Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 46

Advertising
background image

46

COOL or a HIGH COOL mode and maintain a low or high

cool supply air set point.

C.TYP = 4 (TSTAT – 2 STG)

This configuration will force the control to monitor the ther-

mostat inputs to make a determination of mode.

C.TYP = 5 (SPT – MULTI)

This configuration will force the control to monitor a space

temperature sensor to make a determination of mode. Un-

like traditional 2-stage space temperature control, the unit is

allowed to use multiple stages of cooling control and per-

form VAV style operation. The control will be able to call

out a LOW COOL or a HIGH COOL mode and maintain a

low or high cool supply air set point.

C.TYP = 6 (SPT – 2 STG)

This configuration will force the control to monitor the

space temperature sensor to make a determination of mode and

allow two stages of cooling.
MACHINE DEPENDENT CONFIGURATIONS — Some

configurations are linked to the physical unit and must not be

changed. The configurations are provided in case a field

replacement of a board occurs and the settings are not

preserved by the download process of the new software. The

following configurations apply to all machine control types

(C.TYP) except 4 and 6. These configurations are located at the

local display under Configuration

UNIT. See Table 34.

Table 34 — Machine Dependent Configurations

*Dependent on unit.

Unit Size (SIZE) — There are several unit sizes (tons) for the

Z Series control. Make sure this configuration matches the size

called out by the model number of the unit. This is important as

the cooling stage tables are directly determined based on both

the SIZE and 50.HZ configurations.
50 Hertz Unit? (50.HZ) — Some units are designed to run at

50 Hertz instead of 60 Hertz. Make sure this configuration

matches the frequency called out by the model number of the

unit. This is important as the cooling stage tables are directly

determined based on both the SIZE and 50.HZ configurations.
SET POINTS — The set points for both cooling and heating

are located at the local display under Setpoints. See Table 35.
SUPPLY AIR RESET CONFIGURATION — Supply air

reset can be used to modify the current cooling supply air set

point. Supply air reset is applicable to control types, C.TYP =

1,2,3, and 5. The configurations for reset can be found at the

local display under Configuration

EDT.R. See Table 36.

EDT Reset Configuration (RS.CF) — This configuration ap-

plies to several machine control types (Configuration

UNIT

C.TYP = 1,2,3, and 5).

• 0 = NO RESET

No supply air reset is in effect

• 1 = SPT RESET

Space temperature will be used as the reset control variable

along with both RTIO and LIMT in the calculation of the

final amount of reset to be applied (Inputs

RSET

SA.S.R).

• 2 = RAT RESET

Return-air temperature will be used as the reset control vari-

able along with both RTIO and LIMT in the calculation of

the final amount of reset to be applied (Inputs

RSET

SA.S.R).

• 3 = 3RD PARTY RESET

The reset value is determined by a 4 to 20 mA third party

input. An input of 4 mA would correspond to 0º F reset. An

input of 20 mA would correspond to 20º F reset. Configur-

ing the control for this option will cause RES.S to become

enabled automatically with the CEM board. To avoid

alarms make sure the CEM board and third party input are

connected first before enabling this option.

Reset Ratio (RTIO) — This configuration is used when

RS.CF is set to 1 or 2. For every degree that the controlling

temperature (space/return) falls below the occupied cooling set

point (OCSP), the calculated value of the supply air reset will

rise by the number of degrees as specified by this parameter.
Reset Limit (LIMT) — This configuration is used when

RS.CF is set to 1 or 2. This configuration places a clamp on the

amount of supply air reset that can be applied.
EDT 4-20 mA Reset Input (RES.S) — This configuration is

automatically enabled when Configuration

EDT.R

RS.CF is set to 3 (third party reset).
COOLING CONFIGURATION — Relevant configurations for

mechanical cooling are located at the local display under

Configuration

COOL. See Table 37.

Capacity Threshold Adjust (Z.GN) — This configuration is

used for units using the “SumZ” algorithm for cooling capacity

control (Configuration

UNIT

C.TYP = 1, 2, 3 or 5). The

configuration affects the cycling rate of the cooling stages by

raising or lowering the threshold that demand must build to in

order to add or subtract a stage of cooling.

Normally this configuration should not require any tuning or

adjustment. If there is an application where the unit may be sig-

nificantly oversized and there are indications of high compres-

sor cycles then the Capacity Threshold Adjust (Z.GN) can be

used to adjust the overall logic gain. Normally this is set to 1.0,

but it can be adjusted from 0.5 to 4.0. As the value of Z.GN is

increased, the cycling of cooling stages will be slowed.
Compressor Lockout Temperature (MC.LO) — This config-

uration is the outdoor air temperature setting below which

mechanical cooling is locked out.
Lead/Lag Operation? (L.L.EN) — This configuration allows

for lead/lag compressor operation for the unit. If this configura-

tion is set to Yes, every time cooling capacity drops to 0%, on

the next call for cooling, the control will start up the first

compressor on the circuit which did not start the previous

cooling cycle. If set to No, circuit A will always start first.
Motormaster Control? (M.M.) — The condenser head pressure

control for the unit is managed directly by the ComfortLink™

controls. There is no physical motormaster device in the unit.

This configuration allows the head pressure control sequence to

permit additional cycling control of the condenser fans. Setting

this configuration to YES permits mechanical cooling operation

down to 0° F (–18 C) outdoor temperature. If this configuration

is set to NO, the mechanical cooling system is not suited for

operation below 35 F (1.8 C) outdoor temperature.
Head Pressure Set Point (HPSP) — This is the head pressure

set point used by the ComfortLink controls during condenser

fan, head pressure control.
Enable Compressor A1 (A1.EN) — This configuration is

used to disable the A1 compressor in case of failure.
Enable Compressor A2 (A2.EN) — This configuration is

used to disable the A2 compressor in case of failure.
Enable Compressor B1 (B1.EN) — This configuration is

used to disable the B1 compressor in case of failure.
Enable Compressor B2 (B2.EN) — This configuration is

used to disable the B2 compressor in case of failure.
CSB A1 Feedback Alarm (CS.A1) — This configuration is

used to enable or disable the compressor A1 feedback alarm

(105 ton size units only). This configuration must be enabled at

all times for 105 ton units.

ITEM

EXPANSION

RANGE

CCN

POINT

DEFAULTS

UNIT

UNIT CONFIGURATION

SIZE

Unit Size (30-105) 30 - 105 UNITSIZE

*

50.HZ

50 Hertz Unit ?

Yes/No

UNIT_HZ

*

Advertising