Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 119

Advertising
background image

119

Table 92 — Field Terminal Connections

LEGEND

BOARD

NO.

TERMINAL

NUMBER

DESCRIPTION

TYPE

TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box)

11

L1 power supply

208-230/460/575/380/-3-60, 400-3-50

TB1

12

L2 power supply

208-230/460/575/380/-3-60, 400-3-50

13

L3 power supply

208-230/460/575/380/-3-60, 400-3-50

NEUTRAL (in Main Control Box)

Neutral

1

Neutral Power

CCN COMMUNICATIONS (in Main Control Box)

Comm Port

1

LEN +

5 vdc, logic

2

LEN C

5 vdc, logic

3

LEN –

5 vdc, logic

4

24 vac

24 vac

5

CCN +

5 vdc, logic

7

CCN c

5 vdc, logic

7

CCN –

5 vdc, logic

8

Grd

ground

TB201 - FIELD CONNECTIONS (in Main Control Box)

TB201

1

Remote Occupied/Economizer Enable 24 vac out

external contact (maximum 24 vac, 3 A)

2

Remote Occupied/Economizer Enable 24 vac in

external contact (maximum 24 vac, 3 A)

3

Not Used

4

OD Enthalpy Switch in

24 vac

5

Fire Shut Down

external contact (maximum 24 vac, 3 A)

6

Fire Shut Down

external contact (maximum 24 vac, 3 A)

7

VAV Heater Interlock Relay

external contact (maximum 24 vac, 3 A)

8

VAV Heater Interlock Relay

external contact (maximum 24 vac, 3 A)

9

Humidifier Output, Ground

external contact (maximum 24 vac, 3 A)

10

Humidifier Output, 24 VAC

external contact (maximum 24 vac, 3 A)

11

Unit Alarm Output

external contact (maximum 24 vac, 3 A)

12

Unit Alarm Output

external contact (maximum 24 vac, 3 A)

13

Smoke Detector Alarm Input

external contact (maximum 24 vac, 3 A)

14

Smoke Detector Alarm Input

external contact (maximum 24 vac, 3 A)

15

Not Used

16

Not Used

TB202 - THERMOSTAT CONNECTIONS (in Main Control Box)

TB202

1

Thermostat R

24 vac output

2

Thermostat G

24 vac input

3

Thermostat W2

24 vac input

4

Thermostat W1

24 vac input

5

Thermostat Y2

24 vac input

6

Thermostat Y1

24 vac input

7

Not Used

8

Space Sensor TH

Thermistor input

9

Space Sensor COM

Thermistor input

10

Space Sensor Offset SW

Thermistor input

11

Indoor Air IAQ Remote Sensor/Remote
Pot/Remote 4-20 mA

Thermistor input or externally powered 4 to 20 mA when used with
180 ohm resistor

12

Indoor Air IAQ Remote Sensor/Remote
Pot/Remote 4-20 mA

Thermistor input or externally powered 4 to 20 mA when used with
180 ohm resistor

13

Not Used

14

Not Used

15

Not Used

16

Not Used

TB203 - FIELD CONNECTIONS (in Main Control Box)

TB203

1

Ground

ground

2

Demand Limit 4-20 mA (+)

4 to 20 mA loop power

3

Demand Limit 4-20 mA (-)

4 to 20 mA loop power

4

Supply Air Reset 4-20 mA (+)

4 to 20 mA loop power

5

Supply Air Reset 4-20 mA (-)

4 to 20 mA signal

6

Outdoor Air IAQ 4-20 mA (+)

4 to 20 mA loop power

7

Outdoor Air IAQ 4-20 mA (-)

4 to 20 mA signal

8

Space Humidity 4-20 mA (+)

4 to 20 mA loop power

9

Space Humidity 4-20 mA (-)

4 to 20 mA signal

10

Not Used

11

Not Used

12

Not Used

13

Not Used

14

Not Used

15

Not Used

16

Not Used

IAQ

Indoor Air Quality

VAV — Variable Air Volume