Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 121

Advertising
background image

121

Table 94 — VFD Terminal Designations

POWER EXHAUST — The units can be equipped with an

optional power exhaust system. The power exhaust fans are

two belt-drive forward-curved fans. On non-modulating sys-

tems, the fans are staged by the ComfortLink™ controls based

on the economizer damper position. For modulating (CV or

VAV) applications, the fans are turned on by the ComfortLink

control based on building pressure sensed by the building pres-

sure transducer. The fan output is modulated via discharge

dampers with LEN communicating actuators to maintain the

building pressure set point.
HIGH CAPACITY POWER EXHAUST (Sizes 075-105

Only) — The power exhaust fans are two belt-driven forward-

curved fans. Operation of the power exhaust is a combination

modulating/staged control. The lead fan is controlled by a VFD

and provides 0 to 50% of total exhaust capability. The second

fan is staged On/Off (for a step of 50% of total exhaust capabil-

ity) according to the VFD output level on fan no. 1.
RETURN/EXHAUST FAN (Sizes 075-105 Only) — The

return/exhaust fan power exhaust assembly consists of one

belt-drive plenum fan. The plenum fan pressurizes the plenum

fan section so that the air can either be discharged horizontally

out the back of the unit or discharged through the return air

section of the economizer.
ECONOMIZER MOTOR(S) — The economizer outside air

and return air dampers are gear-driven dampers without linkag-

es. An LEN communicating economizer motor(s) controls

their position. The motor position is controlled by the MBB

through the LEN communication bus. This allows for accurate

control of the motors as well as feedback information and diag-

nostics information. The control has a self-calibration routine

that allows the motor position to be configured at initial unit

start-up. The motor(s) is located on the economizer and can be

reached through the filter access door.
THERMISTORS AND PRESSURE TRANSDUCERS —

The unit is equipped with several thermistors for measurement

of temperatures. The thermistors are summarized in Table 95.

The units have two pressure transducers that are connected

to the low side of the system. These two pressure transducers

measure the low side pressure and are used for low pressure

protection and coil freeze protection.

The units also have two pressure transducers that are con-

nected to the high side of the system. These two pressure trans-

ducers measure the discharge pressure and are used to cycle the

condenser fans to maintain head pressure.

By using the high and low side pressure transducers, the

ComfortLink controls display the high and low side pressures

and saturation temperatures and a normal gage set is not

required.
SMOKE DETECTOR — The units can be equipped with an

accessory smoke detector located in the return air. The detector

is wired to the ComfortLink controls and, if activated, will stop

the unit by means of a special fire mode. The smoke detector

can also be wired to an external alarm system through TB201

terminals 5 and 6. The sensor is located in the return air section.
FILTER STATUS SWITCH — The units can be equipped

with an optional filter status switch. The switch measures the

pressure drop across the filters and closes when an adjustable

pressure set point is exceeded. The sensor is located in the re-

turn air section behind the filter access door.

TERMINAL

FUNCTION

U1
V1
W1

Three-Phase Main Circuit Input Power Supply

U2
V2

Three-Phase AC Output to Motor, 0 V to

W2

Maximum Input Voltage Level

X1-11 (GND)
X1-12 (COMMON)
Factory-supplied jumper
X1-10 (24 VDC)
X1-13 (DI-1)

Run (factory-supplied jumper)

X1-10 (24 VDC)

Start Enable 1 (factory-supplied jumper). When

X1-16 (DI-4)

opened the drive goes to emergency stop.

X1-2 (AI-1)
X1-3 (AGND)

Factory wired for 4 to 20 mA remote input

Fig. 31 — VFD Wiring

+

Advertising