Fig. 4 — mode selection – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 43

Advertising
background image

43

System Mode =

OFF?

Inputs -> FIRE ->

FSD in alarm?

HVAC Mode = OFF

(Fire Shutdown)

HVAC Mode = OFF

(Disabled)

Unit not in factory

test AND fire-smoke

control mode is

alarming?

Inputs -> FIRE ->

PRES in alarm?

HVAC Mode = OFF

(Pressurization)

Inputs -> FIRE ->

EVAC in alarm?

HVAC Mode = OFF

(Evacuation)

HVAC Mode = OFF

(Purge)

Config->UNIT->
C.TYP changed

while unit running?

15-second delay

HVAC Mode = OFF

(Disabled)

System Mode =

TEST?

HVAC Mode = TEST

Service Test ->

S.STP = YES?

HVAC Mode = SoftStop

Request

Config->UNIT->
RM.CF =2 AND

Inputs->GEN.I->

REMT = ON

HVAC Mode = OFF
(Rem. Sw. Disable)

(Config->HEAT->

HT.TY=4 OR Config->

DEHU->D.SEL=1) AND

(Inputs ->GEN.I->

FRZ.S=ALRM?)

HVAC Mode = Freeze

Stat Trip

Config->SP-> SP.CF

= 1 OR 2

HVAC Mode = OFF

(Static Pres. Fail)

Config->UNIT->

SFS.M=1 OR 2 AND

Config->UNIT->

SFS.S=YES?

HVAC Mode = OFF

(Fan Status Fail)

Unit just waking up

from power reset?

HVAC Mode = OFF

(Starting Up)

Unit shutting down?

HVAC Mode = Shutting

Down

Compressor

contactor welded

on?

HVAC Mode = Comp.

Stuck On

Unit control free to select

normal heating/cooling

HVAC mode

HVAC Mode = OFF

HVAC Mode =

Tempering Vent

HVAC Mode =

Tempering LoCool

HVAC Mode =

Tempering HiCool

HVAC Mode = Re-Heat

HVAC Mode =

Dehumidification

HVAC Mode = Vent

HVAC Mode = Low Cool

HVAC Mode = High Cool

HVAC Mode = Low Heat

HVAC Mode = High Heat

HVAC Mode = Unocc.

Free Cool

No

No

No

No

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

System

Mode

Fire-

Smoke

Control

Exceptions

Unit

control free

to choose

HVAC

Mode

and static pressure

sensor has failed

and supply fan

has failed

Config->BP->

BP.CF=5

AND

HVAC Mode = OFF

(Plenum Pressure Trip)

There is a plenum

pressure switch

error

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

Fig. 4 — Mode Selection