Appendix b — ccn tables (cont) – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 146

Advertising
background image

146

APPENDIX B — CCN TABLES (cont)

CONFIG TABLES (cont)

SERVICE-CONFIG TABLES

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

DEFAULT

SCHEDOVR

Schedule Number

0-99

SCHEDNUM

0

Accept Global Holidays?

Yes/No

HOLIDAYT

No

Override Time Limit

0-4

hours

OTL

1

Timed Override Hours

0-4

hours

OVR_EXT

0

Accepting an Override:
SPT Override Enabled ?

Yes/No

SPT_OVER

Yes

T58 Override Enabled ?

Yes/No

T58_OVER

Yes

Allowed to Broadcast a
Global Sched. Override ?

Yes/No

GLBLOVER

No

SET_PNT

Occupied Heat Setpoint

55-80

dF

OHSP

68

Occupied Cool Setpoint

55-80

dF

OCSP

75

Unoccupied Heat Setpoint

40-80

dF

UHSP

55

Unoccupied Cool Setpoint

75-95

dF

UCSP

90

Heat-Cool Setpoint Gap

2-10

deltaF

HCSP_GAP

5

VAV Occ. Cool On Delta

0-25

deltaF

VAVOCON

3.5

VAV Occ. Cool Off Delta

1-25

deltaF

VAVOCOFF

2

Supply Air Setpoint

45-75

dF

SASP

55

Supply Air Setpoint Hi

45-75

dF

SASP_HI

55

Supply Air Setpoint Lo

45-75

dF

SASP_LO

60

Heating Supply Air Setpt

90-145

dF

SASPHEAT

85

Tempering Purge SASP

-20-80

dF

TEMPPURG

50

Tempering in Cool SASP

5-75

dF

TEMPCOOL

5

Tempering in Vent Occ SASP

-20-80

dF

TEMPVOCC

65

Tempering Vent Unocc. SASP

-20-80

dF

TEMPVUNC

50

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

DEFAULT

ALLM

SPT lo alert limit/occ

-10-245

dF

SPLO

60

SPT hi alert limit/occ

-10-245

dF

SPHO

85

SPT lo alert limit/unocc

-10-245

dF

SPLU

45

SPT hi alert limit/unocc

-10-245

dF

SPHU

100

EDT lo alert limit/occ

-40-245

dF

SALO

40

EDT hi alert limit/occ

-40-245

dF

SAHO

100

EDT lo alert limit/unocc

-40-245

dF

SALU

40

EDT hi alert limit/unocc

-40-245

dF

SAHU

100

RAT lo alert limit/occ

-40-245

dF

RALO

60

RAT hi alert limit/occ

-40-245

dF

RAHO

90

RAT lo alert limit/unocc

-40-245

dF

RALU

40

RAT hi alert limit/unocc

-40-245

dF

RAHU

100

OAT lo alert limit

-40-245

dF

OATL

-40

OAT hi alert limit

-40-245

dF

OATH

150

RARH low alert limit

0-100

%

RRHL

0

RARH high alert limit

0-100

%

RRHH

100

OARH low alert limit

0-100

%

ORHL

0

OARH high alert limit

0-100

%

ORHH

100

SP low alert limit

0-5

"H2O

SPL

0

SP high alert limit

0-5

"H2O

SPH

2

BP lo alert limit

-0.25-0.25

"H2O

BPL

-0.25

BP high alert limit

-0.25-0.25

"H2O

BPH

0.25

IAQ high alert limit

0-5000

IAQH

1200

BP__

Building Press. Config

0-5

BLDG_CFG

0

Building Pressure Sensor

Enable/Disable

BPSENS

Disable

Bldg. Press. (+/-) Range

0.10 - 0.25

"H2O

BP_RANGE

0.25

Building Pressure Setp.

-0.25 - 0.25

"H2O

BPSP

0.05

BP Setpoint Offset

0 - 0.5

^"H2O

BPSO

0.05

Power Exhaust On Setp.1

0 - 100

%

PES1

25

Power Exhaust On Setp.2

0 - 100

%

PES2

75

Bldg.Pressure Fire Speed

0 - 100

%

BLDGPFSO

100

Bldg.Pressure Min. Speed

0 - 100

%

BLDGPMIN

10

Bldg.Pressure Max. Speed

0 - 100

%

BLDGPMAX

100

BP 1 Actuator Max Pos.

85 - 100

%

BP1SETMX

100

BP 2 Actuator Max Pos.

85 - 100

%

BP2SETMX

100

BP Hi Cap VFD Clamp Val.

5 - 25

%

BLDGCLMP

10

BP Hi Cap VFD Clamp Time

30 - 255

sec

BLDGWAIT

60

Fan Track Learn Enable

Yes/No

DCFM_CFG

NO

Fan Track Learn Rate

5-60

min

DCFMRATE

15

Fan Track Initial DCFM

-20000 - 20000

CFM

DCFMSTRT

2000

Fan Track Max Clamp

0 - 20000

CFM

DCFM_MAX

4000

Fan Track Max Correction

0 -20000

CFM

DCFM_ADJ

1000

Fan Track Internl EEPROM

-20000 - 20000

CFM

DCFM_OFF

0

Fan Track Internal RAM

-20000 - 20000

CFM

DCFM_RAM

0

Fan Track Reset Internal

Yes/No

DCFMRSET

No

Supply Air CFM Config

1 - 2 (multi-text strings)

SCFM_CFG

1