Appendix a — local display tables, Mode — run status – Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 133

133
APPENDIX A — LOCAL DISPLAY TABLES
MODE — RUN STATUS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
PAGE NO.
VIEW
AUTO VIEW OF RUN STATUS
→
HVAC
ascii string spelling out the hvac modes
string
90,92
→
OCC
Occupied ?
YES/NO
OCCUPIED
forcible
90,92
→
MAT
Mixed Air Temperature
dF
MAT
90,92
→
EDT
Evaporator Discharge Tmp
dF
EDT
90,92
→
LAT
Leaving Air Temperature
dF
LAT
90,92
→
EC.C.P
Economizer Control Point
dF
ECONCPNT
90,92
→
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
90,92
→
EC2.P
Economzr Act.Curr.Pos.
0-100
%
ECON2POS
90,92
→
CL.C.P
Cooling Control Point
dF
COOLCPNT
90,92
→
C.CAP
Current Running Capacity
CAPTOTAL
90,92
→
CL.ST
Requested Cool Stage
CL_STAGE
90,92
→
HT.C.P
Heating Control Point
dF
HEATCPNT
90,92
→
HT.ST
Requested Heat Stage
HT_STAGE
90,92
→
H.MAX
Maximum Heat Stages
HTMAXSTG
90,92
ECON
ECONOMIZER RUN STATUS
→
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
69,93
→
EC2.P
Economzr 2 Act.Curr.Pos.
0-100
%
ECON2POS
69,93
→
ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
69,93
→
ACTV
Economizer Active ?
YES/NO
ECACTIVE
69,93
→
DISA
ECON DISABLING CONDITIONS
→
DISA
→
UNV.1
Econ Act. Unavailable?
YES/NO
ECONUNAV
69,93
→
DISA
→
UNV.2
Econ2 Act. Unavailable?
YES/NO
ECN2UNAV
69,93
→
DISA
→
ENTH
Enth. Switch Read High ?
YES/NO
ENTH
69,93
→
DISA
→
DBC
DBC - OAT Lockout?
YES/NO
DBC_STAT
69,93
→
DISA
→
DEW
DEW - OA Dewpt.Lockout?
YES/NO
DEW_STAT
69,93
→
DISA
→
DDBC
DDBD- OAT > RAT Lockout?
YES/NO
DDBCSTAT
69,93
→
DISA
→
OAEC
OAEC- OA Enth Lockout?
YES/NO
OAECSTAT
69,93
→
DISA
→
DEC
DEC - Diff.Enth.Lockout?
YES/NO
DEC_STAT
69,93
→
DISA
→
EDT
EDT Sensor Bad?
YES/NO
EDT_STAT
69,93
→
DISA
→
OAT
OAT Sensor Bad ?
YES/NO
OAT_STAT
69,93
→
DISA
→
FORC
Economizer Forced ?
YES/NO
ECONFORC
69,93
→
DISA
→
SFON
Supply Fan Not On 30s ?
YES/NO
SFONSTAT
69,93
→
DISA
→
CLOF
Cool Mode Not In Effect?
YES/NO
COOL_OFF
69,93
→
DISA
→
OAQL
OAQ Lockout in Effect ?
YES/NO
OAQLOCKD
69,93
→
DISA
→
HELD
Econ Recovery Hold Off?
YES/NO
ECONHELD
69,93
→
DISA
→
DH.DS
Dehumid. Disabled Econ.?
YES/NO
DHDISABL
69,93
→
O.AIR
OUTSIDE AIR INFORMATION
69,93
→
O.AIR
→
OAT
Outside Air Temperature
dF
OAT
forcible
69,93
→
O.AIR
→
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
69,93
→
O.AIR
→
OA.E
Outside Air Enthalpy
OAE
69,93
→
O.AIR
→
OA.D.T
OutsideAir Dewpoint Temp
dF
OADEWTMP
69,93
COOL
COOLING INFORMATION
→
C.CAP
Current Running Capacity
%
CAPTOTAL
92,93
→
CUR.S
Current Cool Stage
COOL_STG
92,93
→
REQ.S
Requested Cool Stage
CL_STAGE
92,93
→
MAX.S
Maximum Cool Stages
CLMAXSTG
92,93
→
DEM.L
Active Demand Limit
%
DEM_LIM
forcible
92,93
→
SUMZ
COOL CAP. STAGE CONTROL
→
SUMZ
→
SMZ
Capacity Load Factor
-100
→
+100
SMZ
92,93
→
SUMZ
→
ADD.R
Next Stage EDT Decrease
^F
ADDRISE
92,93
→
SUMZ
→
SUB.R
Next Stage EDT Increase
^F
SUBRISE
92,93
→
SUMZ
→
R.PCT
Rise Per Percent Capacity
RISE_PCT
92,93
→
SUMZ
→
Y.MIN
Cap Deadband Subtracting
Y_MINUS
92,93
→
SUMZ
→
Y.PLU
Cap Deadband Adding
Y_PLUS
92,93
→
SUMZ
→
Z.MIN
Cap Threshold Subtracting
Z_MINUS
92,93
→
SUMZ
→
Z.PLU
Cap Threshold Adding
Z_PLUS
92,93
→
SUMZ
→
H.TMP
High Temp Cap Override
HI_TEMP
92,93
→
SUMZ
→
L.TMP
Low Temp Cap Override
LOW_TEMP
92,93
→
SUMZ
→
PULL
Pull Down Cap Override
PULLDOWN
92,93
→
SUMZ
→
SLOW
Slow Change Cap Override
SLO_CHNG
92,93
TRIP
MODE TRIP HELPER
→
UN.C.S
Unoccup. Cool Mode Start
UCCLSTRT
93
→
UN.C.E
Unoccup. Cool Mode End
UCCL_END
93
→
OC.C.S
Occupied Cool Mode Start
OCCLSTRT
93
→
OC.C.E
Occupied Cool Mode End
OCCL_END
93
→
TEMP
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
93
→
OC.H.E
Occupied Heat Mode End
OCHT_END
93
→
OC.H.S
Occupied Heat Mode Start
OCHTSTRT
93
→
UN.H.E
Unoccup. Heat Mode End
UCHT_END
93
→
UN.H.S
Unoccup. Heat Mode Start
UCHTSTRT
93
→
HVAC
ascii string spelling out the hvac modes
string
93
LINK
CCN - LINKAGE
→
MODE
Linkage Active - CCN
ON/OFF
MODELINK
94
→
L.Z.T
Linkage Zone Control Tmp
dF
LZT
94
→
L.C.SP
Linkage Curr. Cool Setpt
dF
LCSP
94
→
L.H.SP
Linkage Curr. Heat Setpt
dF
LHSP
94
HRS
COMPRESSOR RUN HOURS
→
HR.A1
Compressor A1 Run Hours
0-999999
HRS
HOURS_A1
config
94
→
HR.A2
Compressor A2 Run Hours
0-999999
HRS
HOURS_A2
config
94
→
HR.B1
Compressor B1 Run Hours
0-999999
HRS
HOURS_B1
config
94
→
HR.B2
Compressor B2 Run Hours
0-999999
HRS
HOURS_B2
config
94
STRT
COMPRESSOR STARTS
→
ST.A1
Compressor A1 Starts
0-999999
CY_A1
config
94
→
ST.A2
Compressor A2 Starts
0-999999
CY_A2
config
94
→
ST.B1
Compressor B1 Starts
0-999999
CY_B1
config
94
→
ST.B2
Compressor B2 Starts
0-999999
CY_B2
config
94
VERS
SOFTWARE VERSION NUMBERS
→
MBB
CESR131292-xx-xx
string
94
→
RCB
CESR131249-xx-xx
string
94
→
ECB
CESR131249-xx-xx
string
94
→
SCB
CESR131226-xx-xx
string
94
→
CEM
CESR131174-xx-xx
string
94
→
ECON
xx-xx-xxx-xxx-xx
string
94
→
IGV
xx-xx-xxx-xxx-xx
string
94
→
HUMD
xx-xx-xxx-xxx-xx
string
94
→
HEAT
xx-xx-xxx-xxx-xx
string
94
→
BP1
xx-xx-xxx-xxx-xx
string
94
→
BP2
xx-xx-xxx-xxx-xx
string
94
→
MARQ
CESR131171-xx-xx
string
94
→
NAVI
CESR130227-xx-xx
string
94