override. Recovery is automatic. Reason for error is either a

faulty sensor, wiring error, or damaged input on the MBB con-

trol board. This error only occurs when the unit is configured

for minimum position override and a 4-20 mA signal is not

present.
T245 (Outside Air Cfm Sensor Failure) — If the outside air cfm

sensor (Inputs

CFM

O.CFM) fails, the economizer will de-

fault to discrete positioning of the economizer (Configuration

IAQ

DCV.C

IAQ.M, Configuration

Econ

EC.MN).

Recovery is automatic. Reason for error is either a faulty sensor,

wiring error, or damaged input on the CEM control board.
T246 (Supply Air Cfm Sensor Failure) — If the supply air

cfm sensor (Inputs

CFM

S.CFM) fails, fan tracking is not

possible and the system will shut down. Recovery is automatic.

Reason for error is either a faulty sensor, wiring error, or dam-

aged input on the ECB control board.
T247 (Return Air Cfm Sensor Failure) — If the return air

cfm sensor (Inputs

CFM

R.CFM) fails, fan tracking is not

possible and the system will shut down. Recovery is automatic.

Reason for error is either a faulty sensor, wiring error, or dam-

aged input on the ECB control board.
T300 (Space Temperature Below Limit) — If the space tem-

perature is below the configurable SPT Low Alert Limits (occu-

pied [Configuration

ALLM

SP.L.O] for 5 minutes or

unoccupied [Configuration

ALLM

SP.L.U] for 10 min-

utes), then an alert will be broadcast. The alert will automatically

reset.
T301 (Space Temperature Above Limit) — If the space tem-

perature is above the configurable SPT High Alert Limits

(occupied [Configuration

ALLM

SP.H.O] for 5 minutes or

unoccupied [Configuration

ALLM

SP.H.U] for 10 min-

utes), then an alert will be broadcast. The alert will automati-

cally reset.
T302 (Supply Temperature Below Limit) — If the supply-air

temperature measured by the supply temperature sensor is below

the configurable SAT LO Alert Limit/Occ (Configuration

ALLM

SA.L.O) for 5 minutes or the Low Supply air tempera-

ture alert limit unoccupied mode (Configuration

ALLM

SA.L.U) for 10 minutes, then an alert will be broadcast.
T303 (Supply Temperature Above Limit) — If the supply

temperature is above the configurable SAT HI Alert Limit Occ

(Configuration

ALLM

SAH.O) for 5 minutes or the SAT

HI Alert Limit/Unocc (Configuration

ALLM

SA.H.U) for

10 minutes, then an alert will be broadcast. The alert will auto-

matically reset.
T304 (Return Air Temperature Below Limit) — If the re-

turn air temperature measured by the RAT sensor is below the

configurable RAT LO Alert Limit/Occ (Configuration

ALLM

RA.L.O) for 5 minutes or RAT HI Alert Limit/Occ

(Configuration

ALLM

RA.L.U) for 10 minutes, then an

alert will be broadcast.
T305 (Return Air Temperature Above Limit) — If the return

air temperature is below the RAT HI Alert Limit/Occ (Configu-

ration

ALLM

RA.H.O) for 5 minutes or RAT HI Alert

Limit/Occ (Configuration

ALLM

RA.H.U) for 10 minutes,

then an alert will be broadcast. The alert will automatically reset.
T308 (Return Air Relative Humidity Below Limit) — If the

unit is configured to use a return air relative humidity sensor

through the Return Air RH Sensor (Configuration

UNIT

SENS

RRH.S) setting, and the measured level is below the

configurable RH Low Alert Limit (Configuration

ALLM

R.RH.L) for 5 minutes, then the alert will occur. The unit will

continue to run and the alert will automatically reset.
T309 (Return Air Relative Humidity Above Limit) — If the

unit is configured to use a return air relative humidity sensor

through the Return Air RH Sensor (Configuration

UNIT

SENS

RRH.S) setting, and the measured level is above the

configurable RH High Alert Limit (Configuration

ALLM

R.RH.H) for 5 minutes, then the alert will occur. Unit will con-

tinue to run and the alert will automatically reset.
T310 (Supply Duct Pressure Below Limit) — If the unit is a

VAV unit with a supply duct pressure sensor and the measured

supply duct static pressure (Pressures

AIR.P

SP) is below

the configurable SP Low Alert Limit (Configuration

ALLM

SP.L) for 5 minutes, then the alert will occur. The unit will

continue to run and the alert will automatically reset.
T311 (Supply Duct Pressure Above Limit) — If the unit is a

VAV unit with a supply duct pressure sensor and the measured

supply duct static pressure (Pressures

AIR.P

SP) is above

the configurable SP Low Alert Limit (Configuration

ALLM

SP.H) for 5 minutes, then the alert will occur. The unit will

continue to run and the alert will automatically reset.
T312 (Building Static Pressure Below Limit) — If the unit

is configured to use modulating power exhaust then a

building static pressure limit can be configured using the BP

Low Alert Limit (Configuration

ALLM

BP.L). If the mea-

sured pressure (Pressures

AIR.P

BP) is below the limit for

5 minutes then the alert will occur.
T313 (Building Static Pressure Above Limit) — If the unit

is configured to use modulating power exhaust then a

building static pressure limit can be configured using the BP HI

Alert Limit (Configuration

ALLM

BP.H). If the measured

pressure (Pressures

AIR.P

BP) is above the limit for

5 minutes, then the alert will occur.
T314 (IAQ Above Limit) — If the unit is configured to use a

CO

2

sensor and the level (Inputs

AIR.Q

IAQ) is above the

configurable IAQ High Alert Limit (Configuration

ALLM

IAQ.H) for 5 minutes then the alert will occur. The unit will

continue to run and the alert will automatically reset.

FULL

2/3

1/2

1/3

UNTIL CHARGE

450

400

350

300

250

200

150

20

40

60

80

100

SUCTION PRESSURE (PSIG)

DISCHARGE PRESSURE (PSIG)

Fig. 14 — Differential Pressure Chart