CL-3
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM
EXPANSION
RANGE
DEFAULT
SETTING
ECON
ECONOMIZER CONFIGURATION
→EC.EN
Economizer Installed?
Yes/No
Yes
→EC2.E
Econ.Act.2 Installed?
Yes/No
No
→EC.MN
Economizer Min.Position
0 - 100%
5
→EC.MX
Economizer Max.Position
0 - 100%
98
→E.TRM
Economzr Trim For SumZ ?
Yes/No
Yes
→E.SEL
Econ ChangeOver Select
0 - 3 (multi-text strings)
0
→OA.E.C
OA Enthalpy ChgOvr Selct
1 - 5 (multi-text strings)
4
→OA.EN
Outdr.Enth Compare Value
18 - 28
24
→OAT.L
High OAT Lockout Temp
-40 - 120 dF
60
→O.DEW
OA Dewpoint Temp Limit
50 - 62 dF
55
→ORH.S
Outside Air RH Sensor
Enable/Disable
Disable
→CFM.C
OUTDOOR AIR CFM CONTROL
→CFM.C→OCF.S
Outdoor Air CFM Sensor
Enable/Disable
Disable
→CFM.C→O.C.MX
Economizer Min.Flow
0 - 20000 CFM
2000
→CFM.C→O.C.MN
IAQ Demand Vent Min.Flow
0 - 20000 CFM
0
→CFM.C→O.C.DB
Econ.Min.Flow Deadband
200 - 1000 CFM
400
→E.CFG
ECON.OPERATION CONFIGS
→E.CFG→E.P.GN
Economizer Prop.Gain
0.7 - 3.0
1
→E.CFG→E.RNG
Economizer Range Adjust
0.5 - 5 ^F
2.5
→E.CFG→E.SPD
Economizer Speed Adjust
0.1 - 10
0.75
→E.CFG→E.DBD
Economizer Deadband
0.1 - 2 ^F
0.5
→UEFC
UNOCC.ECON.FREE COOLING
→UEFC→FC.CF
Unoc Econ Free Cool Cfg
0-2 (multi-text strings)
0
→UEFC→FC.TM
Unoc Econ Free Cool Time
0 - 720 min
120
→UEFC→FC.L.O
Un.Ec.Free Cool OAT Lock
40 - 70 dF
50
→ACT.C
ECON.ACTUATOR CONFIGS
→ACTC→SN.1.1
Econ Serial Number 1
0 - 255
0
→ACTC→SN.1.2
Econ Serial Number 2
0 - 255
0
→ACTC→SN.1.3
Econ Serial Number 3
0 - 255
0
→ACTC→SN.1.4
Econ Serial Number 4
0 - 255
0
→ACTC→SN.1.5
Econ Serial Number 5
0 - 255
0
→ACTC→C.A.L1
Econ Ctrl Angle Lo Limit
0 - 90
85
→ACTC→SN.2.1
Econ 2 Serial Number 1
0 - 255
0
→ACTC→SN.2.2
Econ 2 Serial Number 2
0 - 255
0
→ACTC→SN.2.3
Econ 2 Serial Number 3
0 - 255
0
→ACTC→SN.2.4
Econ 2 Serial Number 4
0 - 255
0
→ACTC→SN.2.5
Econ 2 Serial Number 5
0 - 255
0
→ACTC→C.A.L2
Econ 2 Ctrl Angle Lo Limit
0 - 90
85
BP
BUILDING PRESS. CONFIGS
→BP.CF
Building Press. Config
0 - 5 (multi-text strings)
0
→BP.S
Building Pressure Sensor
Enable/Disable
Disable
→BP.R
Bldg. Press. (+/-) Range
0.10 - 0.25 "H2O
0.25
→BP.SP
Building Pressure Setp.
-0.25 - 0.25 "H2O
0.05
→BP.SO
BP Setpoint Offset
0 - 0.5 "H2O
0.05
→BP.P1
Power Exhaust On Setp.1
0 - 100%
25
→BP.P2
Power Exhaust On Setp.2
0 - 100%
75
→B.V.A
VFD/ACTUATOR CONFIG
→B.V.A→BP.FS
VFD/Act. Fire Speed/Pos.
0 - 100%
100
→B.V.A→BP.MN
VFD/Act. Min.Speed/Pos.
0 - 50%
0
→B.V.A→BP.MX
VFD Maximum Speed
50 - 100%
100
→B.V.A→BP.1M
BP 1 Actuator Max Pos.
85 - 100%
100
→B.V.A→BP.2M
BP 2 Actuator Max Pos.
85 - 100%
100
→B.V.A→BP.CL
BP Hi Cap VFD Clamp Val.
5 - 25%
10