Table 63 — CCN Configuration

Alert Limit Configuration —

The ALLM submenu is

used to configure the alert limit set points. A list is shown in

Table 64.
SPT Low Alert Limit/Occ (SP.L.O) — If the space tempera-

ture is below the configurable occupied SPT Low Alert Limit

(SP.L.O), then Alert 300 will be generated and the unit will be

stopped. The alert will automatically reset.
SPT High Alert Limit/Occ (SP.H.O) — If the space tempera-

ture is above the configurable occupied SPT High Alert Limit

(SP.H.O), then Alert 301 will be generated and the unit will be

stopped. The alert will automatically reset.
SPT Low Alert Limit/Unocc (SP.L.U) — If the space tem-

perature is below the configurable unoccupied SPT Low Alert

Limit (SP.L.U), then Alert 300 will be generated and the unit

will be stopped. The alert will automatically reset.
SPT High Alert Limit/Unocc (SP.H.U) — If the space tem-

perature is above the configurable unoccupied SPT High Alert

Limit (SP.H.U), then Alert 301 will be generated and the unit

will be stopped. The alert will automatically reset.
EDT Low Alert Limit/Occ (SA.L.O) — If the space tempera-

ture is below the configurable occupied evaporator discharge

temperature (EDT) Low Alert Limit (SA.L.O), then Alert 302

will be generated and cooling operation will be stopped but

heating operation will continue. The alert will automatically

reset.
EDT High Alert Limit/Occ (SA.H.O) — If the space temper-

ature is above the configurable occupied EDT High Alert Limit

(SA.H.O), then Alert 303 will be generated and heating opera-

tion will be stopped but cooling operation will continue. The

alert will automatically reset.
EDT Low Alert Limit/Unocc (SA.L.U) — If the space tem-

perature is below the configurable unoccupied EDT Low Alert

Limit (SA.L.U), then Alert 302 will be generated and cooling

operation will be stopped but heating operation will continue.

The alert will automatically reset.
EDT High Alert Limit/Unocc (SA.H.U) — If the space tem-

perature is above the configurable unoccupied EDT High Alert

Limit (SA.H.U), then Alert 303 will be generated and heating

operation will be stopped but cooling operation will continue.

The alert will automatically reset.
RAT Low Alert Limit/Occ (RA.L.O) — If the return-air tem-

perature is below the configurable occupied RAT Low Alert

Limit (RA.L.O), then Alert 304 will be generated and internal

routines will be modified. Unit operation will continue but

VAV heating operation will be disabled. The alert will automat-

ically reset.
RAT High Alert Limit/Occ (RA.H.O) — If the return-air

temperature is above the configurable occupied RAT High

Alert Limit (RA.H.O), then Alert 305 will be generated and

operation will continue. The alert will automatically reset.
RAT Low Alert Limit/Unocc (RA.L.U) — If the return-air

temperature is below the configurable unoccupied RAT Low

Alert Limit (RA.L.U), then Alert 304 will be generated. Unit

operation will continue but VAV heating operation will be dis-

abled. The alert will automatically reset.
RAT High Alert Limit/Unocc (RA.H.U) — If the return-air

temperature is above the configurable unoccupied RAT High

Alert Limit (RA.H.U), then Alert 305 will be generated. Oper-

ation will continue. The alert will automatically reset.
OAT Low Alert Limit (OAT.L) — If the outside-air tempera-

ture measured by the OAT thermistor is below the configurable

OAT Low Alert Limit (OAT.L) then alert T316 will be

generated.
OAT High Alert Limit (OAT.H) — If the outside-air temper-

ature measured by the OAT thermistor is above the config-

urable OAT High Alert Limit (OAT.H) then alert T317 will be

generated
RARH Low Alert Limit (R.RH.L) — If the unit is config-

ured to use a return air relative humidity sensor (Configura-

tion

UNIT

SENS

RRH.S), and the measured level is

below the configurable RH Low Alert Limit (R.RH.L), then

Alert 308 will occur. The unit will continue to run and the alert

will automatically reset.
RARH High Alert Limit (R.RH.H) — If the unit is config-

ured to use a return air relative humidity sensor (Configura-

tion

UNIT

SENS

RRHS), and the measured level is

above the configurable RARH High Alert Limit (R.RH.H),

then Alert 309 will occur. The unit will continue to run and the

alert will automatically reset.
OARH Low Alert Limit (O.RH.L) — If the unit is config-

ured to use an outdoor air relative humidity sensor (Configura-

tion

ECON

ORH.S) and the measured level is below the

configurable OARH Low Alert Limit (O.RH.L), then econo-

mizer operation will be disabled. The unit will continue to run

and the alert will automatically reset.
OARH High Alert Limit (O.RH.H) — If the unit is config-

ured to use a return air relative humidity sensor (Configura-

tion

ECON

ORH.S) and the measured level is above the

configurable OARH High Alert Limit (O.RH.H), then econo-

mizer operation will be disabled. The unit will continue to run

and the alert will automatically reset.
Supply Duct Pressure Low Alert Limit (SP.L) — If the unit

is a VAV unit with a supply duct pressure sensor and the mea-

sured supply duct static pressure is below the configurable SP

Low Alert Limit (DP.L), then Alert 310 will occur. The unit

will continue to run and the alert will automatically reset.

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

CCN

CCN CONFIGURATION

CCNA

CCN Address

1 - 239

CCNADD

1

CCNB

CCN Bus Number

0 - 239

CCNBUS

0

BAUD

CCN Baud Rate

1 - 5

CCNBAUDD

3

BROD

CCN BROADCST DEFINITIONS

TM.DT

CCN Time/Date Broadcast

ON/OFF

CCNBC

On

OAT.B

CCN OAT Broadcast

ON/OFF

OATBC

Off

ORH.B

CCN OARH Broadcast

ON/OFF

OARHBC

Off

OAQ.B

CCN OAQ Broadcast

ON/OFF

OAQBC

Off

G.S.B

Global Schedule Broadcst

ON/OFF

GSBC

Off

B.ACK

CCN Broadcast Ack'er

ON/OFF

CCNBCACK

Off

SC.OV

CCN SCHEDULES-OVERRIDES

SCH.N

Schedule Number

0 - 99

SCHEDNUM

1

HOL.T

Accept Global Holidays?

YES/NO

HOLIDAYT

No

O.T.L.

Override Time Limit

0 - 4

HRS

OTL

1

OV.EX

Timed Override Hours

0 - 4

HRS

OVR_EXT

0

SPT.O

SPT Override Enabled ?

YES/NO

SPT_OVER

Yes

T58.O

T58 Override Enabled ?

YES/NO

T58_OVER

Yes

GL.OV

Global Sched. Override ?

YES/NO

GLBLOVER

No