Start-up troubleshooting procedures, Start-up troubleshooting procedures -2 – Rockwell Automation 8720MC Drives Integration Manual User Manual

Page 56

Advertising
background image

Publication 8720MC-IN002A-EN-P — December 2002

3-2

Troubleshooting Your 8720MC Servo Drive

Start-up Troubleshooting
Procedures

Before installing fuses into the AC input lines of the drive or
regenerative power supply, if supplied, first check that the incoming
AC voltage falls within the range of 324 to 505 Vrms across each of the
three phases. Make sure the AC or DC power inputs are properly
wired per the 8720MC High Performance Drive Installation Manual
(publication 8720MC-IN001x-EN-P). Also make sure the motor and
feedback devices are wired using the recommended shielded cables.
For the feedback cables make sure there is continuity between the
motor and drive connectors. Make sure the Weidmueller connector
spring clamps are clamped to the wire and not the insulation.

If you are using an 8720MC Regenerative Power Supply, refer to the
8720MC Regenerative Power Supply User Manual (publication
8720MC-RM001x-US-P) for configuration and startup information.

After power is applied to the drive the first thing to observe is the
status of the control board LEDs and the HIM display on the drive.
There are two LEDs on the control board. If you have an enclosed
8720MC Drive you must first remove the cover to observe the LEDs.
The left LED is used to indicate the status of the drive control board.
The right LED indicates the status of the SERCOS ring. The table
below indicates how these LED’s should be interpreted.

Fault messages can be displayed on the HIM, or on a PC running
DriveExplorer or RSLogix 5000 if used with SERCOS.

LED Name

LED Status

Potential Cause

Possible corrective action

Drive Status

Not Illuminated

There is no power to the Control
Board

Check the incoming AC power for AC input drives or the
incoming DC power DC for common bus drives

Drive Status

Steady Red

Malfunctioning Control Board

Software or hardware failure. Replace the Control
Board

Drive Status

Flashing Red

A fault has occurred in the
system

Verify wiring. Use the HIM fault log or DriveExplorer to
investigate the fault

Drive Status

Alternating red
and greens

DC bus is not up

Check 3 phase AC incoming or DC incoming power

Drive Status

Flashing Green

There are no faults and the DC
bus is up but the enable input is
not being detected. As a
consequence no torque is being
applied to the motor.
The drive may be in manual
mode and the jog button has not
been depressed.

• Check if +24V dc is on the enable input
• Check the run output from the RPS
• Check the enable output from the Motion Controller
• Check the enable input wiring.
• Recycle the enable
• If in manual mode depress jog button.

Drive Status

Steady Green

Drive is enabled.

No corrective action

SERCOS
Network Status

Flashing Red

There is a SERCOS ring
communication error.

Make sure the fibre optic ring is connected at all nodes
on the ring and that power is on all the nodes. Make
sure power is on the master.

SERCOS
Network Status

Steady Green

Normal operation

No corrective action

SERCOS
Network Status

Green Flashing

Establishing communications

No corrective action