Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 61

Advertising
background image

61

Setting up the System — The relevant set points for temper-

ing are located at the local display under Setpoints:

Operation — First, the unit must be in a vent mode, a low cool,

or a high cool HVAC mode to be considered for a tempering

mode. Secondly, the tempering mode is only allowed when the

rooftop is configured for staged gas or hydronic heating (Con-

figuration

HEAT

HT.CF=3 or 4).

If the control is configured for staged gas or hydronic heat-

ing and the control is in a vent, low cool, or high cool HVAC

mode, and the rooftop control is in a situation where the econo-

mizer must maintain a minimum position/minimum cfm, then

the evaporator discharge temperature (EDT) will be monitored.

If the EDT falls below a particular trip point then the tempering

mode may be called out:

HVAC mode = “Tempering Vent”

HVAC mode = “Tempering LoCool”

HVAC mode = “Tempering HiCool”
The decision making/selection process for the tempering

trip set point is as follows:
• If an HVAC cool mode is in effect, then the vent trip

point is T.CL.

• If in a pre-occupied purge mode (Operating Modes

MODE

IAQ.P=ON), then the trip point is T.PRG.

• If in an occupied mode (Operating Modes

MODE

IAQ.P=ON), then the trip point is TEMPVOCC.

• For all other cases, the trip point is TEMPVUNC.
NOTE: The unoccupied economizer free cooling does not

qualify as a HVAC cool mode as it is an energy saving feature

and has its own OAT lockout already. The unoccupied free

cooling mode (HVAC mode = Unocc. Free Cool) will override

any unoccupied vent mode from triggering a tempering mode.

If OAT is above the chosen tempering set point, tempering

will not be allowed. Additionally, tempering mode is locked

out if any stages of mechanical cooling are present.

A minimum amount of time must pass before calling out

any tempering mode. In effect, the EDT must fall below the

trip point value –1° F continuously for a minimum of 2 min-

utes. Also, at the end of a mechanical cooling cycle, there must

be a minimum 10 minutes of delay allowed before considering

a tempering during vent mode in order to allow any residual

cooling to dissipate from the evaporator coil.

If the above conditions are met, the algorithm is free to

select the tempering mode (MODETEMP).

If a tempering mode becomes active, the modulating heat

source (staged gas or hot water) will attempt to maintain

leaving-air temperature (LAT) at the tempering set point used

to trigger the tempering mode. The technique for modulation of

set point for staged gas and hydronic heat is the same as in a

heat mode. More information regarding the operation of heat-

ing can be referenced in the Heating Control section.

Recovery from a tempering mode (MODETEMP) will

occur when the EDT rises above the trip point. On any change

in HVACMODE, the tempering routine will re-assess the tem-

pering set point which may cause the control to continue or exit

tempering mode.

Static Pressure Control —

Variable air volume (VAV)

air-conditioning systems must provide varying amounts of air

to the conditioned space. As air terminals downstream of the

unit modulate their flows, the unit must simply maintain

control over duct static pressure in order to accommodate the

needs of the terminals, and therefore to meet the varying

combined airflow requirement. The unit design includes two

alternative optional means of accommodating this requirement.

This section describes the technique by which this control takes

place.

A unit intended for use in a VAV system can be equipped

with either an optional variable frequency drive (VFD) or inlet

guide vanes (IGV) for the supply fan. The speed of the fan or

the position of the IGV can be controlled directly by the

ComfortLink™ controls. A transducer is used to measure duct

static pressure. The signal from the transducer is received by

the RCB board and is then used in a PID control routine that

outputs a 4 to 20 mA signal to the VFD, or a digital LEN signal

to the IGV.

Generally only VAV systems utilize static pressure control.

It is required because as the system VAV terminals modulate

closed when less air is required, there must be a means of

controlling airflow from the unit, thereby effectively prevent-

ing overpressurization and its accompanying problems.

The three most fundamental configurations for most appli-

cations are Configuration

SP

SP.CF, which is the static

pressure control type, Configuration

SP

SP.S, used to

enable the static pressure sensor, and Configuration

SP

SP.SP, the static pressure set point to be maintained.

OPERATION — On units equipped with either VFD or IGV

and a proper static pressure sensor, when SP.CF, SP.S and

SP.SP are configured, a PID routine periodically measures the

duct static pressure and calculates the error from set point. This

error at any point in time is simply the duct static pressure set

point minus the measured duct static. The error becomes the

basis for the Proportional term of the PID. The routine also cal-

culates the integral of the error over time, and the derivative

(rate of change) of the error. A value is calculated as a result of

this PID routine, and this value is then used to create an output

signal used to adjust the IGV or VFD to maintain the static

pressure set point.

Static pressure reset is the ability to force a lowering of the

static pressure set point through an external control signal.

Explained in detail further below, the control supports this in

two separate ways; through a 4 to 20 mA signal input wired to

TB203 terminals 6 and 7 (thereby facilitating third party

control), or via CCN.

In the latter case, this feature leverages the communications

capabilities of VAV systems employing ComfortID™ termi-

nals under linkage. The system dynamically determines and

maintains an optimal duct static pressure set point based on

the actual load conditions in the space. This can result in a

significant reduction in required fan energy by lowering the set

point to only the level required to maintain adequate airflow

throughout the system.
SETTING UP THE SYSTEM — The options for static

pressure control are found under the Local Display Mode

Configuration

SP. See Table 52.

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

DEFAULT

T.PRG

Tempering
Purge SASP

–20-80

dF

TEMPPURG 50

T.CL

Tempering in
Cool SASP

5-75

dF

TEMPCOOL

5

T.V.OC

Tempering Vent
Occ SASP

–20-80

dF

TEMPVOCC

65

T.V.UN

Tempering Vent
Unocc. SASP

–20-80

dF

TEMPVUNC

50

Advertising