CONTROLS SET POINT AND CONFIGURATION LOG (cont)

ITEM

EXPANSION

RANGE

DEFAULT

SETTING

ECON

ECONOMIZER CONFIGURATION

EC.EN

Economizer Installed?

Yes/No

Yes

EC2.E

Econ.Act.2 Installed?

Yes/No

No

EC.MN

Economizer Min.Position

0 - 100%

5

EC.MX

Economizer Max.Position

0 - 100%

98

E.TRM

Economzr Trim For SumZ ?

Yes/No

Yes

E.SEL

Econ ChangeOver Select

0 - 3 (multi-text strings)

0

OA.E.C

OA Enthalpy ChgOvr Selct

1 - 5 (multi-text strings)

4

OA.EN

Outdr.Enth Compare Value

18 - 28

24

OAT.L

High OAT Lockout Temp

-40 - 120 dF

60

O.DEW

OA Dewpoint Temp Limit

50 - 62 dF

55

ORH.S

Outside Air RH Sensor

Enable/Disable

Disable

CFM.C

OUTDOOR AIR CFM CONTROL

CFM.COCF.S

Outdoor Air CFM Sensor

Enable/Disable

Disable

CFM.CO.C.MX

Economizer Min.Flow

0 - 20000 CFM

2000

CFM.CO.C.MN

IAQ Demand Vent Min.Flow

0 - 20000 CFM

0

CFM.CO.C.DB

Econ.Min.Flow Deadband

200 - 1000 CFM

400

E.CFG

ECON.OPERATION CONFIGS

E.CFGE.P.GN

Economizer Prop.Gain

0.7 - 3.0

1

E.CFGE.RNG

Economizer Range Adjust

0.5 - 5 ^F

2.5

E.CFGE.SPD

Economizer Speed Adjust

0.1 - 10

0.75

E.CFGE.DBD

Economizer Deadband

0.1 - 2 ^F

0.5

UEFC

UNOCC.ECON.FREE COOLING

UEFCFC.CF

Unoc Econ Free Cool Cfg

0-2 (multi-text strings)

0

UEFCFC.TM

Unoc Econ Free Cool Time

0 - 720 min

120

UEFCFC.L.O

Un.Ec.Free Cool OAT Lock

40 - 70 dF

50

ACT.C

ECON.ACTUATOR CONFIGS

ACTCSN.1.1

Econ Serial Number 1

0 - 255

0

ACTCSN.1.2

Econ Serial Number 2

0 - 255

0

ACTCSN.1.3

Econ Serial Number 3

0 - 255

0

ACTCSN.1.4

Econ Serial Number 4

0 - 255

0

ACTCSN.1.5

Econ Serial Number 5

0 - 255

0

ACTCC.A.L1

Econ Ctrl Angle Lo Limit

0 - 90

85

ACTCSN.2.1

Econ 2 Serial Number 1

0 - 255

0

ACTCSN.2.2

Econ 2 Serial Number 2

0 - 255

0

ACTCSN.2.3

Econ 2 Serial Number 3

0 - 255

0

ACTCSN.2.4

Econ 2 Serial Number 4

0 - 255

0

ACTCSN.2.5

Econ 2 Serial Number 5

0 - 255

0

ACTCC.A.L2

Econ 2 Ctrl Angle Lo Limit

0 - 90

85

BP

BUILDING PRESS. CONFIGS

BP.CF

Building Press. Config

0 - 5 (multi-text strings)

0

BP.S

Building Pressure Sensor

Enable/Disable

Disable

BP.R

Bldg. Press. (+/-) Range

0.10 - 0.25 "H2O

0.25

BP.SP

Building Pressure Setp.

-0.25 - 0.25 "H2O

0.05

BP.SO

BP Setpoint Offset

0 - 0.5 "H2O

0.05

BP.P1

Power Exhaust On Setp.1

0 - 100%

25

BP.P2

Power Exhaust On Setp.2

0 - 100%

75

B.V.A

VFD/ACTUATOR CONFIG

B.V.ABP.FS

VFD/Act. Fire Speed/Pos.

0 - 100%

100

B.V.ABP.MN

VFD/Act. Min.Speed/Pos.

0 - 50%

0

B.V.ABP.MX

VFD Maximum Speed

50 - 100%

100

B.V.ABP.1M

BP 1 Actuator Max Pos.

85 - 100%

100

B.V.ABP.2M

BP 2 Actuator Max Pos.

85 - 100%

100

B.V.ABP.CL

BP Hi Cap VFD Clamp Val.

5 - 25%

10