Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 49

Advertising
background image

49

Operating modes are under Operating Modes

MODE.

Cool Mode Evaluation Logic — The first thing the control

determines is whether the unit is in the occupied mode (OCC)

or is in the temperature compensated start mode (T.C.ST). If

the unit is occupied or in temperature compensated start mode,

the occupied cooling set point (OCSP) is used. For all other

modes, the unoccupied cooling set point (UCSP) is used. For

further discussion and simplification this will be referred to as

the “cooling set point.” See Fig. 6.
Demand Level Low Cool On Offset (L.C.ON) — This is the

cooling set point offset added to the cooling set point at which

point a Low Cool mode starts.
Demand Level High Cool On Offset (H.C.ON) — This is the

cooling set point offset added to the “cooling set point plus

L.C.ON” at which point a High Cool mode begins.
Demand Level Low Cool Off Offset (L.C.OF) — This is the

cooling set point offset subtracted from “cooling set point plus

L.C.ON” at which point a Low Cool mode ends.
NOTE: The “high cool end” trip point uses the “low cool off”

(L.C.OF) offset divided by 2.

To enter into a LOW COOL mode, the controlling tempera-

ture must rise above [the cooling set point plus L.C.ON.]

To enter into a HIGH COOL mode, the controlling temper-

ature must rise above [the cooling set point plus L.C.ON plus

H.C.ON.]

To exit out of a LOW COOL mode, the controlling temper-

ature must fall below [the cooling set point plus L.C.ON minus

L.C.OF.]

To exit out of a HIGH COOL mode, the controlling temper-

ature must fall below [the cooling set point plus L.C.ON minus

L.C.OF/2.]
Comfort Trending — In addition to the set points and offsets

which determine the trip points for bringing on and bringing

off cool modes, there are 2 configurations which work to hold

off the transitioning from a low cool to a high cool mode if the

space is cooling down quickly enough. This technique is

referred to as comfort trending and the configurations of

interest are C.T.LV and C.T.TM.
Cool Trend Demand Level (C.T.LV) — This is the change in

demand that must occur within the time period specified by

C.T.TM in order to hold off a HIGH COOL mode regardless

of demand. This is not applicable to VAV control types

(C.TYP=1 and 2) in the occupied period. As long as a LOW

COOL mode is making progress in cooling the space, the con-

trol will hold off on the HIGH COOL mode. This is especially

true for the space sensor machine control types (C.TYP) = 5

and 6, because they may transition into the occupied mode and

see an immediate large cooling demand when the set points

change.
Cool Trend Time (C.T.TM) — This is the time period upon

which the cool trend demand level (C.T.LV) operates and may

hold off staging or a HIGH COOL mode. This is not applica-

ble to VAV control types (C.TYP=1 and 2) in the occupied

period. See the Cool Trend Demand Level section for more

details.
Timeguards In addition to the set points and offsets which

determine the trip points for bringing on and bringing off cool

modes there is a timeguard which enforces a time delay

between the transitioning from a low cool to a high cool mode.

This time delay is 8 minutes. There is a timeguard which

enforces a time delay between the transitioning from a heat

mode to a cool mode. This time delay is 5 minutes.
Supply Air Set Point Control Once the control has deter-

mined that a cooling mode is in effect, the cooling control

point (Run Status

VIEW

CL.C.P) is calculated and is

based upon either Setpoints

SA.HI or Setpoints

SA.LO,

depending on whether a high or a low cooling mode is in

effect, respectively. In addition, if supply air reset is config-

ured, it will also be added to the cooling control point.

Refer to the SumZ Cooling Algorithm section for a discus-

sion of how the Z Series ComfortLink™ controls manage

supply-air temperature and the staging of compressors for these

control types.
C.TYP = 3 and 4 (Thermostat Cool Mode Selection) —

When a thermostat type is selected, the decision making pro-

cess involved in determining the mode is straightforward.

Upon energizing the Y1 input only, the unit HVAC mode will

be LOW COOL. Upon the energizing of both Y1 and Y2 in-

puts, the unit HVAC mode will be HIGH COOL. If just input

G is energized the unit HVAC mode will be VENT and the

supply fan will run.

Selecting the C.TYP = 3 (TSTAT – MULTI) control type

will cause the control to do the following:
• The control will read both the Configuration

UNIT

SIZE and Configuration

UNIT

50.HZ configura-

tion parameters to determine the number of cooling

stages and the pattern for each stage.

• An HVAC mode equal to LOW COOL will cause the

unit to select the Setpoints

SA.LO set point to control

to. An HVAC mode equal to HIGH COOL will cause the

unit to select the Setpoints

SA.HI set point to control

to. Supply air reset (if configured) will be added to either

the low or high cool set point.

• The control will utilize the SumZ cooling algorithm and

control cooling to a supply air set point. See the section

for the SumZ Cooling Algorithm section for information

on controlling to a supply air set point and compressor

staging.
Selecting the C.TYP = 4 (TSTAT – 2 STG) control type

means that only two stages of cooling will be used. An HVAC

mode of LOW COOL will energize one circuit and an HVAC

mode of HIGH COOL will energize both circuits provided the

economizer is not able to provide adequate free cooling. Refer

to the section on Economizer Integration with Mechanical

Cooling for more information.

ITEM

EXPANSION

RANGE

CCN POINT

MODE

MODES CONTROLLING UNIT

OCC

Currently Occupied

ON/OFF MODEOCCP

T.C.ST

Temp.Compensated Start

ON/OFF MODETCST

H.C.ON

L.C. OF/2

L.C.ON

Cooling Setpoint (OCSP,UCSP)

L.C. OF

Lo Cool End

Hi Cool End

Lo Cool Start

Hi Cool Start

Fig. 6 — Cool Mode Evaluation

Advertising