Table 58 — Building Pressure Configuration

*Some configurations are model number dependent.

Configuration

BP

BP.CF = 2 (Modulating Power Exhaust)

— Control is accomplished with two LEN communicating

actuators in tandem and one exhaust fan relay. If building

pressure (Pressures

AIR.P

BP) rises above the building

pressure set point (BP.SP) and the supply fan is on, building

pressure control is initialized. Thereafter, if the supply fan relay

goes off or if the building pressure drops below the BP.SP

minus the building pressure set point offset (BP.SO) for 5

continuous minutes, building pressure control will be stopped.

Any time building pressure control becomes active, the exhaust

fan relay turns on, starting the dual exhaust fan motors. After

the exhaust fan relay turns on, control is performed with a PID

loop where:
Error = BPBP.SP
K = 1000 * BP.TM / 60 (normalize the PID control for run rate)
P = K * BP.P * (error)
I = K * BP.I * (error) + “I” calculated last time through the PID
D = K * BP.D * (error – error computed last time through the

PID)
Power exhaust control signal (limited between BP.MN and

(BP.1M/BP.2M) %) = P + I + D
Configuration

BP

BP.CF = 3 (VFD Controlling Exhaust

Fan Motors) — The VFD controlling high-capacity power

exhaust consists of an exhaust fan VFD (Outputs

FANS

E.VFD) enabled by one power exhaust relay (Outputs

FANS

P.E.1). If building pressure (Pressures

AIR.P

BP) rises

above the building pressure set point (BP.SP) and the supply fan

is on, then building pressure control is initialized. Thereafter, if

the supply fan relay goes off or if the building pressure drops be-

low the BP.SP minus the building pressure set point offset

(BP.SO) for 5 continuous minutes, building pressure control

will be stopped. The 5-minute timer will continue to re-initialize

while the VFD is commanded to a position > 0%. If the building

pressure falls below the set point, the VFD will slow down auto-

matically. Any time building pressure control becomes active,

the exhaust fan relay turns on which energizes the exhaust fan

VFD. Control is performed with a PID loop where:
Error = BPBP.SP
K = 1000 * BP.TM/60 (normalize the PID control for run rate)
P = K * BP.P * (error)
I = K * BP.I * (error) + “I” calculated last time through the PID
D = K * BP.D * (error – error computed last time through the

PID)
VFD control signal (clamped between BP.MN and BP.MX%)

= P + I + D
NOTE: Do not change values of PID set point without

approval from Carrier.
BP.CF = 4 (High-Capacity Exhaust Control) — Control is

accomplished with a VFD and two exhaust fan relays. High-

capacity power exhaust consists of an exhaust fan VFD

(Outputs

FANS

E.VFD) enabled by one power exhaust

relay (Outputs

FANS

P.E.1) and a second power exhaust

relay (Outputs

FANS

P.E.2) which controls a single speed

fan which is equal in capacity to the VFD running at full speed.

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

BP

BUILDING PRESS. CONFIGS

BP.CF

Building Press. Config

0 - 5

BLDG_CFG

0*

BP.S

Building Pressure Sensor

Enable/Disable

BPSENS

Disable*

BP.R

Bldg. Press. (+/-) Range

0.10 - 0.25

"H2O

BP_RANGE

0.25

BP.SP

Building Pressure Setp.

-0.25 - 0.25

"H2O

BPSP

0.05

BP.SO

BP Setpoint Offset

0 - 0.5

"H2O

BPSO

0.05

BP.P1

Power Exhaust On Setp.1

0 - 100

%

PES1

25

BP.P2

Power Exhaust On Setp.2

0 - 100

%

PES2

75

B.V.A

VFD/ACTUATOR CONFIG

BP.FS

VFD/Act. Fire Speed/Pos.

0 - 100

%

BLDGPFSO

100

BP.MN

VFD/Act. Min.Speed/Pos.

0 - 50

%

BLDGPMIN

10

BP.MX

VFD Maximum Speed

50 - 100

%

BLDGPMAX

100

BP.1M

BP 1 Actuator Max Pos.

85 - 100

%

BP1SETMX

100

BP.2M

BP 2 Actuator Max Pos.

85 - 100

%

BP2SETMX

100

BP.CL

BP Hi Cap VFD Clamp Val.

5 - 25

%

BLDGCLMP

10

FAN.T

FAN TRACKING CONFIG

FT.CF

Fan Track Learn Enable

Yes/No

DCFM_CFG

No

FT.TM

Fan Track Learn Rate

5-60

min

DCFMRATE

15

FT.ST

Fan Track Initial DCFM

-20000 - 20000

CFM

DCFMSTRT

2000

FT.MX

Fan Track Max Clamp

0 - 20000

CFM

DCFM_MAX

4000

FT.AD

Fan Track Max Correction

0 -20000

CFM

DCFM_ADJ

1000

FT.OF

Fan Track Internl EEPROM

-20000 - 20000

CFM

DCFM_OFF

0

FT.RM

Fan Track Internal RAM

-20000 - 20000

CFM

DCFM_RAM

0

FT.RS

Fan Track Reset Internal

Yes/No

DCFMRSET

No

SCF.C

Supply Air CFM Config

1 - 2

SCFM_CFG

1

B.PID

BLDG.PRESS.PID CONFIGS

BP.TM

Bldg.Pres.PID Run Rate

5 - 120

sec

BPIDRATE

10

BP.P

Bldg.Press. Prop. Gain

0 - 5

BLDGP_PG

0.5

BP.I

Bldg.Press. Integ. Gain

0 - 2

BLDGP_IG

0.5

BP.D

Bldg.Press. Deriv. Gain

0 - 5

BLDGP_DG

0.3

ACT.C

BLDG.PRES. ACTUATOR CFGS

BP.1

BLDG.PRES. ACT.1 CONFIGS

SN.1

BP 1 Serial Number 1

0 - 255

BP_1_SN1

0

SN.2

BP 1 Serial Number 2

0 - 255

BP_1_SN2

0

SN.3

BP 1 Serial Number 3

0 - 255

BP_1_SN3

0

SN.4

BP 1 Serial Number 4

0 - 255

BP_1_SN4

0

SN.5

BP 1 Serial Number 5

0 - 255

BP_1_SN5

0

C.A.LM

BP1 Cntrl Angle Lo Limit

0-90

BP1_CALM

35

BP.2

BLDG.PRES. ACT.2 CONFIGS

SN.1

BP 2 Serial Number 1

0 - 255

BP_2_SN1

0

SN.2

BP 2 Serial Number 2

0 - 255

BP_2_SN2

0

SN.3

BP 2 Serial Number 3

0 - 255

BP_2_SN3

0

SN.4

BP 2 Serial Number 4

0 - 255

BP_2_SN4

0

SN.5

BP 2 Serial Number 5

0 - 255

BP_2_SN5

0

C.A.LM

BP2 Cntrl Angle Lo Limit

0-90

BP2_CALM

35