per rev

0100 = SCM_60

Multi-turn absolute 512 S/C per rev

0101 = SNS_60

High resolution incremental 1024 S/C per rev

1000 = Analog Reference

+/- 10V dc differential

1001 = Sin/Cos

Generic linear or rotary S/C device w/index

1010 = TTL

Generic linear or rotary TTL A quad B device w/index

Analog reference must be chosen whenever the drive is configured for an analog command reference.
See parameter 500

Default:
Analog Ref

Length
2 bytes

Minimum/Maximum
N/A

Scaling Resolution
N/A

Units
N/A

Name: Posn_Integ_Err

Data Display: Signed Decimal

R

Parameter No.
515
File:
Control
Group:
Position

Description: This parameter contains the position loop integral gain multiplied by the integrator. This is the
integrator’s contribution to the velocity command.

Default:
6000

Length
2 bytes

SCANport Min/Max
Min.

≥ 0

Max.

≤ +30,000

SCANport Scaling Resolution
1 = 1RPM

Units
RPM

Default:
0.0

Length
4 bytes

SERCOS/DPI Min/Max

Min.

≥ -2

31

Max.

≤ +2

31

- 1

SERCOS/DPI Scaling Resolution
Scaling type: parameter 44
Scaling factor: parameter 45
Scaling exponent: parameter 46

Units
parameter
44