Table 35 — Setpoints

Table 36 — Supply Air Reset Configuration

Table 37 — Cooling Configuration

CSB A2 Feedback Alarm (CS.A2) — This configuration is

used to enable or disable the compressor A2 feedback alarm

(105 ton size units only). This configuration must be enabled at

all times for 105 ton units.
CSB B1 Feedback Alarm (CS.B1) — This configuration is

used to enable or disable the compressor B1 feedback alarm

(105 ton size units only). This configuration must be enabled at

all times for 105 ton units.
CSB B2 Feedback Alarm (CS.B2) — This configuration is

used to enable or disable the compressor B2 feedback alarm

(105 ton size units only). This configuration must be enabled at

all times for 105 ton units.
Compressor A1 High Pressure Switch Trip (HPS.A) — This

configuration is used when high-pressure switches are used.

This is true for all units except the 105 ton size units which

incorporate current sensor boards (CSB). In the case of a high-

pressure switch trip on compressor A1, the control will sample

the discharge pressure on circuit A and store this value minus

3 psig and attempt to catch this failure the next time before the

switch trips. The value is modifiable by the user but will still

get overriden if the control does not catch a high pressure

condition before the switch trips.
Compressor B1 High Pressure Switch Trip (HPS.B) — This

configuration is used when high-pressure switches are used.

This is true for all units except the 105 ton size units which

incorporate current sensor boards (CSB). In the case of a

high-pressure switch trip on compressor B1, the control will

sample the discharge pressure on circuit B and store this value

minus 3 psig and attempt to catch this failure the next time

before the switch trips. The value is modifiable by the user but

will still get overriden if the control does not catch a high

pressure condition before the switch trips.
High SST Alert Delay Time (H.SST) — This option allows

the low saturated suction temperature alert timing delay to be

adjusted.
COOL MODE SELECTION PROCESS — The Z Series

ComfortLink™ controls offer three distinct methods by which

they may select a cooling mode.

1. Thermostat (C.TYP=3 and 4): The thermostat does not

depend upon the state of occupancy or temperature and

the modes are called out directly by the discrete inputs

(Inputs

STAT

Y1 and Y2).

2. VAV cooling types (C.TYP=1 and 2) are called out

in the occupied period (Operating Modes

MODE

OCC=ON).

3. VAV cooling types (C.TYP=1 and 2) are called out in the

unoccupied period (Operating Modes

MODE

OCC=OFF). They are also used for space sensor control

types (C.TYP=5 and 6) in both the occupied and unoccu-

pied periods.

This section is devoted to the process of cooling mode

determination for the three types outlined above.

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

OHSP

Occupied Heat Setpoint

40-99

dF

OHSP

68

OCSP

Occupied Cool Setpoint

40-99

dF

OCSP

75

UHSP

Unoccupied Heat Setpoint

40-99

dF

UHSP

55

UCSP

Unoccupied Cool Setpoint

40-110

dF

UCSP

90

GAP

Heat-Cool Setpoint Gap

2-10

deltaF

HCSP_GAP

5

V.C.ON

VAV Occ. Cool On Delta

0-25

deltaF

VAVOCON

3.5

V.C.OF

VAV Occ. Cool Off Delta

1-25

deltaF

VAVOCOFF

2

SASP

Supply Air Setpoint

45-75

dF

SASP

55

SA.HI

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

SA.LO

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

SA.HT

Heating Supply Air Setpt

90-145

dF

SASPHEAT

85

T.PRG

Tempering Purge SASP

–20-80

dF

TEMPPURG

50

T.CL

Tempering in Cool SASP

5-75

dF

TEMPCOOL

5

T.V.OC

Tempering Vent Occ SASP

–20-80

dF

TEMPVOCC

65

T.V.UN

Tempering Vent Unocc. SASP

–20-80

dF

TEMPVUNC

50

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

EDT.R

EVAP.DISCHRGE TEMP RESET

RS.CF

EDT Reset Configuration

0 - 3

EDRSTCFG

2

RTIO

Reset Ratio

0 - 10

RTIO

2

LIMT

Reset Limit

0 - 20

deltaF

LIMT

10

RES.S

EDT 4-20 ma Reset Input

Enable/Disable

EDTRSENS

Disable

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

COOL

COOLING CONFIGURATION

Z.GN

Capacity Threshold Adjst

–10 - 10

Z_GAIN

1

MC.LO

Compressor Lockout Temp

–25 - 55

dF

OATLCOMP

40

L.L.EN

Lead/Lag Operation ?

Yes/No

LLENABLE

No

M.M.

Motor Master Control ?

Yes/No

MOTRMAST

No

HPSP

Head Pressure Setpoint

80 - 150

dF

HPSP

113

A1.EN

Enable Compressor A1

Enable/Disable

CMPA1ENA

Enable

A2.EN

Enable Compressor A2

Enable/Disable

CMPA2ENA

Enable

B1.EN

Enable Compressor B1

Enable/Disable

CMPB1ENA

Enable

B2.EN

Enable Compressor B2

Enable/Disable

CMPB2ENA

Enable

CS.A1

CSB A1 Feedback Alarm

Enable/Disable

CSB_A1EN

Enable

CS.A2

CSB A2 Feedback Alarm

Enable/Disable

CSB_A2EN

Enable

CS.B1

CSB B1 Feedback Alarm

Enable/Disable

CSB_B1EN

Enable

CS.B2

CSB B2 Feedback Alarm

Enable/Disable

CSB_B2EN

Enable

HPS.A

CMPA1 Hi.Pr.Sw. Trip

365 - 415

PSIG

HPSATRIP

415

HPS.B

CMPB1 Hi.Pr.Sw. Trip

365 - 415

PSIG

HPSBTRIP

415

H.SST

Hi SST Alert Delay Time

5 - 30

min

HSSTTIME

10