Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 125

Advertising
background image

125

SERVICE

Service Access —

All unit components can be reached

through clearly labeled hinged access doors. These doors are

not equipped with tiebacks, so if heavy duty servicing is need-

ed, either remove them or prop them open to prevent accidental

closure.

Each door is held closed with 3 latches. The latches are

secured to the unit with a single

1

/

4

-in. –20 x

1

/

2

-in. long bolt.

See Fig. 34.

To open, loosen the latch bolt using a

7

/

16

-in. wrench. Pivot

the latch so it is not in contact with the door. Open the door. To

shut, reverse the above procedure.
NOTE: Disassembly of the top cover may be required under

special service circumstances. It is very important that the ori-

entation and position of the top cover be marked on the unit

prior to disassembly. This will allow proper replacement of the

top cover onto the unit and prevent rainwater from leaking into

the unit.

COMPRESSORS
Sizes 030-050 — Access to the compressors is through the

doors on the condenser end of the unit. This door also provides

access to the discharge and suction service valves, the crank-

case heaters, and the high-pressure and low-pressure switches.

Compressor no. 1 is always the compressor on the left when

facing main control box.
Sizes 055-105 — The oil pump end (compressor access) of

each compressor is readily accessible from sides of unit. Access

the motor end of the compressor through the condenser end of the

unit or by removing compressor.
LIQUID SERVICE VALVES, FILTER DRIERS, AND

SIGHT GLASSES
Sizes 030-050 — Access to these components is through the

access panel on the right side of the unit. See Fig. 35. There is

also a Schrader port in each suction line that is accessible

through this same panel. When charging unit, route service line

through the round holes and replace panel to minimize air

bypass.
Sizes 055-105 — Access to these components is from the side

of the unit.
SUPPLY-FAN MOTORS, PULLEYS, AND BELTS — Ac-

cess to these components is through the 2 doors labeled FAN

SECTION on each side of the unit.
POWER EXHAUST MOTORS, PULLEYS, AND BELTS —

Access to these components is through the door below the side

economizer hoods on both sides of the unit. See Fig. 36.
RETURN AIR FILTERS — Access to these filters is through

the door marked FILTER SECTION.
UNIT CONTROL BOX — Access to this component is

through the doors marked ELECTRICAL SECTION on the

condenser end of the unit.
GAS HEAT SECTION (48Z Only) — Access to the gas heat

section is through the door labeled HEAT SECTION on the

right side of the unit (when facing return air end). See Fig. 37

and 38.

All gas system components are in the gas section.

MAIN BURNERS (48Z Only) — At the beginning of each

heating season, inspect for deterioration due to corrosion or

other causes. Observe the main burner flames and adjust if nec-

essary. See Gas System Adjustment section on page 131.
FLUE GAS PASSAGEWAYS (48Z Only) — The flue col-

lector box and heat exchanger cells may be inspected by

removing heat exchanger access panel, flue box cover, and

main burner assembly (Fig. 39). Refer to Main Burners

Removal and Replacement section on page 131 for burner

removal sequence. If cleaning is required, remove heat

exchanger baffles and clean tubes with a wire brush.

Use caution with ceramic heat exchanger baffles. When in-

stalling retaining clip, be sure the center leg of the clip extends

inward toward baffle. See Fig. 40.
COMBUSTION-AIR BLOWERS (48Z Only) — Clean peri-

odically to assure proper airflow and heating efficiency.

Inspect blower wheel every fall and periodically during heat-

ing season. For the first heating season, inspect blower wheel

bi-monthly to determine proper cleaning frequency.

To inspect blower wheel, remove heat exchanger access

panel. Shine a flashlight into opening to inspect wheel. If clean-

ing is required, remove motor and wheel assembly by remov-

ing screws holding motor mounting plate to top of combustion

fan housing (Fig. 41). The motor and wheel assembly will slide

up and out of the fan housing. Remove the blower wheel from

the motor shaft and clean with a detergent or solvent. Replace

motor and wheel assembly.
ECONOMIZER DAMPER MOTOR(S) — On units so

equipped, the economizer motor(s) is located in the mixing

box section. Access to it is through the door labeled FILTER

SECTION.
CONDENSER FANS AND FAN MOTORS — Remove the

wire fan guard on top of the unit to gain access to the condenser

fans and motors.
INLET GUIDE VANE MOTOR — The inlet guide vane mo-

tor is located on the evaporator-fan sled on the side opposite the

fan motor. See Fig. 42A and 42B. Access is through the door

labeled FAN SECTION.
25% OUTDOOR-AIR DAMPER — Access to adjust the

damper is through the hoods. Remove filters to gain access into

unit to adjust linkage arms.
MODULATING POWER EXHAUST DAMPER MOTOR —

The modulating power exhaust damper motor is located in the

return-air end of the unit.

The motor is accessed through the small door below the side

economizer hoods on the left side of the unit. See Fig. 36.
RETURN-AIR FILTERS — Access to these filters is through

the door marked FILTER SECTION. Filters in upper and low-

er bag filter tracks can only be removed from the right side of

the unit.

IMPORTANT: After servicing is completed, make sure

door is closed and relatched properly, and that the

latches are tight. Failure to do this can result in water

leakage into the indoor-air section of the unit.

IMPORTANT: When replacing panel, be sure to prop-

erly secure it in order to prevent water from being drawn

into the unit.

Advertising