APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
LEN_ACTU
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
Economzr 2 Act.Curr.Pos.
0-100
%
ECON2POS
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
IGV Actuator Current Pos.
0-100
%
IGV_RPOS
IGV Actuator Command Pos
0-100
%
IGV_CPOS
Humidifier Act.Curr.Pos.
0-100
%
HUMDRPOS
Humidifier Command Pos.
0-100
%
HUMDCPOS
Ht.Coil Act.Curr.Pos.
0-100
%
HTCLRPOS
Ht.Coil Command Position
0-100
%
HTCLCPOS
BP 1 Actuator Curr.Pos.
0-100
%
BP1_RPOS
BP 1 Command Position
0-100
%
BP1_CPOS
BP 2 Actuator Curr.Pos.
0-100
%
BP2_RPOS
BP 2 Command Position
0-100
%
BP2_CPOS
Find LEN bus actuator ?
Yes/No
BELSERCH
config
BELx Serial Number-
BELXSNUM
LINKDATA
Supervisory Element #
SUPE-ADR
Supervisory Bus
SUPE-BUS
Supervisory Block Number
BLOCKNUM
Average Occup. Heat Stp.
dF
AOHS
Average Occup. Cool Stp.
dF
AOCS
Average Unocc. Heat Stp.
dF
AUHS
Average Unocc. Cool Stp.
dF
AUCS
Average Zone Temperature
dF
AZT
Average Occup. Zone Temp
dF
AOZT
Linkage System Occupied?
LOCC
Next Occupied Day
LNEXTOCD
Next Occupied Time
LNEXTOCC
Next Unoccupied Day
LNEXTUOD
Next Unoccupied Time
LNEXTUNC
Last Unoccupied Day
LLASTUOD
Last Unoccupied Time
LLASTUNC
MILLIAMP
IAQ milliamps
ma
IAQ_MA
OAQ milliamps
ma
OAQ_MA
SP Reset milliamps
ma
SPRST_MA
4-20 ma Demand Signal
ma
DMDLMTMA
forcible
EDT Reset milliamps
ma
EDTRESMA
OARH milliamps
ma
OARH_MA
SPRH milliamps
ma
SPRH_MA
RARH milliamps
ma
RARH_MA
SACFM milliamps
ma
SACFM_MA
RACFM milliamps
ma
RACFM_MA
OACFM milliamps
ma
OACFM_MA
BP milliamps
ma
BP_MA
SP milliamps
ma
SP_MA
MODES
System Mode…………:
ascii text strings
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Currently Occupied
On/Off
MODEOCCP
Timed Override in effect
On/Off
MODETOVR
DCV resetting min pos
On/Off
MODEADCV
Supply Air Reset
On/Off
MODESARS
Demand Limit in Effect
On/Off
MODEDMLT
Temp.Compensated Start
On/Off
MODETCST
IAQ pre-occ purge active
On/Off
MODEIQPG
Linkage Active - DAV
On/Off
MODELINK
Mech.Cooling Locked Out
On/Off
MODELOCK
HVAC Mode Numerical Form
number
MODEHVAC
OCCDEFME
Current Day, Time & Date:
ascii date & time
TIMEDATE
Occupancy Controlled By:
ascii text
OCDFTXT1
ascii text
OCDFTXT2
ascii text
OCDFTXT3
Currently Occupied
Yes/No
MODE_OCC
Current Occupied Time
STRTTIME
Current Unoccupied Time
ENDTIME
Next Occupied Day & Time
NXTOC_DT
Next Unocc. Day & Time
NXTUN_DT
Last Unocc. Day & Time
PRVUN_DT
Current Occup. Period #
PER_NO
Timed-Override in Effect
Yes/No
OVERLAST
Timed-Override Duration
hours
OVR_HRS