The economizer’s reported and commanded positions

are also viewable, as well as outside air temperature, relative

humidity, enthalpy and dew point temperature.

The following information can be found under the Local

Display Mode Run Status

ECON. See Table 57.

Economizer Control Point Determination Logic — Once the

economizer is allowed to provide free cooling, the economizer

must determine exactly what set point it should try to maintain.

The set point the economizer attempts to maintain when “free

cooling” is located at Run Status

VIEW

EC.C.P. This is

the economizer control point.

The control selects set points differently, based on the

control type of the unit. This control type can be found at

Configuration

UNIT

C.TYP. There are 6 types of control.

C.TYP = 1

VAV-RAT

C.TYP = 2

VAV-SPT

C.TYP = 3

TSTAT Multi-Staging

C.TYP = 4

TSTAT 2 Stage

C.TYP = 5

SPT Multi-Staging

C.TYP = 6

SPT 2 Stage

If the economizer is not allowed to do free cooling, then

EC.C.P = 0.

If the economizer is allowed to do free cooling and the

Unoccupied Free Cooling Mode is ON, then EC.C.P =

Setpoints

SASP + Inputs

RSET

SA.S.R.

If the economizer is allowed to do free cooling and the

Dehumidification mode is ON, then EC.C.P = the Cooling

Control Point (Run Status

VIEW

CL.C.P).

If the C.TYP is either 4 or 6, and the unit is in a cool mode,

then:
If Stage = 0

EC.C.P = the Cooling Control Point (Run

Status

VIEW

CL.C.P)

If Stage = 1

53.0 + economizer suction pressure reset

If Stage = 2

48.0 + economizer suction pressure reset

NOTE: To check the current cooling stage go to Run Status

Cool

CUR.S.

If the C.TYP is either 1,2,3 or 5, and the unit is in a cool

mode, then EC.C.P = the Cooling Control Point (Run Status

VIEW

CL.C.P).

Economizer Suction Pressure Reset for Two-Stage

Cooling — If the unit’s control type is set to either 2-stage ther-

mostat or 2-stage space temperature control, then there is no

cooling control point. Stages 1 and 2 are brought on based on

demand, irrespective of the evaporator discharge temperature.

In this case, the economizer monitors suction pressure and

resets the economizer control point accordingly in order to

protect the unit from freezing. For those conditions when the

economizer opens up fully but is not able to make set point, and

then a compressor comes on, it is conceivable that the coil

might freeze. This can be indirectly monitored by checking suc-

tion pressure. Rather than fail a circuit, the control will attempt

to protect the unit by resetting the economizer control point

until the suction pressure rises out of freezing conditions.

If either circuit’s suction pressure drops to within 5 psig

of the low suction pressure trip point, the control will start

adding reset to the economizer control point if it is active. It

will be possible to reset the control point upwards, 10 degrees

(2 degrees per psig), between the low suction pressure trip

point of 48 psig and 5 psig above it. If this does not work, and if

the suction pressure drops below the trip point, then the control

will further reset the control point 1 degree every 15 seconds

up to a maximum of 10 degrees. The resulting effect will be to

warm up the mixed air entering the evaporator, thereby raising

the suction pressure.

Building Pressure Control —

This control sequence

provides control of the building pressure through the modulat-

ing flow rate functions of one of the modulating power exhaust

options or through management of the return fan option. This

function also provides control of the constant volume 2-stage

power exhaust option. See below for available power exhaust

options for each unit model.

LEGEND

Table 57 — Economizer Run Status Table

UNIT

CONSTANT

VOLUME
2-STAGE

MODULATING

POWER

EXHAUST

S.O.

VFD*

HIGH

CAPACITY

POWER

EXHAUST†

RETURN/

EXHAUST†

48ZG, 50ZG,Z2

X

X

S.O.

NA

NA

48ZN, 50ZN,Z3

NA

X

S.O.

NA

NA

48ZT,ZW
50ZT,ZW,ZX,ZZ

NA

NA

NA

STD

NA

48Z6,Z8
50Z6,Z7,Z8,Z9

NA

NA

NA

NA

STD

X

Available as Factory Option

S.O.

Available as Special Order

NA

Not Available on this Unit

STD

Standard Feature on this Unit

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

EC2.P

Economzr 2 Act.Curr.Pos.

0-100

%

ECON2POS

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

ACTV

Economizer Active ?

YES/NO

ECACTIVE

DISA

ECON DISABLING CONDITIONS

UNV.1

Econ Act. Unavailable?

YES/NO

ECONUNAV

UNV.2

Econ2 Act. Unavailable?

YES/NO

ECN2UNAV

ENTH

Enth. Switch Read High ?

YES/NO

ENTH

DBC

DBC - OAT Lockout?

YES/NO

DBC_STAT

DEW

DEW - OA Dewpt.Lockout?

YES/NO

DEW_STAT

DDBC

DDBD- OAT > RAT Lockout?

YES/NO

DDBCSTAT

OAEC

OAEC- OA Enth Lockout?

YES/NO

OAECSTAT

DEC

DEC - Diff.Enth.Lockout?

YES/NO

DEC_STAT

EDT

EDT Sensor Bad?

YES/NO

EDT_STAT

OAT

OAT Sensor Bad ?

YES/NO

OAT_STAT

FORC

Economizer Forced ?

YES/NO

ECONFORC

SFON

Supply Fan Not On 30s ?

YES/NO

SFONSTAT

CLOF

Cool Mode Not In Effect?

YES/NO

COOL_OFF

OAQL

OAQ Lockout in Effect ?

YES/NO

OAQLOCKD

HELD

Econ Recovery Hold Off?

YES/NO

ECONHELD

DH.DS

Dehumid. Disabled Econ.?

YES/NO

DHDISABL

O.AIR

OUTSIDE AIR INFORMATION

OAT

Outside Air Temperature

dF

OAT

forcible

OA.RH

Outside Air Rel. Humidity

%

OARH

forcible

OA.E

Outside Air Enthalpy

OAE

OA.D.T

Outside Air Dewpoint Temp

dF

OADEWTMP

*Single VFD controlling both fan

motors.
†Single VFD controlling one fan
motor and staging of the second
fan motor.