Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 66

Advertising
background image

66

Table 56 — Economizer Configuration Table

The enthalpy switch may also be field converted to a differ-

ential enthalpy switch by field installing an enthalpy sensor

(33CSENTSEN or HH57ZC001). The enthalpy switch/receiv-

er remains installed in its factory location to sense outdoor air

enthalpy. The additional enthalpy sensor (33CSENTSEN) is

mounted in the return airstream to measure return air enthalpy.

The enthalpy control jumper must be changed from M1 to M2

for differential enthalpy control. For the 2-wire return air en-

thalpy sensor, connect power to the Vin input and signal to the

4-20 loop input. See Fig. 8 for diagram showing the settings

and inputs on the enthalpy switch.

There is another way to accomplish differential enthalpy

control when both an outdoor and return air relative humidity

sensor are present. See Economizer Changeover Select section

below for further information.
ECONOMIZER CHANGEOVER SELECT (E.SEL) — The

control is capable of performing any one of the following

changeover types in addition to both the dry bulb lockout and

the standard external input:
E.SEL = 0

none

E.SEL = 1

Differential Dry Bulb Changeover

E.SEL = 2

Outdoor Enthalpy Changeover

E.SEL = 3

Differential Enthalpy Changeover

Differential Dry Bulb Changeover — As both return air and

outside air temperature sensors are installed as standard on

these units, the user may select this option, E.SEL = 1, to

perform a qualification of return and outside air in the enabling/

disabling of free cooling. If this option is selected and outside-

air temperature is greater than return-air temperature, free

cooling will not be allowed.
Outdoor Enthalpy Changeover — This option should be used

in climates with higher humidity conditions. The Z Series

control can use an enthalpy switch or enthalpy sensor, or the

standard installed outdoor dry bulb sensor and an accessory

relative humidity sensor to calculate the enthalpy of the air.

Setting Configuration

ECON

E.SEL = 2 requires that

the user configure Configuration

ECON

OA.E.C, the

Outdoor Enthalpy Changeover Select, and install an outdoor

relative humidity sensor. A control expansion module (CEM)

is required. Once the sensor and board are installed, enable

Configuration

ECON

ORH.S, the outdoor relative humid-

ity sensor configuration option. This will automatically enable

the CEM board, if it is not enabled already.

If the user selects one of the Honeywell curves, A,B,C or D,

then OA.E.C options 1-4 should be selected. See Fig. 9 for a

diagram of these curves on a psychrometric chart.
OA.E.C = 1

Honeywell A Curve

OA.E.C = 2

Honeywell B Curve

OA.E.C = 3

Honeywell C Curve

OA.E.C = 4

Honeywell D Curve

OA.E.C = 5

custom enthalpy curve

If the user selects OA.E.C = 5, a direct compare of outdoor

enthalpy versus an enthalpy set point is done. This outdoor

enthalpy set point limit is configurable, and is called

Configuration

ECON

OA.EN.

Depending on what Configuration

ECON

OA.E.C is

configured for, if the outdoor enthalpy exceeds the Honeywell

curves or the outdoor enthalpy compare value (Configuration

ECON

OA.EN), then free cooling will not be allowed.

NOTE: If the user wishes to disable the standard enthalpy

control from running concurrently, a field-supplied jumper

must be installed between TB201 terminals 3 and 4.
Differential Enthalpy Changeover — This option compares

the outdoor-air enthalpy to the return air enthalpy and chooses

the option with the lowest enthalpy. This option should be

used in climates with high humidity conditions. This option

uses both humidity sensors and dry bulb sensors to calculate

the enthalpy of the outdoor and return air. An accessory

outdoor air humidity sensor (ORH.S) and return air humidity

sensor (RRH.S) are used. The outdoor air relative humidity

sensor config (ORH.S) and return air humidity sensor config

(Configuration

SENS

RRH.S) must be enabled.

NOTE: If the user wishes to disable the standard enthalpy

control from running concurrently, a field-supplied jumper

must be installed between TB201 terminals 3 and 4.
Outdoor Dewpoint Limit Check — If an outdoor relative

humidity sensor is installed, the control is able to calculate the

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

EC.EN

Economizer Installed?

Yes/No

ECON_ENA

Yes

EC2.E

Econ.Act.2 Installed?

Yes/No

ECON_TWO

No

EC.MN

Economizer Min.Position

0 - 100

%

ECONOMIN

5

EC.MX

Economizer Max.Position

0 - 100

%

ECONOMAX

98

E.TRM

Economzr Trim For SumZ ?

Yes/No

ECONTRIM

Yes

E.SEL

Econ ChangeOver Select

0 - 3

ECON_SEL

0

OA.E.C

OA Enthalpy ChgOvr Selct

1 - 5

OAEC_SEL

4

OA.EN

Outdr.Enth Compare Value

18 - 28

OAEN_CFG

24

OAT.L

High OAT Lockout Temp

-40 - 120

dF

OAT_LOCK

60

O.DEW

OA Dewpoint Temp Limit

50 - 62

dF

OADEWCFG

55

ORH.S

Outside Air RH Sensor

Enable/Disable

OARHSENS

Disable

CFM.C

OUTDOOR AIR CFM CONTROL

OCF.S

Outdoor Air CFM Sensor

Enable/Disable

OCFMSENS

Disable

O.C.MX

Economizer Min.Flow

0 - 20000

CFM

OACFMMAX

2000

O.C.MN

IAQ Demand Vent Min.Flow

0 - 20000

CFM

OACFMMIN

0

O.C.DB

Econ.Min.Flow Deadband

200 - 1000

CFM

OACFM_DB

400

E.CFG

ECON.OPERATION CONFIGS

E.P.GN

Economizer Prop.Gain

0.7 - 3.0

EC_PGAIN

1

E.RNG

Economizer Range Adjust

0.5 - 5

^F

EC_RANGE

2.5

E.SPD

Economizer Speed Adjust

0.1 - 10

EC_SPEED

0.75

E.DBD

Economizer Deadband

0.1 - 2

^F

EC_DBAND

0.5

UEFC

UNOCC.ECON.FREE COOLING

FC.CF

Unoc Econ Free Cool Cfg

0-2

UEFC_CFG

0

FC.TM

Unoc Econ Free Cool Time

0 - 720

min

UEFCTIME

120

FC.L.O

Un.Ec.Free Cool OAT Lock

40 - 70

dF

UEFCNTLO

50

ACT.C

ECON.ACTUATOR CONFIGS

SN.1.1

Econ Serial Number 1

0 - 255

ECON_SN1

0

SN.1.2

Econ Serial Number 2

0 - 255

ECON_SN2

0

SN.1.3

Econ Serial Number 3

0 - 255

ECON_SN3

0

SN.1.4

Econ Serial Number 4

0 - 255

ECON_SN4

0

SN.1.5

Econ Serial Number 5

0 - 255

ECON_SN5

0

C.A.L1

Econ Ctrl Angle Lo Limit

0 - 90

ECONCALM

85

SN.2.1

Econ 2 Serial Number 1

0 - 255

ECN2_SN1

0

SN.2.2

Econ 2 Serial Number 2

0 - 255

ECN2_SN2

0

SN.2.3

Econ 2 Serial Number 3

0 - 255

ECN2_SN3

0

SN.2.4

Econ 2 Serial Number 4

0 - 255

ECN2_SN4

0

SN.2.5

Econ 2 Serial Number 5

0 - 255

ECN2_SN5

0

C.A.L2

Econ 2 Ctrl Angle Lo Limit

0 - 90

ECN2CALM

85