LEGEND FOR FIG. 15-25

ROOFTOP CONTROL BOARD (RCB) — The RCB has

additional inputs and outputs required for the control of the

unit. All units have an RCB board. See Fig. 27. The board has

9 inputs and 8 outputs. Details can be found in Table 88. The

RCB board is located in the main control box.
ECONOMIZER CONTROL BOARD (ECB) — The ECB

is used on size 075-105 units with high-capacity power exhaust

or return/exhaust fan. See Fig. 27. The ECB board sends a 4 to

20 mA signal to the VFD to control the exhaust fan speed. The

board also has inputs to sense the return fan cfm and supply fan

cfm. This board is located in the main control box. Input and

output assignments are summarized in Table 89.
STAGED GAS HEAT BOARD (SCB) — When optional

staged gas heat is used, the SCB board is installed and controls

additional stages of gas heat. See Fig. 28. The SCB also pro-

vides additional sensors for monitoring of the supply-air and

limit switch temperatures. This board is located in the main

unit control box. The inputs and outputs are summarized in

Table 90.

ACCSY —

Accessory

ACC’Y

Accessory

AF

Airfoil

AN

Analog

APS

Air Pressure Switch

BM

Blower Motor

BR

Blower Relay

C

Compressor Contactor

CB

Compressor Circuit Breaker

CBT

Circuit Breaker, Transformer

CCB

Control Circuit Breaker

CCN

Carrier Comfort Network®

CCT

Cooling Coil Thermistor

CEM

Controls Expansion Module

CH

Crankcase Heater

CM

Combustion Motor

COMP

Compressor

CR

Control Relay

CSB

Current Sensor Board

CV

Constant Volume

DI

Digital Input

DPT

Discharge Pressure Transducer

ECB

Economizer Control Board

ECON

Economizer

EQUIP

Equipment

FU

Fuse

GND

Ground

GVR

Gas Valve Relay

HC

Heater Contactor

HIR

Heat Interlock Relay

HPS

High-Pressure Switch

HS

Hall Effect Sensor

HV

High Voltage

I

Ignitor

IAQ

Indoor Air Quality

IDM

Induced Draft Motor

IFC

Indoor Fan Contactor

IFCB

Indoor Fan Circuit Breaker

IFM

Indoor Fan Motor

IGC

Integrated Gas Controller

IGV

Inlet Guide Vane

IP

Internal Protector

LEI

Local Equipment Interface

LEN

Local Equipment Network

LS

Limit Switch

MBB

Main Base Board

MGV

Main Gas Valve

MMC

Motormaster® Contactor

MMR

Motormaster Relay

MOD PE —

Modulating Power Exhaust

NEC

National Electrical Code

OA

Outdoor Air

OAQ

Outdoor Air Quality

OAT

Outdoor-Air Thermostat

OD

Outdoor

OFC

Outdoor Fan Contactor

OFM

Outdoor Fan Motor

OPT

Option

PE

Power Exhaust

PEC

Power Exhaust Contactor

PECB

Power Exhaust Circuit Breaker

PEM

Power Exhaust Motor

PL

Plug Assembly

PTC

Positive Temperature Coefficient
Power Reference

RA

Return Air

RAT

Return Air Thermistor

RCB

Rooftop Control Board

RF

Return Fan

RS

Rollout Switch

SAT

Supply Air Thermistor

SCB

Staged Gas Control Board

SEN

Sensor

SPT

Suction Pressure Transducer

STDU

Standard Tier Display Unit

TB

Terminal Block

TRAN

Transformer

U

Unloader

VAV

Variable Air Volume

VFD

Variable Frequency Drive

Terminal Block

Terminal (Unmarked)

Terminal (Marked)

Splice

Factory Wiring

Field Wiring

To indicate common potential
only, not to represent wiring.

To indicate factory-installed
option or accessory

CEPL130346-01 HK 50AA029 CE BO 430346

STATUS

LEN

J1

J2

J4

J3

J5

J6

J7

J8

J9

J10

RED LED - STATUS

GREEN LED - LEN (LOCAL EQUIPMENT NETWORK)

YELLOW LED -
CCN (CARRIER COMFORT NETWORK)

INSTANCE JUMPER (SET TO 1)

Fig. 26 — Main Base Board (MBB)