APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — INPUTS

*The display text changes depending on the remote switch configuration (Configuration

UNIT

RM.CF). If RM.CF is set to 0 (No Remote Switch), then the display

text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop),
then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

GEN.I

GENERAL INPUTS

FLT.S

Filter Status Input

DRTY/CLN

FLTS

forcible

G.FAN

Fan Request From IGC

ON/OFF

IGCFAN

REMT

Remote Input State

*

RMTIN

forcible

ENTH

Enth. Switch Read High ?

YES/NO

ENTH

forcible

S.FN.S

Supply Fan Status Switch

ON/OFF

SFS

forcible

FRZ.S

Freeze Status Switch

ALRM/NORM

FRZ

forcible

PP.SW

Plenum Press.Safety Sw.

HIGH/LOW

PPS

forcible

DL.S1

Demand Limit Switch 1

ON/OFF

DMD_SW1

forcible

DL.S2

Demand Limit Switch 2

ON/OFF

DMD_SW2

forcible

DH.IN

Dehumidify Switch Input

ON/OFF

DHDISCIN

forcible

FD.BK

COMPRESSOR FEEDBACK

HPS.A

Circ A High Press. Switch

HIGH/LOW

CIRCAHPS

HPS.B

Circ B High Press. Switch

HIGH/LOW

CIRCBHPS

CS.A1

Compressor A1 Feedback

ON/OFF

CSB_A1

CS.A2

Compressor A2 Feedback

ON/OFF

CSB_A2

CS.B1

Compressor B1 Feedback

ON/OFF

CSB_B1

CS.B2

Compressor B2 Feedback

ON/OFF

CSB_B2

STAT

THERMOSTAT INPUTS

G

Thermostat G Input

ON/OFF

G

forcible

W1

Thermostat W1 Input

ON/OFF

W1

forcible

W2

Thermostat W2 Input

ON/OFF

W2

forcible

Y1

Thermostat Y1 Input

ON/OFF

Y1

forcible

Y2

Thermostat Y2 Input

ON/OFF

Y2

forcible

FIRE

FIRE-SMOKE INPUTS

FSD

Fire Shutdown Input

ALRM/NORM

FSD

forcible

PRES

Pressurization Input

ALRM/NORM

PRES

forcible

EVAC

Evacuation Input

ALRM/NORM

EVAC

forcible

PURG

Smoke Purge Input

ALRM/NORM

PURG

forcible

REL.H

RELATIVE HUMIDITY

OA.RH

Outside Air Rel. Humidity

%

OARH

forcible

OA.EN

Outdoor Air Enthalpy

OAE

OA.DP

OutsideAir Dewpoint Temp

dF

OADEWTMP

RA.RH

Return Air Rel. Humidity

%

RARH

forcible

RA.EN

Return Air Enthalpy

RAE

SP.RH

Space Relative Humidity

%

SPRH

forcible

SP.EN

Space Enthalpy

SPE

AIR.Q

AIR QUALITY SENSORS

IAQ.I

IAQ - Discrete Input

HIGH/LOW

IAQIN

forcible

IAQ

IAQ - PPM Return CO2

IAQ

forcible

OAQ

OAQ - PPM Return CO2

OAQ

forcible

DAQ

Diff.Air Quality in PPM

DAQ

IQ.P.O

IAQ Min.Pos. Override

%

IAQMINOV

forcible

CFM

CFM SENSORS

O.CFM

Outside Air CFM

CFM

OACFM

R.CFM

Return Air CFM

CFM

RACFM

S.CFM

Supply Air CFM

CFM

SACFM

D.CFM

Fan Track Control D.CFM

CFM

DELTACFM

RSET

RESET INPUTS

SA.S.R

Supply Air Setpnt. Reset

^F

SASPRSET

forcible

SP.RS

Static Pressure Reset

SPRESET

forcible

4-20

4-20 MILLIAMP INPUTS

IAQ.M

IAQ Milliamps

ma

IAQ_MA

OAQ.M

OAQ Milliamps

ma

OAQ_MA

SP.R.M

SP Reset milliamps

ma

SPRST_MA

DML.M

4-20 ma Demand Signal

ma

DMDLMTMA

forcible

EDR.M

EDT Reset Milliamps

ma

EDTRESMA

ORH.M

OARH Milliamps

ma

OARH_MA

SRH.M

SPRH Milliamps

ma

SPRH_MA

RRH.M

RARH Milliamps

ma

RARH_MA

SAC.M

SACFM Milliamps

ma

SACFM_MA

SA.M.T

Supply Air CFM Trim (ma)

-2.0

2.0

SAMATRIM

RAC.M

RACFM Milliamps

ma

RACFM_MA

RA.M.T

Return Air CFM Trim (ma)

-2.0

2.0

RAMATRIM

config

OAC.M

OACFM Milliamps

ma

OACFM_MA

OA.M.T

Outside Air CFM Trim(ma)

-2.0

2.0

OAMATRIM

config

BP.M

BP Milliamps

ma

BP_MA

BP.M.T

Bldg. Pressure Trim (ma)

-2.0

2.0

BPMATRIM

config

SP.M

SP Milliamps

ma

SP_MA

SP.M.T

Static Press. Trim (ma)

-2.0

2.0

SPMATRIM

config