Appendix b — ccn tables (cont) – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 143

Advertising
background image

143

APPENDIX B — CCN TABLES (cont)

STATUS DISPLAY TABLES (cont)

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

ECONOMZR

Economizer Act.Curr.Pos.

%

ECONOPOS

Economizer 2 Act.Curr.Pos.

%

ECON2POS

Economizer Act.Cmd.Pos.

%

ECONOCMD

forcible

Economizer Active ?

ECACTIVE

Economizer Control Point

dF

ECONCPNT

Outside Air Temperature

dF

OAT

forcible

Evaporator Discharge Tmp

dF

EDT

Controlling Return Temp

dF

RETURN_T

forcible

Econo Current Min. Pos.

%

ECMINPOS

Econo Current Min. CFM

CFM

ECMINCFM

Outside Air CFM

CFM

OACFM

GENERAL

Occupied ?

YES/NO

OCCUPIED

forcible

Static Pressure

"H2O

SP

Building Pressure

"H2O

BP

Outside Air CFM

CFM

OACFM

Return Air CFM

CFM

RACFM

Supply Air CFM

CFM

SACFM

Outside Air Rel.Humidity

%

OARH

forcible

Return Air Rel.Humidity

%

RARH

forcible

Space Relative Humidity

%

SPRH

forcible

Space Temperature Offset

^F

SPTO

forcible

Supply Air Setpnt. Reset

^F

SASPRSET

forcible

Static Pressure Reset

SPRESET

forcible

IAQ - PPM Return CO2

IAQ

forcible

OAQ - PPM Return CO2

OAQ

forcible

IAQ Min.Pos.Override

%

IAQMINOV

forcible

GENERIC

20 points dependent upon
the configuration of the
"generics" table in the
Service-Config section on page 150

HEATING

HVAC Mode…………..:

ascii text strings

Control Mode………..:

ascii text strings

Heat Control Type……:

ascii text strings

Re-Heat Control Type...:

ascii text strings

Heating Mode………..:

ascii text strings

Requested Heat Stage

HT_STAGE

Ht.Coil Act.Current Pos.

%

HTCLRPOS

Heating Control Point

dF

HEATCPNT

Heat Relay 1

HS1

Heat Relay 2

HS2

Relay 3 W1 Gas Valve 2

HS3

Relay 4 W2 Gas Valve 2

HS4

Relay 5 W1 Gas Valve 3

HS5

Relay 6 W2 Gas Valve 3

HS6

Heat Interlock Relay

HIR

forcible

MODEDISP

System Mode…………:

ascii text strings

HVAC Mode…………..:

ascii text strings

Control Mode………..:

ascii text strings

Currently Occupied

On/Off

MODEOCCP

Timed Override in effect

On/Off

MODETOVR

DCV resetting min pos

On/Off

MODEADCV

Supply Air Reset

On/Off

MODESARS

Demand Limit in Effect

On/Off

MODEDMLT

Temp.Compensated Start

On/Off

MODETCST

IAQ pre-occ purge active

On/Off

MODEIQPG

Linkage Active - DAV

On/Off

MODELINK

Mech.Cooling Locked Out

On/Off

MODELOCK

HVAC Mode Numerical Form

number

MODEHVAC

MODETRIP

Unoccup. Cool Mode Start

UCCLSTRT

Unoccup. Cool Mode End

UCCL_END

Occupied Cool Mode Start

OCCLSTRT

Occupied Cool Mode End

OCCL_END

Ctl.Temp RAT,SPT or Zone

CTRLTEMP

Occupied Heat Mode End

OCHT_END

Occupied Heat Mode Start

OCHTSTRT

Unoccup. Heat Mode End

UCHT_END

Unoccup. Heat Mode Start

UCHTSTRT

HVAC Mode…………..:

ascii text strings

string

TEMPCTRL

Evaporator Discharge Tmp

dF

EDT

Leaving Air Temperature

dF

LAT

Mixed Air Temperature

dF

MAT

Controlling Return Temp

dF

RETURN_T

forcible

Controlling Space Temp

dF

SPACE_T

forcible

Advertising