Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 177

CL-5
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
ITEM
EXPANSION
RANGE
DEFAULT
SETTING
IAQ (cont)
→AQ.SP
AIR QUALITY SETPOINTS
→AQ.SP→IQ.O.P
IAQ Econo Override Pos.
0 - 100%
100
→AQ.SP→IQ.O.C
IAQ Override Flow
0 - 31000 CFM
10000
→AQ.SP→DAQ.L
Diff.Air Quality LoLimit
0 - 1000
100
→AQ.SP→DAQ.H
Diff. Air Quality HiLimit
100 - 2000
700
→AQ.SP→D.F.OF
DAQ PPM Fan Off Setpoint
0 - 2000
200
→AQ.SP→D.F.ON
DAQ PPM Fan On Setpoint
0 - 2000
400
→AQ.SP→IAQ.R
Diff. AQ Responsiveness
-5 - 5
0
→AQ.SP→OAQ.L
OAQ Lockout Value
0 - 2000
0
→AQ.SP→OAQ.U
User Determined OAQ
0 - 5000
400
→AQ.S.R
AIR QUALITY SENSOR RANGE
→AQ.S.R→IQ.R.L
IAQ Low Reference
0 - 5000
0
→AQ.S.R→IQ.R.H
IAQ High Reference
0 - 5000
2000
→AQ.S.R→OQ.R.L
OAQ Low Reference
0 - 5000
0
→AQ.S.R→OQ.R.H
OAQ High Reference
0 - 5000
2000
→IAQ.P
IAQ PRE-OCCUPIED PURGE
→IAQ.P→IQ.PG
IAQ Purge
Yes/No
No
→IAQ.P→IQ.P.T
IAQ Purge Duration
5 - 60 min
15
→IAQ.P→IQ.P.L
IAQ Purge LoTemp Min Pos
0 - 100%
10
→IAQ.P→IQ.P.H
IAQ Purge HiTemp Min Pos
0 - 100%
35
→IAQ.P→IQ.L.O
IAQ Purge OAT Lockout
35 - 70 dF
50
HUMD
HUMIDITY CONFIGURATION
→HM.CF
Humidifier Control Cfg.
0 - 4
0
→HM.SP
Humidifier Setpoint
0 - 100%
40
→H.PID
HUMIDIFIER PID CONFIGS
→H.PID→HM.TM
Humidifier PID Run Rate
10 - 120 sec
30
→H.PID→HM.P
Humidifier Prop. Gain
0 - 5
1
→H.PID→HM.I
Humidifier Integral Gain
0 - 5
0.3
→H.PID→HM.D
Humidifier Deriv. Gain
0 - 5
0.3
→ACT.C
HUMIDIFIER ACTUATOR CFGS
→ACTC→SN.1
Humd Serial Number 1
0 - 255
0
→ACTC→SN.2
Humd Serial Number 2
0 - 255
0
→ACTC→SN.3
Humd Serial Number 3
0 - 255
0
→ACTC→SN.4
Humd Serial Number 4
0 - 255
0
→ACTC→SN.5
Humd Serial Number 5
0 - 255
0
→ACTC→C.A.LM
Humd Ctrl Angle Lo Limit
0-90
85
DEHU
DEHUMIDIFICATION CONFIG.
→D.SEL
Dehumidification Config
0-3(multi-text strings)
0
→D.SEN
Dehumidification Sensor
1-3(multi-text strings)
1
→D.EC.D
Econ disable in DH mode?
Yes/No
Yes
→D.V.CF
Vent Reheat Setpt Select
0-1(multi-text strings)
0
→D.V.RA
Vent Reheat RAT offset
0-8 delta F
0
→D.V.HT
Vent Reheat Setpoint
55-95 dF
70
→D.C.SP
Dehumidify Cool Setpoint
40-55 dF
45
→D.RH.S
Dehumidify RH Setpoint
10-90%
55
CCN
CCN CONFIGURATION
→CCNA
CCN Address
1 - 239
1
→CCNB
CCN Bus Number
0 - 239
0
→BAUD
CCN Baud Rate
1 - 5 (multi-text strings)
3
→BROD
CCN BROADCST DEFINITIONS
→BROD→TM.DT
CCN Time/Date Broadcast
ON/OFF
On
→BROD→OAT.B
CCN OAT Broadcast
ON/OFF
Off
→BROD→ORH.B
CCN OARH Broadcast
ON/OFF
Off
→BROD→OAQ.B
CCN OAQ Broadcast
ON/OFF
Off
→BROD→G.S.B
Global Schedule Broadcst
ON/OFF
Off
→BROD→B.ACK
CCN Broadcast Ack'er
ON/OFF
Off
→SC.OV
CCN SCHEDULES-OVERRIDES
→SC.OV→SCH.N
Schedule Number
0 - 99
1
→SC.OV→HOL.T
Accept Global Holidays?
YES/NO
No
→SC.OV→O.T.L.
Override Time Limit
0 - 4 HRS
1
→SC.OV→OV.EX
Timed Override Hours
0 - 4 HRS
0