Table 52 — Static Pressure Control Configuration

Static Pressure Configuration (SP.CF) — This variable is

used to configure the use of ComfortLink™ controls for static

pressure control. It has the following options:
0 (None) — No static pressure control by ComfortLink

controls. This would be used for a constant volume (CV)

application when static pressure control is not required or for a

VAV application if there will be third-party control of the VFD

or IGV. In this latter case, a suitable means of control must be

field installed.
1 (VFD Control) — This will enable the use of ComfortLink

controls for static pressure control via a supply fan VFD.
2 (IGV Control) — This will enable the use of ComfortLink

controls for static pressure control via supply fan inlet guide

vanes (IGV).
Static Pressure Sensor (SP.S) — This variable enables the use

of a supply duct static pressure sensor. This must be enabled to

use ComfortLink controls for static pressure control. If using a

third-party control for the VFD or IGV, this should be disabled.
Static Pressure Low Range (SP.LO) — This is the minimum

static pressure that the sensor will measure. For most sensors

this will be 0 in. wg. The ComfortLink controls will map this

value to a 4 mA sensor input.
Static Pressure High Range (SP.HI) — This is the maximum

static pressure that the sensor will measure. Commonly this

will be 5 in. wg. The ComfortLink controls will map this value

to a 20 mA sensor input.
Static Pressure Set Point (SP.SP) — This is the static pres-

sure control point. It is the point against which the

ComfortLink controls compares the actual measured supply

duct pressure for determination of the error that is used for PID

control. Generally one would set SP.SP to the minimum value

necessary for proper operation of air terminals in the condi-

tioned space at all load conditions. Too high of a value will

cause unnecessary fan motor power consumption at part-load

conditions and/or noise problems. Too low a value will result in

insufficient airflow. Additional information will be found on

page 63, under Static Pressure Reset.

VFD-IGV Minimum Speed (SP.MN) — This is the mini-

mum speed for the supply fan VFD or the minimum opening

for the supply fan IGV. Typically the value is chosen to main-

tain a minimum level of ventilation.
NOTE: Most VFDs have a built-in minimum speed adjustment

which must be configured for 0% when using ComfortLink

controls for static pressure control.
VFD-IGV Maximum Speed (SP.MX) — This is the maxi-

mum speed for the supply fan VFD or the maximum opening

for the supply fan IGV. This is usually set to 100%.
VFD-IGV Fire Speed Override (SP.FS) — This is the speed

that the supply fan VFD or the supply fan IGV will use during

the fire modes; pressurization, evacuation and purge. This is

usually set to 100%.
Static Pressure Reset Configuration (SP.RS) — This option

is used to configure the static pressure reset function. When

SP.RS = 0, there is no static pressure reset via an analog input.

When SP.RS = 1, there is static pressure reset based on the

CEM 4-20MA input and ranged from 0 to 3 in. wg. When

SP.RS = 2, there is static pressure reset based on RAT and

defined by SP.RT and SP.LM. When SP.RS = 3, there is

static pressure reset based on SPT and defined by SP.RT and

SP.LM. When SP.RS = 4, there is VFD speed control where

0 mA = 0% speed and 20 mA = 100% (SP.MN and SP.MX will

override).
Static Pressure Reset Ratio (SP.RT) — This option defines

the reset ratio in terms of static pressure versus temperature.

The reset ratio determines how much is the static pressure

reduced for every degree below set point for RAT or SPT.
Static Pressure Reset Limit (SP.LM) — This option defines

the maximum amount of static pressure reset that is allowed.

This is sometimes called a “clamp.”
NOTE: Resetting static pressure via RAT and SPT is primarily

a constant volume application which utilizes a VFD. The rea-

soning is that there is significant energy savings in slowing

down a supply fan as opposed to running full speed with

supply air reset. Maintaining the supply air set point and

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

SP

SUPPLY STATIC PRESS.CFG.

SP.CF

Static Pressure Config

0, 1, 2

STATICFG

0

SP.S

Static Pressure Sensor

Enable/Disable

SPSENS

Disable

SP.LO

Static Press. Low Range

–10 - 0

in. W.C.

SP_LOW

0

SP.HI

Static Press. High Range

0 - 10

in. W.C.

SP_HIGH

5

SP.SP

Static Pressure Setpoint

0 - 5

in. W.C.

SPSP

1.5

SP.MN

VFD-IGV Minimum Speed

0 - 100

%

STATPMIN

20

SP.MX

VFD-IGV Maximum Speed

0 - 100

%

STATPMAX

100

SP.FS

VFD-IGV Fire Speed Over.

0 - 100

%

STATPFSO

100

SP.RS

Stat. Pres. Reset Config

0 - 4

SPRSTCFG

0

SP.RT

SP Reset Ratio (

″/dF)

0 - 2.00

SPRRATIO

0.2

SP.LM

SP Reset Limit in iwc (

″)

0 - 2.00

SPRLIMIT

0.75

SP.EC

SP Reset Econo.Position

0 - 100

%

ECONOSPR

5

S.PID

STAT.PRESS.PID CONFIGS

S.PIDSP.TM

Static Press. PID Run Rate

5 - 120

sec

SPIDRATE

15

S.PIDSP.P

Static Press. Prop. Gain

0 - 5

STATP_PG

0.5

S.PIDSP.I

Static Pressure Intg. Gain

0 - 2

STATP_IG

0.5

S.PIDSP.D

Static Pressure Derv. Gain

0 - 5

STATP_DG

0.3

ACT.C

IGV ACTUATOR CONFIGS

ACTCSN.1

IGV Serial Number 1

0 - 255

IGV_SN1

0

ACTCSN.2

IGV Serial Number 2

0 - 255

IGV_SN2

0

ACTCSN.3

IGV Serial Number 3

0 - 255

IGV_SN3

0

ACTCSN.4

IGV Serial Number 4

0 - 255

IGV_SN4

0

ACTCSN.5

IGV Serial Number 5

0 - 255

IGV_SN5

0

ACTCC.A.LM

IGV Cntrl Angle Lo Limit

0-90

deg

IGV_CALM

25