Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 68

Advertising
background image

68

Control Angle Alarm Configuration — The economizer ac-

tuator determines its end stops through a calibration at the

factory. Field-installed actuators may be calibrated in the

Service Test mode. When an actuator learns its end stops

through calibration, it also determines its control angle. The

actuator will resolve this control angle and express its operation

in a percent (%) of this learned range.

If the economizer has not learned a sufficient control angle

during calibration, the economizer damper will be unable

to control ventilation and free cooling. For this reason the

economizer actuator used in the Z Series control system has a

configurable control angle alarm low limit (Configuration

ECON

ACT.C

C.A.L1 or C.A.L2). If the control angle

learned through calibration is less than C.A.L1 or C.A.L2, an

alert will occur and the actuator will not function.
NOTE: This configuration does not typically need adjustment.

It is configurable for the small number of jobs which may

require a custom solution or workaround.
UNOCCUPIED ECONOMIZER FREE COOLING — This

Free Cooling function is used to start the supply fan and use

the economizer to bring in outside air when the outside

temperature is cool enough to pre-cool the space. This is done

to delay the need for mechanical cooling when the system

enters the occupied period. This function requires the use of a

space temperature sensor.

When configured, the economizer will modulate during an

unoccupied period and attempt to maintain space temperature

to the occupied cooling set point. Once the need for cooling has

been satisfied during this cycle, the fan will be stopped.

Configuring the economizer for Unoccupied Economizer

Free Cooling is done in the UEFC group. There are three

configuration options, FC.CF, FC.TM and FC.LO.
Unoccupied Economizer Free Cooling Configuration

(FC.CF) — This option is used to configure the type of unoc-

cupied economizer free cooling control that is desired.
0 = disable unoccupied economizer free cooling
1 = perform unocc. economizer free cooling as available dur-

ing the entire unoccupied period.

2 = perform unocc. economizer free cooling as available,

FC.TM minutes before the next occupied period.

Unoccupied Economizer Free Cooling Time Configuration

(FC.TM) — This option is a configurable time period, prior to

the next occupied period, that the control will allow unoccu-

pied economizer free cooling to operate. This option is only

applicable when FC.CF = 2.
Unoccupied Economizer Free Cooling Outside Lockout

Temperature (FC.LO) — This configuration option allows

the user to select an outside-air temperature below which unoc-

cupied free cooling is not allowed. This is further explained in

the logic section.
Unoccupied Economizer Free Cooling Logic — The follow-

ing qualifications that must be true for unoccupied free cooling

to operate:
• Unit configured for an economizer

• Space temperature sensor enabled and sensor reading

within limits

• Unit in the unoccupied mode

FC.CF set to 1 or FC.CF set to 2 and control is within

FC.TM minutes of the next occupied period

• Not in the Temperature Compensated Start mode

• Not in a cooling mode

• Not in a heating mode

• Not in a tempering mode

• Outside-air temperature sensor reading within limits

• Economizer would be allowed to cool if the fan were

requested and in a cool mode

• OAT > FC.LO (1.0° F hysteresis applied)

• Unit not in a fire smoke mode

• No fan failure when configured to for unit to shut down

on a fan failure

If all of the above conditions are satisfied:
Unoccupied Economizer Free Cooling will start when both of

the following conditions are true:
{SPT > (OCSP + 2)} AND {SPT > (OAT + 8)}
The Unoccupied Economizer Free Cooling Mode will stop

when either of the following conditions are true:
{SPT < OCSP} OR {SPT < (OAT + 3)} where SPT = Space

Temperature and OCSP = Occupied Cooling Set Point.

When the Unoccupied Economizer Free Cooling mode is

active, the supply fan is turned on and the economizer damper

modulated to control to the supply air set point (Setpoints

SASP) plus any supply air reset that may be applied (Inputs

RSET

SA.S.R).

OUTDOOR AIR CFM CONTROL — If an outdoor air cfm

flow station has been installed, the economizer is able to

provide minimum ventilation based on cfm, instead of

damper position. The outdoor air cfm reading can be found in

Inputs

CFM

O.CFM. During cfm control, the economizer

must guarantee a certain amount of cfm at any time for ventila-

tion purposes. If the outdoor air cfm measured is less than the

current calculated cfm minimum position, then the economizer

will attempt to open until the outdoor air cfm is greater than or

equal to this cfm minimum position. The following options are

used to program outside air cfm control.
Outdoor Air Cfm Sensor Enable (OCF.S) — If this option is

enabled, the outdoor air cfm sensor will be read and outside air

cfm control will be enabled.
Economizer Minimum Flow Rate (O.C.MX) — This option

replaces the Economizer Minimum Position (Configuration

ECON

EC.MN) when the outdoor air cfm sensor is

enabled.
IAQ Demand Vent Minimum Flow Rate (O.C.MN) — This

option replaces the IAQ Demand Ventilation Minimum

Position (Configuration

IAQ

DCV.C

IAQ.M) when the

outdoor air cfm sensor is enabled.
Economizer Minimum Flow Deadband (O.C.DB) — This

option defines the deadband of the cfm control logic.

The configurable deadband is added to the economizer’s

minimum cfm position and creates a range (ECMINCFM to

ECMINCFM ± OACFM_DB) where the economizer will not

attempt to adjust to maintain the minimum cfm position.

Increasing this deadband value may help to slow down exces-

sive economizer movement when attempting to control to a

minimum position at the expense of bringing in more ventila-

tion air than desired.
ECONOMIZER OPERATION CONFIGURATION — The

configuration items in the E.CFG menu group affect how

the economizer modulates when attempting to follow an

economizer cooling set point. Typically, they will not need

adjustment. In fact, it is strongly advised not to adjust these

configuration items from their default settings without first

consulting a service engineering representative.

In addition, the economizer cooling algorithm is designed to

automatically slow down the economizer actuator’s rate of

travel as outside air temperature decreases.
ECONOMIZER DIAGNOSTIC HELP — Because there are

so many conditions which might disable the economizer from

being able to provide free cooling, the control has a display

table to identify these potentially disabling sources. The user

can check ACTV, the “Economizer Active” flag. If this flag is

set to Yes there is no reason to check DISA (Economizer

Disabling Conditions). If the flag is set to No, this means that at

least one or more of the flags under the group DISA are set

to Yes and the user can discover what is preventing the econo-

mizer from performing free cooling by checking the table.

Advertising