APPENDIX B — CCN TABLES (cont)

MAINTENANCE DISPLAY TABLES (cont)

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

PRESBLDG

Building Pressure

"H2O

BP

Return Air CFM

CFM

RACFM

Supply Air CFM

CFM

SACFM

Power Exhaust Relay 1

On/Off

PE1

Power Exhaust Relay 2

On/Off

PE2

BP 1 Actuator Curr.Pos.

%

BP1_RPOS

BP 1 Command Position

%

BP1_CPOS

BP 2 Actuator Curr.Pos.

%

BP2_RPOS

BP 2 Command Position

%

BP2_CPOS

Exhaust Fan VFD Speed

%

EFAN_VFD

Building Pressure Setp.

"H2O

BPSP

config

BP Setpoint Offset

^"H2O

BPSO

config

Fan Track Learn Enable

Yes/No

DCFM_CFG

config

Fan Track Learn Rate

min

DCFMRATE

config

Fan Track Initial DCFM

CFM

DCFMSTRT

config

Fan Track Max Clamp

CFM

DCFM_MAX

config

Fan Track Max Correction

CFM

DCFM_ADJ

config

Fan Track Internl EEPROM

CFM

DCFM_OFF

config

Fan Track Reset Internal

DCFMRSET

config

Fan Track Internal RAM

CFM

DCFM_RAM

Fan Track Control D.CFM

CFM

DELTACFM

PRESDUCT

Static Pressure

"H2O

SP

Supply Fan VFD Speed

%

SFAN_VFD

IGV Actuator Current Pos

%

IGV_RPOS

IGV Actuator Command Pos

%

IGV_CPOS

Static Pressure Setpoint

"H2O

SPSP

config

Static Pressure Reset

SPRESET

forcible

STAGEGAS

Heating Mode………..:

ascii text strings

Requested Heat Stage

HT_STAGE

Heating Control Point

HEATCPNT

Staged Gas LAT Sum

dF

LAT_SGAS

Staged Gas LAT 1

dF

LAT1SGAS

Staged Gas LAT 2

dF

LAT2SGAS

Staged Gas LAT 3

dF

LAT3SGAS

Staged Gas Limit Sw.Temp

dF

LIMSWTMP

Heat PID Timer

sec

HTSGTIMR

Staged Gas Capacity Calc

%

HTSGCALC

Current Running Capacity

%

HTSG_CAP

Proportional Cap. Change

HTSG_P

Derivative Cap. Change

HTSG_D

Maximum Heat Stages

HTMAXSTG

Hi Limit Switch Tmp Mode

LIMTMODE

LAT Cutoff Mode

LATCMODE

Capacity Clamp Mode

CAPMODE

STRTHOUR

Compressor A1 Run Hours

hours

HR_A1

config

Compressor A2 Run Hours

hours

HR_A2

config

Compressor B1 Run Hours

hours

HR_B1

config

Compressor B2 Run Hours

hours

HR_B2

config

Compressor A1 Starts

CY_A1

config

Compressor A2 Starts

CY_A2

config

Compressor B1 Starts

CY_B1

config

Compressor B2 Starts

CY_B2

config

SUMZ

Cooling Control Point

dF

COOLCPNT

Mixed Air Temperature

dF

MAT

Evaporator Discharge Tmp

dF

EDT

Return Air Temperature

dF

RAT

forcible

Outside Air Temperature

dF

OAT

forcible

Econo Damper Current Pos

%

ECONOPOS

Economzr 2 Act.Curr.Pos.

%

ECON2POS

Capacity Threshold Adjst

Z_GAIN

config

Capacity Load Factor

SMZ

Next Stage EDT Decrease

ADDRISE

Next Stage EDT Increase

SUBRISE

Rise Per Percent Capacity

RISE_PCT

Cap Deadband Subtracting

Y_MINUS

Cap Deadband Adding

Y_PLUS

Cap Threshold Subtracting

Z_MINUS

Cap Threshold Adding

Z_PLUS

High Temp Cap Override

On/Off

HI_TEMP

Low Temp Cap Override

On/Off

LOW_TEMP

Pull Down Cap Override

On/Off

PULLDOWN

Slow Change Cap Override

On/Off

SLO_CHNG