CONTROLS SET POINT AND CONFIGURATION LOG (cont)

ITEM

EXPANSION

RANGE

DEFAULT

SETTING

HEAT

HEATING CONFIGURATION

HT.CF

Heating Control Type

0 - 4

0

HT.SP

Heating Supply Air Setpt

80 - 120 dF

85

OC.EN

Occupied Heating Enabled

Yes/No

No

LAT.M

MBB Sensor Heat Relocate

Yes/No

No

SG.CF

STAGED GAS CONFIGS

SG.CFHT.ST

Staged Gas Heat Type

0 - 4

0

SG.CFCAP.M

Max Cap Change per Cycle

5 - 45

45

SG.CFM.R.DB

S.Gas DB min.dF/PID Rate

0 - 5

0.5

SG.CFS.G.DB

St.Gas Temp. Dead Band

0 - 5

^F

2

SG.CFRISE

Heat Rise dF/sec Clamp

0.05 - 0.2

0.06

SG.CFLAT.L

LAT Limit Config

0 - 20

^F

10

SG.CFLIM.M

Limit Switch Monitoring?

Yes/No

Yes

SG.CFSW.H.T

Limit Switch High Temp

110 - 180

dF

170

SG.CFSW.L.T

Limit Switch Low Temp

100 - 170

dF

160

SG.CFHT.P

Heat Control Prop. Gain

0 - 1.5

1

SG.CFHT.D

Heat Control Derv. Gain

0 - 1.5

1

SG.CFHT.TM

Heat PID Rate Config

60 - 300 sec

90

HH.CF

HYDRONIC HEAT CONFIGS

HH.CFHW.P

Hydronic Ctl.Prop. Gain

0 - 1.5

1

HH.CFHW.I

Hydronic Ctl.Integ. Gain

0 - 1.5

1

HH.CFHW.D

Hydronic Ctl.Derv. Gain

0 - 1.5

1

HH.CFHW.TM

Hydronic PID Rate Config

15 - 300 sec

90

HH.CFACT.C

HYDR.HEAT ACTUATOR CFGS.

HH.CFACTCSN.1

Hydronic Ht.Serial Num.1

0 - 255

0

HH.CFACTCSN.2

Hydronic Ht.Serial Num.2

0 - 255

0

HH.CFACTCSN.3

Hydronic Ht.Serial Num.3

0 - 255

0

HH.CFACTCSN.4

Hydronic Ht.Serial Num.4

0 - 255

0

HH.CFACTCSN.5

Hydronic Ht.Serial Num.5

0 - 255

0

HH.CFACTCC.A.LM

Hydr.Ht.Ctl.Ang.Lo Limit

0-90

85

SP

SUPPLY STATIC PRESS.CFG.

SP.CF

Static Pressure Config

0-2 (multi-text strings)

0

SP.S

Static Pressure Sensor

Enable/Disable

Disable

SP.LO

Static Press. Low Range

-10 - 0

0

SP.HI

Static Press. High Range

0 - 10

5

SP.SP

Static Pressure Setpoint

0 - 5

1.5

SP.MN

VFD-IGV Minimum Speed

0 - 100

20

SP.MX

VFD-IGV Maximum Speed

0 - 100

100

SP.FS

VFD-IGV Fire Speed Over.

0 - 100

100

SP.RS

Stat. Pres. Reset Config

0 - 4 (multi-text strings)

0

SP.RT

SP Reset Ratio

0.00 - 2.00

0.20

SP.LM

SP Reset Limit

0.00 - 2.00

0.75

SP.EC

SP Reset Econo Position

0 - 100%

5

S.PID

STAT.PRESS.PID CONFIGS

S.PIDSP.TM

Stat.Pres.PID Run Rate

5 - 120

15

S.PIDSP.P

Static Press. Prop. Gain

0 - 5

0.5

S.PIDSP.I

Static Pressure Intg. Gain

0 - 2

0.5

S.PIDSP.D

Static Pressure Derv. Gain

0 - 5

0.3

ACT.C

IGV ACTUATOR CONFIGS

ACTCSN.1

IGV Serial Number 1

0 - 255

0

ACTCSN.2

IGV Serial Number 2

0 - 255

0

ACTCSN.3

IGV Serial Number 3

0 - 255

0

ACTCSN.4

IGV Serial Number 4

0 - 255

0

ACTCSN.5

IGV Serial Number 5

0 - 255

0

ACTCC.A.LM

IGV Cntrl Angle Lo Limit

0-90

25