Table 77 — Discharge Pressure

Transducer Pressure (psig) vs Voltage

Forcing Inputs and Outputs —

Many of variables

may be forced both from the CCN and directly at the local

display. This can be useful during diagnostic testing and also

during operation, typically as part of an advanced third party

control scheme. Please see Appendix A and B.
NOTE: In the case of a power reset, any force levels in effect

at the time of the power reset will be cleared.
CONTROL LEVEL FORCING — If any of the following

points are forced with a priority level of 7 (consult CCN litera-

ture for a description of priority levels), the software clears the

force from the point if it has not been written to or forced again

within the timeout periods defined below:

Run Status Menu —

The Run Status menu provides the

user important information about the unit. The Run Status table

can be used to troubleshoot problems and to help determine

how and why the unit is operating.
AUTO VIEW OF RUN STATUS — The Auto View of Run

Status display table provides the most important unit informa-

tion. The HVAC Mode (Run Status

VIEW

HVAC) in-

forms the user what HVAC mode the unit is currently in. Refer

to the Modes section on page 40 for information on HVAC

modes. The occupied status, unit temperatures, unit set points,

and stage information can also be shown. See Table 78.
Run Status

VIEW

HVAC — Displays the current HVAC

Mode(s) by name. HVAC Modes include:

OFF

VENT

HIGH HEAT

STARTING UP

HIGH COOL

FIRE SHUT DOWN

SHUTTING DOWN

LOW COOL

PRESSURIZATION

DISABLED

UNOCC FREE COOL EVACUATION

SOFTSTOP REQUEST TEMPERING HICOOL SMOKE PURGE
REM SW DISABLE

TEMPERING LOCOOLDEHUMIDIFICATION

COMP STUCK ON

TEMPERING VENT

RE-HEAT

TEST

LOW HEAT

Run Status

VIEW

OCC — Displays the current occupan-

cy status of the control.
Run Status

VIEW

MAT — Displays the current value for

mixed-air temperature. This value is calculated based on

return-air and outside-air temperatures and economizer damper

position.
Run Status

VIEW

EDT — Displays the current evapora-

tor discharge air temperature during Cooling modes. This value

is read at the supply air thermistor location (or at cooling coil

thermistor array if unit is equipped with hydronic heating coil).
Run Status

VIEW

LAT — Displays the current leaving-

air temperature during Vent and Hydronic Heating modes. This

value is read at the supply air thermistor location.
Run Status

VIEW

EC.C.P — Displays the current econo-

mizer control point value (a target value for air temperature

leaving the evaporator coil location).
Run Status

VIEW

ECN.P — Displays the current actual

economizer position (in percentage open).
Run Status

VIEW

EC2.P — Displays the current posi-

tion of actuator no. 2 (in percentage open).
Run Status

VIEW

CL.C.P — Displays the current cool-

ing control point (a target value for air temperature leaving the

evaporator coil location).
Run Status

VIEW

C.CAP — Displays the current

amount of unit cooling capacity (in percent of maximum).

Compare to staging tables in Appendix C.
Run Status

VIEW

CL.ST — Displays the current number

of requested cooling stages. Compare to staging tables in

Appendix C and to C.CAP above.
Run Status

VIEW

HT.C.P — Displays the current heat-

ing control point, for use with staged gas control option only (a

target value for air temperature leaving the supply duct).
Run Status

VIEW

HT.ST — Displays the current number

of heating stages active (for staged gas control option only).

Compare to following point.
Run Status

VIEW

H.MAX — Displays the maximum

number of heat stages available for this model.

PRESSURE

(psig)

VOLTAGE DROP

(v)

0

0.466

10

0.564

20

0.663

30

0.761

40

0.860

50

0.958

60

1.056

70

1.155

80

1.253

90

1.352

100

1.450

110

1.549

120

1.647

130

1.745

140

1.844

150

1.942

160

2.041

170

2.139

180

2.238

190

2.336

200

2.434

210

2.533

220

2.631

230

2.730

240

2.828

250

2.927

260

3.025

270

3.124

280

3.222

290

3.320

300

3.419

310

3.517

320

3.616

330

3.714

340

3.813

350

3.911

360

4.009

370

4.108

380

4.206

390

4.305

400

4.403

410

4.502

420

4.600

Temperatures

AIR.T

OAT Outside Air Temperature

30 minutes

Temperatures

AIR.T

RAT Return Air Temperature

3 minutes

Temperatures

AIR.T

SPT Space Temperature

3 minutes

Inputs

RSET

SP.RS

Static Pressure Reset

30 minutes

Inputs

REL.H

OA.RH

Outside Air Relative Humidity 30 minutes

Inputs

AIR.Q

OAQ

Outside Air Quality

30 minutes