CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM
EXPANSION
RANGE
DEFAULT
SETTING
HEAT
HEATING CONFIGURATION
→HT.CF
Heating Control Type
0 - 4
0
→HT.SP
Heating Supply Air Setpt
80 - 120 dF
85
→OC.EN
Occupied Heating Enabled
Yes/No
No
→LAT.M
MBB Sensor Heat Relocate
Yes/No
No
→SG.CF
STAGED GAS CONFIGS
→SG.CF→HT.ST
Staged Gas Heat Type
0 - 4
0
→SG.CF→CAP.M
Max Cap Change per Cycle
5 - 45
45
→SG.CF→M.R.DB
S.Gas DB min.dF/PID Rate
0 - 5
0.5
→SG.CF→S.G.DB
St.Gas Temp. Dead Band
0 - 5
^F
2
→SG.CF→RISE
Heat Rise dF/sec Clamp
0.05 - 0.2
0.06
→SG.CF→LAT.L
LAT Limit Config
0 - 20
^F
10
→SG.CF→LIM.M
Limit Switch Monitoring?
Yes/No
Yes
→SG.CF→SW.H.T
Limit Switch High Temp
110 - 180
dF
170
→SG.CF→SW.L.T
Limit Switch Low Temp
100 - 170
dF
160
→SG.CF→HT.P
Heat Control Prop. Gain
0 - 1.5
1
→SG.CF→HT.D
Heat Control Derv. Gain
0 - 1.5
1
→SG.CF→HT.TM
Heat PID Rate Config
60 - 300 sec
90
→HH.CF
HYDRONIC HEAT CONFIGS
→HH.CF→HW.P
Hydronic Ctl.Prop. Gain
0 - 1.5
1
→HH.CF→HW.I
Hydronic Ctl.Integ. Gain
0 - 1.5
1
→HH.CF→HW.D
Hydronic Ctl.Derv. Gain
0 - 1.5
1
→HH.CF→HW.TM
Hydronic PID Rate Config
15 - 300 sec
90
→HH.CF→ACT.C
HYDR.HEAT ACTUATOR CFGS.
→HH.CF→ACTC→SN.1
Hydronic Ht.Serial Num.1
0 - 255
0
→HH.CF→ACTC→SN.2
Hydronic Ht.Serial Num.2
0 - 255
0
→HH.CF→ACTC→SN.3
Hydronic Ht.Serial Num.3
0 - 255
0
→HH.CF→ACTC→SN.4
Hydronic Ht.Serial Num.4
0 - 255
0
→HH.CF→ACTC→SN.5
Hydronic Ht.Serial Num.5
0 - 255
0
→HH.CF→ACTC→C.A.LM
Hydr.Ht.Ctl.Ang.Lo Limit
0-90
85
SP
SUPPLY STATIC PRESS.CFG.
→SP.CF
Static Pressure Config
0-2 (multi-text strings)
0
→SP.S
Static Pressure Sensor
Enable/Disable
Disable
→SP.LO
Static Press. Low Range
-10 - 0
0
→SP.HI
Static Press. High Range
0 - 10
5
→SP.SP
Static Pressure Setpoint
0 - 5
1.5
→SP.MN
VFD-IGV Minimum Speed
0 - 100
20
→SP.MX
VFD-IGV Maximum Speed
0 - 100
100
→SP.FS
VFD-IGV Fire Speed Over.
0 - 100
100
→SP.RS
Stat. Pres. Reset Config
0 - 4 (multi-text strings)
0
→SP.RT
SP Reset Ratio
0.00 - 2.00
0.20
→SP.LM
SP Reset Limit
0.00 - 2.00
0.75
→SP.EC
SP Reset Econo Position
0 - 100%
5
→S.PID
STAT.PRESS.PID CONFIGS
→S.PID→SP.TM
Stat.Pres.PID Run Rate
5 - 120
15
→S.PID→SP.P
Static Press. Prop. Gain
0 - 5
0.5
→S.PID→SP.I
Static Pressure Intg. Gain
0 - 2
0.5
→S.PID→SP.D
Static Pressure Derv. Gain
0 - 5
0.3
→ACT.C
IGV ACTUATOR CONFIGS
→ACTC→SN.1
IGV Serial Number 1
0 - 255
0
→ACTC→SN.2
IGV Serial Number 2
0 - 255
0
→ACTC→SN.3
IGV Serial Number 3
0 - 255
0
→ACTC→SN.4
IGV Serial Number 4
0 - 255
0
→ACTC→SN.5
IGV Serial Number 5
0 - 255
0
→ACTC→C.A.LM
IGV Cntrl Angle Lo Limit
0-90
25