MAT Calc Config (MAT.S) This configuration gives the

user three options in the processing of the mixed-air tempera-

ture (MAT) calculation:

MAT.S = 0

The control will not attempt to learn MAT over time. The

control will simply calculate MAT based on the position of

the economizer, outside and return air temperature, linearly.

MAT.S = 1

The control will attempt to learn MAT over time. Any time

the system is in a vent mode and the economizer stays at a

particular position for long enough, MAT = EDT. Using

this, the control has an internal table whereby it can more

closely determine the true MAT value.

MAT.S = 2

The control will stop learning and use whatever the control

has already learned. Using this setting infers that the control

has spent some time set to MAT.S = 1.
First set MAT.S = 1. Then go into the Service Test mode,

turn on the fan and open the economizer to a static position for

5 minutes. Move to several positions (20%,40%,60%,80%). It

is important that the difference between return and outside

temperature be greater than 5 degrees. (The greater the delta,

the better). When done, set MAT.S = 2 and the system has been

commissioned.
Reset MAT Table Entries? (MAT.R) This configuration

allows the user to reset the internally stored MAT learned

configuration data back to the default values. The defaults are

set to a linear relationship between the economizer damper

position and OAT and RAT in the calculation of MAT.
SumZ Overrides There are a number of overrides to the

SumZ algorithm which may add or subtract stages of cooling.
• High Temp Cap Override (H.TMP)

• Low Temp Cap Override (L.TMP)

• Pull Down Cap Override (PULL)

• Slow Change Cap Override (SLOW)
Economizer Trim Override The unit may drop stages of

cooling when the economizer is performing free cooling and

the configuration Configuration

ECON

E.TRM is set to

Yes. The economizer controls to the same supply air set point

as mechanical cooling does for SumZ when E.TRM = Yes.

This allows for much tighter temperature control as well as cut-

ting down on the cycling of compressors.

For a long cooling session where the outside-air tempera-

ture may drop over time, there may be a point at which the

economizer has closed down far enough were the unit could

remove a cooling stage and open up the economizer further to

make up the difference.
Mechanical Cooling Lockout (Configuration

COOL

MC.LO)This configuration allows a configurable outside-

air temperature set point below which mechanical cooling will

be completely locked out.
DEMAND LIMIT CONTROL — Demand Limit Control

may override the cooling algorithm and clamp or shed

cooling capacity during run time. The term Demand Limit

Control refers to the restriction of the machine capacity

to control the amount of power that a machine will use.

Demand limit control is intended to interface with an external

Loadshed Device either through CCN communications, exter-

nal switches, or 4 to 20 mA input.

The control has the capability of loadshedding and limiting

in 3 ways:
• Two discrete inputs tied to configurable demand limit set

point percentages.

• An external 4 to 20 mA input that can reset capacity back

linearly to a set point percentage.

• CCN loadshed functionality.
NOTE: It is also possible to force the demand limit variable

(Run Status

COOL

DEM.L).

To use Demand Limiting, select the type of demand limiting

to use. This is done with the Demand Limit Select configura-

tion (Configuration

DMD.L

DM.L.S).

To view the current demand limiting currently in effect,

look at Run Status

COOL

DEM.L.

The configurations associated with demand limiting can be

viewed at the local display at Configuration

DMD.L. See

Table 41.
Demand Limit Select (DM.L.S) — This configuration deter-

mines the type of demand limiting.
• 0 = NONE — Demand Limiting not configured.

• 1 = 2 SWITCHES — This will enable switch input

demand limiting using the switch inputs connected to the

CEM board. Connections should be made to TB204

terminals 1, 2, 3, and 4.

• 2 = 4 to 20 mA — This will enable the use of a remote 4

to 20 mA demand limit signal. The CEM module must

be used. The 4 to 20 mA signal must come from an exter-

nally sourced controller and should be connected to

TB203 terminals 2 and 3.

• 3 = CCN LOADSHED — This will allow for loadshed

and red lining through CCN communications.

Two-Switch Demand Limiting (DM.L.S = 1) — This type of

demand limiting utilizes two discrete inputs:
Demand Limit Switch 1 Setpoint (D.L.S1) — Dmd Limit

Switch Setpoint 1 (0-100% total capacity)
Demand Limit 2 Setpoint (D.L.S2) — Dmd Limit Switch

Setpoint 2 (0-100% total capacity)

The state of the discrete switch inputs can be found at the lo-

cal display:
Inputs

GEN.I

DL.S1

Inputs

GEN.I

DL.S2

The following table illustrates the demand limiting (Run

Status

COOL

DEM.L) that will be in effect based on the

logic of the applied switches:

4-20 mA Demand Limiting (DM.L.S = 2) — If the unit has

been configured for 4 to 20 mA demand limiting, then the

Inputs

4-20

DML.M value is used to determine the

amount of demand limiting in effect (Run Status

COOL

DEM.L). The Demand Limit at 20 mA (D.L.20) configuration

must be set. This is the configured demand limit correspond-

ing to a 20 mA input (0 to 100%).

The value of percentage reset is determined by a linear

interpolation from 0% to “D.L.20”% based on the Inputs

4-20

DML.M input value.

The following examples illustrate the demand limiting

(Run Status

COOL

DEM.L) that will be in effect based on

amount of current seen at the 4 to 20 mA input, DML.M.

Switch Status

Run Status

COOL

DEM.L = 1

Inputs

GEN.I

DL.S1 = OFF

Inputs

GEN.I

DL.S2 = OFF

100%

Inputs

GEN.I

DL.S1= ON

Inputs

GEN.I

DL.S2 = OFF

Configuration

DMD.L

D.L.S1

Inputs

GEN.I

DL.S1= ON

Inputs

GEN.I

DL.S2 = ON

Configuration

DMD.L

D.L.S2

Inputs

GEN.I

DL.S1= OFF

Inputs

GEN.I

DL.S2 = ON

Configuration

DMD.L

D.L.S2

D.L.20 = 80%

D.L.20 = 80%

D.L.20 = 80%

DML.M = 4mA

DML.M = 12 mA

DML.M = 20mA

DEM.L = 100%

DEM.L = 90%

DEM.L = 80%