If the switch is closed, the IAQ reading will be high and the

economizer will be commanded to the Economizer Minimum

Position. If the outdoor airflow station is installed and outdoor

air cfm can be read, the economizer will move to the Econo-

mizer Minimum Flow CFM control setting.
These settings may be adjusted and are located here:

Configuration

IAQ

DCV.C

EC.MN

Configuration

IAQ

DCV.C

O.C.MX

IQ.I.C = 2 (IAQ Discrete Override) — If the user sets IQ.I.C

to 2 (IAQ Discrete Override), and Configuration

SW.LG

IAQ.L is set to OPEN, then an open switch reads low and a

closed switch reads high.

If the switch reads low, no action will be taken. If the switch

reads high, the economizer will immediately be commanded to

the IAQ Economizer Override Position. This can be set from 0

to 100% and can be found at Configuration

IAQ

AQ.SP

IQ.O.P.
FAN CONTROL FOR THE IAQ DISCRETE INPUT —

Under Configuration

IAQ

AQ.CF, the IQ.I.F (IAQ Dis-

crete Input Fan Configuration) must also be set. There are

three configurations for IQ.I.F. Select the configuration which

will be used for fan operation.

This configuration allows the

user to decide (if the supply fan is not already running),

whether the IAQ discrete switch will start the fan, and in which

state of occupancy the fan will start.

IAQ ANALOG INPUT CONFIGURATION — This input is

an analog input located on the main base board (MBB). There

are 4 different functions for this input. The location of this con-

figuration is at Configuration

IAQ

AQ.CF

IQ.A.C.

The functions possible for IQ.A.C are:
• 0 = no IAQ analog input

• 1 = IAQ analog input

• 2 = IAQ analog input used to override to a set position

• 3 = 4 to 20 mA 0 to 100% economizer minimum position

control

• 4 = 0 to 10 kilo-ohms 0 to 100% economizer minimum

position control
Options 2, 3, and 4 are dedicated for third party control.

IQ.A.C = 2 (IAQ Analog Input Used to Override) — Under

Configuration

IAQ

AQ.SP, set IQ.O.P (IAQ Economizer

Override Position). The IQ.O.P configuration is adjustable

from 0 to 100%. These configurations are also used in conjunc-

tion with Configuration

IAQ

AQ.CF

IQ.A.F (IAQ 4 to

20 mA Fan Configuration). There are three configurations for

IQ.A.F and they follow the same logic as for the discrete input.

This configuration allows the user to decide (if the supply fan is

not already running), if the IAQ Analog Minimum Position

Override input will start the fan, and in which state of occupan-

cy the fan will start.

If IQ.A.F is configured to request the supply fan, then

configurations D.F.ON and D.F.OF need to be set. These

configuration settings are located under Configuration

IAQ

AQ.SP and configure the fan override operation based

on the differential air quality (DAQ). If DAQ rises above

D.F.ON, the control will request the fan on until DAQ falls be-

low D.F.OF.
NOTE: If D.F.ON is configured below DAQ.H, the unit is in

occupied mode, and the fan was off, then DAQ rose above

D.F.ON and the fan came on, the economizer will go to the

economizer minimum position (EC.MN).

The 4 to 20 mA signal from the sensor wired to TB12 and

TB11 is scaled to an equivalent indoor CO

2

(IAQ) by the

parameters IQ.R.L and IQ.R.H located under the Configura-

tion

IAQ

AQ.SR menu. The parameters are defined such

that 4 mA = IQ.R.L and 20 mA = IQ.R.H. When the differen-

tial air quality DAQ (IAQ – OAQ.U) exceeds the DAQ.H set

point (Configuration

IAQ

AQ.SP menu) and the supply

fan is on, the economizer minimum vent position (Configura-

tion

IAQ

DCV.C

EC.MN) is overridden and the damper

is moved to the IQ.P.O configuration. When the DAQ falls be-

low the DAQ.L set point (Configuration

IAQ

AQ.SP

menu), the economizer damper is moved back to the minimum

vent position (EC.MN).
NOTE: Configuration OAQ.U is used in the calculation of the

trip point for override and can be found under Configura-

tion

IAQ

AQ.SP.

IQ.A.C = 3 (4 to 20 mA Damper Control) — This configura-

tion will provide full 4 to 20 mA remotely controlled analog in-

put for economizer minimum damper position. The 4 to 20 mA

signal is connected to terminals TB12 and TB11. The input is

processed as 4 mA = 0% and 20 mA = 100%, thereby giving

complete range control of the effective minimum position.

The economizer sequences can be disabled by removing the

enthalpy switch input at TB201-4 and not enabling any other

economizer changeover sequence at Configuration

ECON

E.SEL. Complete control of the economizer damper

position is then possible by using a 4 to 20 mA economizer

minimum position control or a 0 to 10 kilo-ohm 0 to 100%

economizer minimum position control via configuration deci-

sions at Configuration

IAQ

IQ.A.C.

To disable the standard enthalpy control input function,

remove the enthalpy switch input connection at TB201-4 and

provide a jumper from TB201-3 to TB201-4 (see wiring

diagrams in Major System Components section on page 102).
IQ.A.C = 4 (10 Kohm Potentiometer Damper Control) —

This configuration will provide input for a 10 kilo-ohm linear

potentiometer that acts as a remotely controlled analog input

for economizer minimum damper position. The input is pro-

cessed as 0 ohms = 0% and 10,000 ohms = 100%, thereby giv-

ing complete range control of the effective minimum position.
NOTE: For complete economizer control, the user can make

the economizer inactive by removing the enthalpy switch

connection from terminal TB201-4.

CONTROLS OPERATION

Modes —

The ComfortLink™ controls operate under a

hierarchy of command structure as defined by three essential

elements: the System mode, the HVAC mode and the Control

mode. The System mode is the top level mode that defines three

essential states for the control system: OFF, RUN and TEST.

The HVAC mode is the functional level underneath the

System mode which further defines the operation of the

control.

The Control mode is essentially the control type of the unit

(Configuration

UNIT

C.TYP). This defines from where

the control looks to establish a cooling or heating mode and

whether 2 stages or multiple stages of cooling capacity opera-

tion are controlled.

Furthermore, there are a number of modes which operate

concurrently when the unit is running. The operating modes of

IQ.I.F = 0

Minimum Position Override Switch input

will not start fan

IQ.I.F = 1

Minimum Position Override Switch input

will start fan in occupied mode only

IQ.I.F = 2

Minimum Position Override Switch input

will start fan in both occupied and unoccu-

pied modes

IQ.A.F = 0

IAQ analog sensor input cannot start the

supply fan

IQ.A.F = 1

IAQ analog sensor input can start the supply

fan in occupied mode only

IQ.A.F = 2

IAQ analog sensor input can start the supply

fan in both occupied and unoccupied modes