damper position will never exceed the bounds specified by

IAQ.M and EC.MN during IAQ control.

If the building is occupied and the indoor fan is running and

the differential between IAQ and OAQ is less than DAQ.L, the

economizer will remain at IAQ.M. The economizer will not

close completely. The damper position will be 0 when the fan

is not running or the building is unoccupied. The damper posi-

tion may exceed EC.MN in order to provide free cooling.

The ComfortLink™ controls are configured for air quality

sensors which provide 4 mA at 0 ppm and 20 mA at 2000 ppm.

If a sensor has a different range, these bounds must be

reconfigured. These pertinent configurations for ranging the air

quality sensors are IQ.R.L, IQ.R.H, OQ.R.L and OQ.R.H. The

bounds represent the PPM corresponding to 4 mA (low) and

20 mA (high) for IAQ and OAQ, respectively.

If OAQ exceeds the OAQ Lockout Value (OAQ.L), then the

economizer will remain at IAQ.M. This is used to limit the use

of outside air which outdoor air CO

2

levels are above the

OAQ.L limit. Normally a linear control of the damper vs. the

IAQ control signal can be used, but the control also supports

non-linear control. Different curves can be used based on the

Diff.IAQ Responsiveness Variable (IAQ.R). See Fig. 12.
SETTING UP THE SYSTEM — The IAQ configuration op-

tions are under the Local Display Mode Configuration

IAQ.

See Table 59.
IAQ Analog Sensor Config (Configuration

IAQ

AQ.CF

IQ.A.C) — This is used to configure the type of

IAQ position control. It has the following options:
IQ.A.C = 0 (No analog input). If there is no other mini-

mum position control, the economizer minimum position

will be Configuration

IAQ

EC.MN and there will be

no IAQ control.

IQ.A.C = 1 (IAQ analog input). An indoor air (space or

return air) CO

2

sensor is installed. If an outdoor air CO

2

sensor is also installed, or OAQ is broadcast on the CCN,

or if a default OAQ value is used, then the unit can per-

form IAQ control.

IQ.A.C = 2 (IAQ analog input with minimum position

override) — If the differential between IAQ and OAQ

is above Configuration

IAQ

AQ.SP

DAQ.H, the

economizer minimum position will be the IAQ override

position (Configuration

IAQ

AQ.SP

IQ.O.P).

IQ.A.C = 3 (4 to 20 mA minimum position) — With a 4

to 20 mA signal connected to TB202 terminal 11 and 12,

the economizer minimum position will be scaled linearly

from 0% (4 mA) to EC.MN (20 mA).

IQ.A.C = 4 (10K potentiometer minimum position) — With

a 10K linear potentiometer connected to TB202 terminal 11

and 12, the economizer minimum position will be scaled

linearly from 0% (0 kilo-ohms) to EC.MN (10 kilo-ohms).

IAQ Analog Fan Config (Configuration

IAQ

AQ.CF

IQ.A.F) — This configuration is used to configure the control

of the indoor fan. If this option is used then the IAQ sensor

must be in the space and not in the return duct. It has the fol-

lowing configurations:
IQ.A.F = 0 (No Fan Start) — IAQ demand will never

override normal indoor fan operation during occupied or

unoccupied period and turn it on.

IQ.A.F = 1 (Fan On If Occupied) — IAQ demand will

override normal indoor fan operation and turn it on (if

off) only during the occupied period (CV operation with

automatic fan).

IQ.A.F = 2 (Fan On Occupied/Unoccupied) — IAQ

demand will always override normal indoor fan operation

and turn it on (if off) during both the occupied and unoccu-

pied period. For IQ.A.F = 1 or 2, the fan will be turned on as

described above when DAQ is above the DAQ Fan On Set

Point (Configuration

IAQ

AQ.SP

D.F.ON). The fan

will be turned off when DAQ is below the DAQ Fan Off Set

Point (Configuration

IAQ

AQ.SP

D.F.OF). The con-

trol can also be set up to respond to a discrete IAQ input.

The discrete input is connected to TB204 terminal 11 and

12.

Table 59 — Indoor Air Quality Configuration

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

DCV.C

DCV ECONOMIZER SETPOINTS

EC.MN

Economizer Min.Position

0 - 100

%

ECONOMIN

5

IAQ.M

IAQ Demand Vent Min.Pos.

0 - 100

%

IAQMINP

0

O.C.MX

Economizer Min.Flow

0 - 20000

CFM

OACFMMAX

2000

O.C.MN

IAQ Demand Vent Min.Flow

0 - 20000

CFM

OACFMMIN

0

O.C.DB

Econ.Min.Flow Deadband

200 - 1000

CFM

OACFM_DB

400

AQ.CF

AIR QUALITY CONFIGS

IQ.A.C

IAQ Analog Sensor Config

0 - 4

IAQANCFG

0

IQ.A.F

IAQ 4-20 ma Fan Config

0 - 2

IAQANFAN

0

IQ.I.C

IAQ Discrete Input Config

0 - 2

IAQINCFG

0

IQ.I.F

IAQ Disc.In. Fan Config

0 - 2

IAQINFAN

0

OQ.A.C

OAQ 4-20ma Sensor Config

0 - 2

OAQANCFG

0

AQ.SP

AIR QUALITY SETPOINTS

IQ.O.P

IAQ Econo Override Pos.

0 - 100

%

IAQOVPOS

100

IQ.O.C

IAQ Override Flow

0 - 31000

CFM

IAQOVCFM

10000

DAQ.L

Diff.Air Quality LoLimit

0 - 1000

DAQ_LOW

100

DAQ.H

Diff. Air Quality HiLimit

100 - 2000

DAQ_HIGH

700

D.F.OF

DAQ PPM Fan Off Setpoint

0 - 2000

DAQFNOFF

200

D.F.ON

DAQ PPM Fan On Setpoint

0 - 2000

DAQFNON

400

IAQ.R

Diff. AQ Responsiveness

-5 - 5

IAQREACT

0

OAQ.L

OAQ Lockout Value

0 - 2000

OAQLOCK

0

OAQ.U

User Determined OAQ

0 - 5000

OAQ_USER

400

AQ.S.R

AIR QUALITY SENSOR RANGE

IQ.R.L

IAQ Low Reference

0 - 5000

IAQREFL

0

IQ.R.H

IAQ High Reference

0 - 5000

IAQREFH

2000

OQ.R.L

OAQ Low Reference

0 - 5000

OAQREFL

0

OQ.R.H

OAQ High Reference

0 - 5000

OAQREFH

2000

IAQ.P

IAQ PRE-OCCUPIED PURGE

IQ.PG

IAQ Purge

Yes/No

IAQPURGE

No

IQ.P.T

IAQ Purge Duration

5 - 60

min

IAQPTIME

15

IQ.P.L

IAQ Purge LoTemp Min Pos

0 - 100

%

IAQPLTMP

10

IQ.P.H

IAQ Purge HiTemp Min Pos

0 - 100

%

IAQPHTMP

35

IQ.L.O

IAQ Purge OAT Lockout

35 - 70

dF

IAQPNTLO

50