APPENDIX E — MODE SELECTION PROCESS (cont)

HVAC mode:

("Vent ")

This is a normal operation mode where no heating

or cooling is required and outside air is being

delivered to the space to control IAQ levels.
HVAC mode:

("Low Cool ")

This is a normal cooling mode when a low cooling

demand exists.
HVAC mode:

("High Cool ")

This is a normal cooling mode when a high

cooling demand exists.
HVAC mode:

("Low Heat ")

This is a normal heating mode when a low

heating demand exists.
HVAC mode:

("High Heat ")

This is a normal heating mode when a low

heating demand exists.

HVAC mode:

("Unocc. Free Cool")

In this mode the unit will operate in cooling but

will be using the economizer for free cooling.

Entering this mode will depend on the status of the

outside air. The unit can be configured for outside

air changeover, differential dry bulb changeover,

outside air enthalpy changeover, differential

enthalpy changeover, or a custom arrangement

of enthalpy/dewpoint and dry bulb. See the

Economizer section for further details.

}

NOTE: There is also a transitional mode whereby the machine

may be waiting for relay timeguards to expire before shutting

the machine completely down:

HVAC mode:

("Shutting Down ")