Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 101

Advertising
background image

101

T316 (OAT Below Limit) — If the outside-air temperature

measured by the OAT thermistor (Temperatures

AIR.T

OAT) is below the configurable OAT Low Alert Limit (Con-

figuration

ALLM

OAT.L) for 5 minutes then the alert will

be broadcast.
T317 (OAT Above Limit — If the outside-air temperature

measured by the OAT thermistor (Temperatures

AIR.T

OAT) is above the configurable OAT High Alert Limit

(Configuration

ALLM

OAT.H) for 5 minutes then the alert

will be broadcast.
A400 (Hydronic Freezestat Trip) — If the freezestat for the

hydronic coil trips, the unit goes into emergency mode and

does not allow cooling or heating. The economizer goes to 0%

open. Supply fan operation is enabled. Recovery is automatic

when the switch goes off.
A404 (Fire Shut Down Emergency Mode [fire-smoke]) —

If the fire shutdown input is energized (fire shutdown is in ef-

fect), or if two fire smoke modes are incorrectly energized at

the same time, a Fire Shutdown mode will occur. This is an

emergency mode requiring the complete shutdown of the unit.

Recovery is automatic when the inputs are no longer on.
A405 (Evacuation Emergency Mode) — If the evacuation in-

put on the CEM is energized, an evacuation mode occurs

which flags an alarm. This mode attempts to lower the pressure

of the space to prevent smoke from moving into another space.

This is the reverse of the Pressurization Mode. Closing the

economizer, opening the return-air damper, turning on the

power exhaust, and shutting down the indoor fan will decrease

pressure in the space. Recovery is automatic when the input is

no longer on.
A406 (Pressurization Emergency Mode) — If the pressuriza-

tion input on the CEM is energized, a pressurization mode

occurs which flags an alarm. This mode attempts to raise the

pressure of a space to prevent smoke infiltration from another

space. The space with smoke should be in an Evacuation Mode

attempting to lower its pressure. Opening the economizer, clos-

ing the return air damper, shutting down power exhaust, and

turning the indoor fan on will increase pressure in the space.

Recovery is automatic when the input is no longer on.
A407 (Smoke Purge Emergency Mode) — If the smoke

purge input on the CEM is energized, a smoke purge mode

occurs which flags an alarm. This mode attempts to draw out

smoke from the space after the emergency condition. Opening

the economizer, closing the return-air damper, and turning on

both the power exhaust and indoor fan will evacuate smoke

and bring in fresh air. Recovery is automatic when the input is

no longer on.
T408 (Dirty Air Filter) — If no dirty filter switch is installed,

the switch will read “clean filter” all the time. Therefore the

dirty filter routine runs continuously and diagnoses the input.

Because of the different possible times it takes to generate

static pressure, this routine waits 2 minutes after the fan starts

before the dirty filter switch is monitored. If the dirty filter

switch reads “dirty filter” for 2 continuous minutes, an alert is

generated. No system action is taken. This is a reminder that it

is time to change the filters in the unit. Recovery from this alert

is through a clearing of all alarms (manual) or after the dirty fil-

ter switch reads clean for 30 continuous seconds (automatic).
T409 (Supply Fan Commanded On, Sensed Off Failure)

T409 (Supply Fan Commanded Off, Sensed On Failure)

A409 (Supply Fan Commanded On, Sensed Off Failure)

A409 (Supply Fan Commanded Off, Sensed On Failure) —

Both the alert and the alarm refer to the same failure. The only

difference between the alarm and alert is that in the case where

the supply fan status configuration to shut down the unit is set

to YES (Configuration

UNIT

SFS.S), the alarm will be

generated AND the unit will be shut down. It is possible to

configure Configuration

UNIT

SFS.M to either a switch

or to monitor a 0.2-in. wg rise in duct pressure if the unit is

VAV with duct pressure control (IGV or VFD).

The timings for failure for both are the same and are illus-

trated in the following table:

Recovery is manual. Reason for failure may be a broken fan

belt, failed fan relay or failed supply fan status switch.
T421 (Thermostat Y2 Input On without Y1 On) — If Y2 is

on and Y1 is off then this alert condition is initiated. The

control continues as if both Y1 and Y2 were requested. Alert

recovery will not occur until Y1 is seen. This handles some

conditions of an incorrectly wired thermostat and may prevent

multiple alerts and recoveries from clogging the alarm

histories.
T422 (Thermostat W2 Input On without W1 On) — If W2

is on and W1 is off then this alert condition is initiated.

The control continues as if both W1 and W2 were requested.

Alert recovery will not occur until W1 is seen. This handles

some conditions of an incorrectly wired thermostat and may

prevent multiple alerts and recoveries from clogging the alarm

histories.
T423 (Thermostat Y and W Inputs On) — Simultaneous calls

for heating and cooling are illegal and will be alarmed. Cooling

and heating will be locked out. Recovery is automatic when the

condition no longer exists.
T424 (Thermostat G Input Off On a Cooling Call) — If G is

off and there is a cooling request (Y1 or Y2), then it is possible

the G connection has not been made to the unit terminal block.

An alert is initiated for this condition as continuous fan opera-

tion and manual fan control may not be possible. Cooling is

started, if allowed, and the fan is turned on. The controls do not

diagnose the fan if a heat request (W1 or W2) is in progress.
T430 (Plenum Pressure Safety Switch Trip)

A430 (Plenum Pressure Safety Switch Trip) — If the unit is

configured for fan tracking and the plenum pressure switch

trips, the unit will be instructed to shut down immediately. The

first 2 times the switch trips, the unit will automatically start up

and clear the alert 3 minutes after the switch recovers. The third

time the switch trips, the unit shuts down and calls out the

alarm. Manual reset of the switch (located in the auxiliary con-

trol panel) is required. Software reset is automatic when switch

has been reset. Possible causes are blocked exhaust or return

dampers causing high pressure at the plenum fan.
T500 (Current Sensor Board Failure - A1)

T501 (Current Sensor Board Failure - A2)

T502 (Current Sensor Board Failure - B1)

T503 (Current Sensor Board Failure - B2)
NOTE: These alerts are only applicable to size 105 units.

If the current sensor board malfunctions or is not properly

connected to its assigned digital input, an alert will be generat-

ed. It takes 2 to 4 seconds to log the alert. If the alert is logged,

it stays active for a minimum of 15 seconds to provide the ap-

plication a reasonable time to catch the failure. Compressors

will be not be inhibited by this failure. Recovery is automatic.

Reason for failure may be a faulty current sensor board, incor-

rect wiring, or a damaged input on the MBB control board.

UNIT TYPE/MODE

MINIMUM ON
TIME WAIT

MINIMUM OFF
TIME WAIT

CV (no gas heat)

30 seconds

1 minute

CV (gas heat)

2 minutes

4 minutes

VAV (IGV/no gas heat)

2 minutes

4 minutes

VAV (VFD/no gas heat)

1 minute

1 minute

VAV (IGV/gas heat)

4 minutes

4 minutes

VAV (VFD/gas heat)

3 minutes

4 minutes

Advertising