Gas System Adjustment (48Z Only)

GAS VALVE ADJUSTMENT — The gas valve opens and

closes in response to the unit control.

When power is supplied to valve terminals D1 and C2, the

main valve opens to its preset position.

The regular factory setting is stamped on the valve body

(3.3 in. wg).
To adjust regulator:

1. Set thermostat at setting for no call for heat.
2. Switch main gas valve to OFF position.
3. Remove

1

/

8

-in. pipe plug from manifold or gas valve

pressure tap connection. Install a suitable pressure-

measuring device.

4. Switch main gas valve to ON position.
5. Set thermostat at setting to call for heat.
6. Remove screw cap covering regulator adjustment

screw (see Fig. 50).

7. Turn adjustment screw clockwise to increase pressure

or counterclockwise to decrease pressure.

8. Once desired pressure is established, set thermostat

setting for no call for heat, turn off main gas valve,

remove pressure-measuring device, and replace

1

/

8

-in.

pipe plug and screw cap.

MAIN BURNERS — For all applications, main burners are

factory set and should require no adjustment.
MAIN BURNER REMOVAL AND REPLACEMENT

1. Shut off (field-supplied) manual main gas valve.
2. Shut off power to unit.
3. Remove gas section access door, door frame, and corner

post.

4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable form IGC board.
8. Remove 2 screws securing manifold bracket to basepan.
9. Remove 2 screws that hold the burner support plate

flange to the vestibule plate.

10. Lift burner assembly out of unit.

11. Replace burner assembly. Reinstall by reversing Steps 1

to 10.

Moisture/Liquid Indicator —

A clear flow of liquid

refrigerant indicates sufficient charge in the system. Bubbles

indicate undercharged system or the presence of noncondens-

ables. Moisture in the system measured in parts per million

(ppm) changes the color of the indicator:

Green — moisture below 45 ppm (dry)

Chartreuse — 45 to 130 ppm (caution!)

Yellow — moisture above 130 ppm (wet)

Change filter driers at the first sign of moisture in the sys-

tem. See Carrier Charging Handbook for more information.

Filter Drier —

Replace whenever the moisture/liquid indi-

cator shows moisture in the system.

Liquid Line Service Valve —

Located immediately

ahead of the filter drier, this valve has a

1

/

4

-in. flare connection

for field charging. With the liquid circuit shut, the compressor

can be used to pump the refrigerant down into the high side.

The refrigerant can then be stored there by closing the com-

pressor discharge valve.

Compressor Discharge Service Valve —

Each

compressor has one.

Compressor Suction Service Valve —

Each com-

pressor has one.

Protective Devices

COMPRESSOR PROTECTION
Overcurrent — Each compressor has one manual reset,

calibrated trip, magnetic circuit breaker. Do not bypass connec-

tions or increase the size of the circuit breaker to correct trou-

ble. Determine the cause and correct it before resetting the

breaker.
Overtemperature — Each 06D compressor has an internal

protector to protect it against excessively high discharge gas

temperatures. Each 06E compressor has an external discharge

gas thermostat. See Fig. 51. They will reset, but the circuit will

automatically be locked out by the control board. Unit must be

manually reset by interrupting control power.
Crankcase Heater — Each compressor has a crankcase heater

to prevent absorption of liquid refrigerant by oil in the crank-

case when the compressor is idle. Since 115-v power for the

crankcase heaters is drawn from the unit control circuit, main

unit power must be on for the heaters to be energized.

Liquid Pressure at Liquid Valve (PSIG)

CHARGING CHART

BOTH CIRCUITS

ALL OUTDOOR FANS MUST BE OPERATING

Liquid T

emperature at Liquid V

alve (deg F)

140

120

100

80

60

40

50

100

150

200

250

300

350

400

Add Charge if Above Curve

Reduce Charge if Below Curve

Fig. 49 — Charging Chart — 48/50Z030-105 Units

IMPORTANT: Unit must be in operation at least

12 hours before moisture indicator can give an accurate

reading. With unit running, indicating element must be

in contact with liquid refrigerant to give a true reading.

INLET PRESSURE
TAP (ON SIDE)
1/8-IN. 27 NPT

OUTLET PRESSURE
TAP (ON SIDE)
1/8-IN. 27 NPT

HIGH-FIRE REGULATOR
ADJUSTMENT SCREW

LOW-FIRE REGULATOR
ADJUSTMENT SCREW

Fig. 50 — Gas Valve