Cl-6, Controls set point and configuration log (cont) – Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 178

CL-6
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
--
- -
-
- -
- -
-
- -
-
- -
-
- -
- - -
CUT
AL
ONG DO
TT
E
D
LINE
CU
T ALONG DO
TT
E
D
LINE
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM
EXPANSION
RANGE
DEFAULT
SETTING
CCN (cont)
→SC.OV→SPT.O
SPT Override Enabled ?
YES/NO
Yes
→SC.OV→T58.O
T58 Override Enabled ?
YES/NO
Yes
→SC.OV→GL.OV
Global Sched. Override ?
YES/NO
No
ALLM
ALERT LIMIT CONFIG.
→SP.L.O
SPT lo alert limit/occ
-10-245 dF
60
→SP.H.O
SPT hi alert limit/occ
-10-245 dF
85
→SP.L.U
SPT lo alert limit/unocc
-10-245 dF
45
→SP.H.U
SPT hi alert limit/unocc
-10-245 dF
100
→SA.L.O
EDT lo alert limit/occ
-40-245 dF
40
→SA.H.O
EDT hi alert limit/occ
-40-245 dF
100
→SA.L.U
EDT lo alert limit/unocc
-40-245 dF
40
→SA.H.U
EDT hi alert limit/unocc
-40-245 dF
100
→RA.L.O
RAT lo alert limit/occ
-40-245 dF
60
→RA.H.O
RAT hi alert limit/occ
-40-245 dF
90
→RA.L.U
RAT lo alert limit/unocc
-40-245 dF
40
→RA.H.U
RAT hi alert limit/unocc
-40-245 dF
100
→OAT.L
OAT lo alert limit
-40-245 dF
-40
→OAT.H
OAT hi alert limit
-40-245 dF
150
→R.RH.L
RARH low alert limit
0-100%
0
→R.RH.H
RARH high alert limit
0-100%
100
→O.RH.L
OARH low alert limit
0-100%
0
→O.RH.H
OARH high alert limit
0-100%
100
→SP.L
SP low alert limit
0-5 "H2O
0
→SP.H
SP high alert limit
0-5 "H2O
2
→BP.L
BP lo alert limit
-0.25-0.25 "H2O
-0.25
→BP.H
BP high alert limit
-0.25-0.25 "H2O
0.25
→IAQ.H
IAQ high alert limit
0-5000
1200
TRIM
SENSOR TRIM CONFIG.
→SAT.T
Air Temp Lvg SF Trim
-10 - 10 ^F
0
→RAT.T
RAT Trim
-10 - 10 ^F
0
→OAT.T
OAT Trim
-10 - 10 ^F
0
→SPT.T
SPT Trim
-10 - 10 ^F
0
→L.SW.T
Limit Switch Trim
-10 - 10 ^F
0
→CCT.T
Air Temp Lvg Evap Trim
-10 - 10 ^F
0
→SP.A.T
Suct.Press.Circ.A Trim
-50 - 50 PSIG
0
→SP.B.T
Suct.Press.Circ.B Trim
-50 - 50 PSIG
0
→DP.A.T
Dis.Press.Circ.A Trim
-50 - 50 PSIG
0
→DP.B.T
Dis.Press.Circ.B Trim
-50 - 50 PSIG
0
SW.LG
SWITCH LOGIC: NO / NC
→FTS.L
Filter Status Inpt-Clean
Open/Close
Open
→IGC.L
IGC Feedback - Off
Open/Close
Open
→RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
Open
→ENT.L
Enthalpy Input - Low
Open/Close
Close
→SFS.L
Fan Status Sw. - Off
Open/Close
Open
→DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
Open
→DL2.L
Dmd.Lmt.Sw.2 - Off
Open/Close
Open
→IAQ.L
IAQ Disc.Input - Low
Open/Close
Open
→FSD.L
Fire Shutdown - Off
Open/Close
Open
→PRS.L
Pressurization Sw. - Off
Open/Close
Open
→EVC.L
Evacuation Sw. - Off
Open/Close
Open
→PRG.L
Smoke Purge Sw. - Off
Open/Close
Open
→DH.LG
Dehumidify Sw. - Off
Open/Close
Open
DISP
DISPLAY CONFIGURATION
→TEST
Test Display LEDs
ON/OFF
Off
→METR
Metric Display
ON/OFF
Off
→LANG
Language Selection
0 - 1 (multi-text strings)
0
→PAS.E
Password Enable
ENABLE/DISABLE
Enable
→PASS
Service Password
0000 - 9999
1111