IAQ Discrete Input Config (Configuration

IAQ

AQ.CF

IQ.I.C) — This configuration is used to set the type of IAQ

sensor. The following are the options:
IQ.I.C = 0 (No Discrete Input) — This is used to indicate

that no discrete input will be used and the standard IAQ

sensor input will be used.

IQ.I.C = 1 (IAQ Discrete Input) — This will indicate

that the IAQ level (high or low) will be indicated by

the discrete input. When the IAQ level is low, the

economizer minimum position will be Configuration

IAQ

DCV.C

IAQ.M.

IQ.I.C = 2 (IAQ Discrete Input with Minimum Position

Override. This will indicate that the IAQ level (high or

low) will be indicated by the discrete input and the econ-

omizer minimum position will be the IAQ override posi-

tion, IQ.P.O (when high).
It is also necessary to configure how the fan operates when

using the IAQ discrete input.
IAQ Discrete Fan Config (Configuration

IAQ

AQ.CF

IQ.I.F) — This is used to configure the operation of the

fan during an IAQ demand condition. It has the following

configurations:
IQ.I.F = 0 (No Fan Start) — IAQ demand will never

override normal indoor fan operation during occupied or

unoccupied period and turn it on.

IQ.I.F = 1 (Fan On If Occupied) — IAQ demand will

override normal indoor fan operation and turn it on (if

off) only during the occupied period (CV operation with

automatic fan).

IQ.I.F = 2 (Fan On Occupied/Unoccupied) — IAQ

demand will always override normal indoor fan opera-

tion and turn it on (if off) during both the occupied and

unoccupied period.

Economizer Min Position (Configuration

IAQ

DCV.C

EC.MN) — This is the fully occupied minimum economizer

position.
IAQ Demand Vent Min Pos. (Configuration

IAQ

DCV.C

IAQ.M) — This configuration will be used to set the

minimum damper position in the occupied period when there

is no IAQ demand.
IAQ Econo Override Pos (Configuration

IAQ

AQ.SP

IQ.O.P) — This configuration is the position that the econo-

mizer goes to when override is in effect.
OAQ 4-20 mA Sensor Config (Configuration

IAQ

AQ.CF

OQ.A.C) — This is used to configure the type of

outdoor sensor that will be used for OAQ levels. It has the fol-

lowing configuration options:
OQ.A.C = 0 (No Sensor) — No sensor will be used and

the internal software reference setting will be used.

OQ.A.C = 1 (OAQ Sensor with DAQ) — An outdoor

CO

2

sensor will be used.

OQ.A.C = 2 (4 to 20 mA Sensor without DAQ).
OAQ Lockout Value (Configuration

IAQ

AQ.SP

OAQ.L) — This is the maximum OAQ level above which de-

mand ventilation will be disabled.
Diff. Air Quality Lo Limit (Configuration

IAQ

AQ.SP

DAQ.L) — This is the differential CO

2

level at which IAQ

control of the dampers will be initiated.
Diff. Air Quality Hi Limit (Configuration

IAQ

AQ.SP

DAQ.H) — This is the differential CO

2

level at which IAQ

control of the dampers will be at maximum and the dampers

will be at the Configuration

IAQ

DCV.C

EC.MN.

DAQ ppm Fan On Set Point (Configuration

IAQ

AQ.SP

D.F.ON) — This is the CO

2

level at which

the indoor fan will be turned on.
DAQ ppm Fan Off Set Point (Configuration

IAQ

AQ.SP

D.F.OF) — This is the CO

2

level at which the

indoor fan will be turned off.
IAQ Low Reference (Configuration

IAQ

AQ.S.R

IQ.R.L) — This is the reference that will be used with a to

non-Carrier IAQ sensor that may have a different characteristic

curve. It represents the CO

2

level at 4 mA.

IAQ High Reference (Configuration

IAQ

AQ.SR

IQ.R.H) — This is the reference that will be used with a

non-Carrier IAQ sensor that may have a different characteristic

curve. It represents the CO

2

level at 4 mA.

NOTE: Calculating the IAQ.M and EC.MN damper position based
on differential IAQ measurement.

Based on the configuration parameter IAQREACT, the reaction to
damper positioning based on differential air quality ppm can be
adjusted.

IAQREACT = 1 to 5 (more responsive)

IAQREACT = 0 (linear)

IAQREACT = –1 to –5 (less responsive)

Fig. 12 — IAQ Response Curve

100
500

700

1000

INSIDE/OUTSIDE CO

2

DIFFERENTIAL

INSIDE CO

2

CONCENTRATION

AQ
DIFFERENTIAL
LOW (DAQ.L)

AQ
DIFFERENTIAL
HIGH (DAQ.H)

MINIMUM
IAQ
DAMPER
POSITION

ECONOMIZER
MINIMUM
DAMPER
POSITION

INCREASING VENTILA

TION

VENTILATION FOR PEOPLE

VENTILATION FOR SOURCES

Fig. 11 — IAQ Control